Browse all
Browse all

TeSys D Contactor Coil LXD1, 600 V AC 50/60 Hz for 9… 38 A Contactor

TeSys D Contactor Coil LXD1, 600 V AC 50/60 Hz for 9… 38 A Contactor

Item Number: LXD1X7

This product is TeSys Deca replacement AC coil 600V 50/60Hz for TeSys Deca contactors. It is applied on contactors LC1D09...D38 and LC1DT20…DT40. It operates in the voltage limits 0.85-1.1 Uc and environments until 60°C

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product TeSys Deca
Range TeSys
Product or component type contactor coil
Product compatibility
  • LC1D09...D38
  • CAD
  • LC1DT20...DT40
Warranty 18 months

Physical

Mechanical durability 15 Mcycles
Ambient air temperature for operation -5...60 °C
Net weight 0.07 kg
Reach free of svhc Yes
Toxic heavy metal free Yes
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP1501004EN
Reach regulation Free of Substances of Very High Concern above the threshold
China rohs regulation Product out of China RoHS scope
Eu rohs directive Compliant
California proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Life cycle assessment data No
If one of the deliverables is not relevant please give the reason acc
Substance regulation data deliverable Yes
Legacy weee scope Out
At least in Europe
Average percentage of recycled plastic content 0 %
Package 3 bare product quantity 960
Package 2 bare product quantity 30
Package 1 bare product quantity 1
Warranty duration(in months) bmecat 18
Weee label No
Device short name LXD1
Control circuit type AC at 50/60 Hz
[uc] control circuit voltage 600 V AC 50/60 Hz
Average resistance 3810 Ohm at 20 °C
Inductance of closed circuit 136 H
Maximum operating rate 3600 cyc/h 60 °C
Coil technology without built-in suppressor module
Control circuit voltage limits
  • drop-out: 0.3...0.6 Uc at 50/60 Hz (at <60 °C)
  • operational: 0.8...1.1 Uc at 50 Hz (at <60 °C)
  • operational: 0.85...1.1 Uc at 60 Hz (at <60 °C)
Inrush power in va
  • 70 VA 60 Hz cos phi 0.75 (at 20 °C)
  • 70 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in va
  • 7.5...7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
  • 7 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation 2...3 W at 50/60 Hz
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 7.000 cm
Package 1 width 4.500 cm
Package 1 length 3.500 cm
Package 1 weight 79.000 g
Unit type of package 2 S01
Number of units in package 2 30
Package 2 height 15 cm
Package 2 width 15 cm
Package 2 length 40 cm
Package 2 weight 2.570 kg
Unit type of package 3 P06
Number of units in package 3 960
Package 3 height 75.000 cm
Package 3 width 80.000 cm
Package 3 length 60.000 cm
Package 3 weight 90.240 kg
Green premium status for reporting Green Premium product
Sustainable packaging Yes
Pvc free Yes
F-gas free N/A
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
China rohs label 1
Pvc free Yes
End of life manual availability ENVEOLI1501004
Take-back No
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • Technical Data Catalogues

  • Environmental Disclosure

  • End of Life Manual

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.