TeSys D Contactor Coil LX1D6, 240V AC 50/60 Hz for 80 & 95 A Contactor

TeSys D Contactor Coil LX1D6, 240V AC 50/60 Hz for 80 & 95 A Contactor

Item Number: LX1D6U7

TeSys Deca replacement AC coil 240V 50/60Hz for TeSys Deca contactors. To be used with 3 and 4-pole contactors LC1 D40 to D95. It operates in the voltage limits 0.85-1.1 Uc and environments until 55°C

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys Deca

Range

TeSys

Product or component type

contactor coil

Product compatibility

  • LC1D80
  • LC1D95

Warranty

18 months

Physical

Mechanical durability

4 Mcycles

Ambient air temperature for operation

-5...60 °C

Net weight

0.28 kg

Reach free of svhc

Yes

Toxic heavy metal free

Yes

Mercury free

Yes

Rohs exemption information

Yes

Environmental disclosure

ENVPEP110205EN

Eu rohs directive

Pro-active compliance (Product out of EU RoHS legal scope)

Reach regulation

Free of Substances of Very High Concern above the threshold

China rohs regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

California proposition 65

WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Life cycle assessment data

No

If one of the deliverables is not relevant please give the reason

acc

Substance regulation data deliverable

Yes

Average percentage of recycled plastic content

0 %

Package 2 bare product quantity

16

Package 1 bare product quantity

1

Legacy weee scope

Out

At least in Europe

Weee label

No

Device short name

LX1D6

Control circuit type

AC at 50/60 Hz

[uc] control circuit voltage

240 V AC 50/60 Hz

Average resistance

131 Ohm at 20 °C

Inductance of closed circuit

8.3 H

Maximum operating rate

3600 cyc/h 60 °C

Coil technology

without built-in suppressor module

Control circuit voltage limits

  • drop-out: 0.3...0.6 Uc at 50/60 Hz (at <55 °C)
  • operational: 0.8...1.1 Uc at 50 Hz (at <55 °C)
  • operational: 0.85...1.1 Uc at 60 Hz (at <55 °C)

Inrush power in va

  • 245 VA 60 Hz cos phi 0.75 (at 20 °C)
  • 245 VA 50 Hz cos phi 0.75 (at 20 °C)

Hold-in power consumption in va

  • 26 VA 60 Hz cos phi 0.3 (at 20 °C)
  • 26 VA 50 Hz cos phi 0.3 (at 20 °C)

Heat dissipation

6...10 W at 50/60 Hz

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

6.000 cm

Package 1 width

8.900 cm

Package 1 length

12.500 cm

Package 1 weight

313.000 g

Unit type of package 2

S02

Number of units in package 2

16

Package 2 height

15.000 cm

Package 2 width

30.000 cm

Package 2 length

40.000 cm

Package 2 weight

5.305 kg

Green premium status for reporting

Green Premium product

Sustainable packaging

No

F-gas free

N/A

Take-back

No

Product contributes to saved and avoided emissions

No

Removable battery

N/A

Average percentage of recycled metal content

0 %

Packaging made with recycled cardboard

Yes

Packaging without single use plastic

No

Scip number

33f78681-eb6b-4762-93e0-d91a4cabd5c8

End of life manual availability

N/A

Take-back

No

Warranty (in months)

18
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • Technical Data Catalogues

  • Environmental Disclosure

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.