TeSys D Contactor TeSys Deca, 3P(3 NO), AC-3/AC-3e, 0 to 440V, 32A, 60VDC standard coil
Item Number: LC1D32ND
Specifications
Design
Range
- TeSys
- TeSys Deca
Range of product
Product or component type
Warranty
Physical
[ue] rated operational voltage
- power circuit: <= 690 V AC 25...400 Hz
- power circuit: <= 300 V DC
[ie] rated operational current
- 32 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
- 50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
- 32 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
Mechanical durability
Electrical durability
- 1.65 Mcycles 32 A AC-3 at Ue <= 440 V
- 1.4 Mcycles 50 A AC-1 at Ue <= 440 V
- 1.65 Mcycles 32 A AC-3e at Ue <= 440 V
Connections - terminals
- control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
- control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end
- control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
- power circuit: screw clamp terminals 1 2.5-10 mm² - cable stiffness: flexible without cable end
- power circuit: screw clamp terminals 2 2.5-10 mm² - cable stiffness: flexible without cable end
- power circuit: screw clamp terminals 1 1-10 mm² - cable stiffness: flexible with cable end
- power circuit: screw clamp terminals 2 1.5-6 mm² - cable stiffness: flexible with cable end
- power circuit: screw clamp terminals 1 1.5-10 mm² - cable stiffness: solid without cable end
- power circuit: screw clamp terminals 2 2.5-10 mm² - cable stiffness: solid without cable end
Insulation resistance
Mounting support
- rail
- plate
Standards
- CSA C22.2 No 14
- EN 60947-4-1
- EN 60947-5-1
- IEC 60947-4-1
- IEC 60947-5-1
- UL 60947-4-1
- IEC 60335-1:Clause 30.2
- IEC 60335-2-40:Annex JJ
- UL 60335-2-40:Annex JJ
- CSA C22.2 No 60947-4-1
Product certifications
- UL
- CCC
- CSA
- Marine
- UKCA
- EAC
- CB Scheme
Ip degree of protection
Climatic withstand
- conforming to IACS E10 exposure to damp heat
- conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Height
Width
Depth
Net weight
Reach regulation
Eu rohs directive
Mercury free
China rohs regulation
Rohs exemption information
Environmental disclosure
Circularity profile
Others
Package 1 bare product quantity
Substance regulation data deliverable
Life cycle assessment data
Device short name
Contactor application
- resistive load
- motor control
Utilisation category
- AC-3
- AC-1
- AC-3e
Poles description
[uc] control circuit voltage
Motor power kw
- 7.5 kW at 220...230 V AC 50/60 Hz (AC-3)
- 15 kW at 380...400 V AC 50/60 Hz (AC-3)
- 15 kW at 415...440 V AC 50/60 Hz (AC-3)
- 18.5 kW at 500 V AC 50/60 Hz (AC-3)
- 18.5 kW at 660...690 V AC 50/60 Hz (AC-3)
- 7.5 kW at 400 V AC 50/60 Hz (AC-4)
- 7.5 kW at 220...230 V AC 50/60 Hz (AC-3e)
- 15 kW at 380...400 V AC 50/60 Hz (AC-3e)
- 15 kW at 415...440 V AC 50/60 Hz (AC-3e)
- 18.5 kW at 500 V AC 50/60 Hz (AC-3e)
- 18.5 kW at 660...690 V AC 50/60 Hz (AC-3e)
Motor power hp
- 2 hp at 115 V AC 50/60 Hz for 1 phase motors
- 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors
- 10 hp at 200/208 V AC 50/60 Hz for 3 phases motors
- 10 hp at 230/240 V AC 50/60 Hz for 3 phases motors
- 20 hp at 460/480 V AC 50/60 Hz for 3 phases motors
- 25 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Compatibility code
Pole contact composition
Protective cover
[ith] conventional free air thermal current
- 10 A (at 60 °C) for signalling circuit
- 50 A (at 60 °C) for power circuit
Irms rated making capacity
- 140 A AC for signalling circuit conforming to IEC 60947-5-1
- 250 A DC for signalling circuit conforming to IEC 60947-5-1
- 550 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
[icw] rated short-time withstand current
- 60 A 40 °C - 10 min for power circuit
- 138 A 40 °C - 1 min for power circuit
- 260 A 40 °C - 10 s for power circuit
- 430 A 40 °C - 1 s for power circuit
- 100 A - 1 s for signalling circuit
- 120 A - 500 ms for signalling circuit
- 140 A - 100 ms for signalling circuit
Associated fuse rating
- 10 A gG for signalling circuit conforming to IEC 60947-5-1
- 63 A gG at <= 690 V coordination type 1 for power circuit
- 63 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
Power dissipation per pole
- 2 W AC-3
- 5 W AC-1
- 2 W AC-3e
[ui] rated insulation voltage
- power circuit: 600 V CSA certified
- power circuit: 600 V UL certified
- signalling circuit: 690 V conforming to IEC 60947-1
- signalling circuit: 600 V CSA certified
- signalling circuit: 600 V UL certified
- power circuit: 690 V conforming to IEC 60947-4-1
Overvoltage category
Pollution degree
[uimp] rated impulse withstand voltage
Safety reliability level
- B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
- B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Control circuit type
Coil technology
Control circuit voltage limits
- 0.1...0.25 Uc (-40-70 °C):drop-out DC
- 0.7...1.25 Uc (-40-60 °C):operational DC
- 1...1.25 Uc (60-70 °C):operational DC
Inrush power in w
Hold-in power consumption in w
Operating time
- 20 ±20 % ms opening
- 63 ±15 % ms closing
Time constant
Maximum operating rate
Tightening torque
- control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
- control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
- power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
- power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2
- control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
- power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Auxiliary contact composition
Auxiliary contacts type
- type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
- type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency
Minimum switching voltage
Minimum switching current
Non-overlap time
- 1.5 ms on de-energisation between NC and NO contact
- 1.5 ms on energisation between NC and NO contact
Contact compatibility
Protective treatment
Permissible ambient air temperature around the device
- -40...60 °C
- 60...70 °C with derating
Operating altitude
Fire resistance
Flame retardance
Mechanical robustness
- vibrations contactor open (2 Gn, 5...300 Hz)
- vibrations contactor closed (4 Gn, 5...300 Hz)
- shocks contactor closed (15 Gn for 11 ms)
- shocks contactor open (8 Gn for 11 ms)
Unit type of package 1
Number of units in package 1
Package 1 height
Package 1 width
Package 1 length
Package 1 weight
Unit type of package 2
Number of units in package 2
Package 2 height
Package 2 width
Package 2 length
Package 2 weight
Packaging made with recycled cardboard
Scip number
Green premium status for reporting
Packaging without single use plastic
Sustainable packaging
Pvc free
Pvc free
F-gas usage performance
Take-back
Take-back
Product contributes to saved and avoided emissions
Removable battery
Global warming ; total life cycle
Carbon footprint (kg.eq.co2 per cr, total life cycle)
Minimum percentage of recycled plastic content
Documents & downloads
hide show-
All
-
CAD Files and Packs
-
Technical Data Catalogues
-
End of Life Manual
-
Environmental Disclosure
-
Installation Instruction
-
Technical illustration
-
Certificates (MSDS)
-