Specifications

Design

Range of product TeSys Deca
Product or component type contactor
Warranty 18 months

Physical

[ue] rated operational voltage
  • power circuit: <= 690 V AC 25...400 Hz
  • power circuit: <= 300 V DC
[ie] rated operational current
  • 25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
  • 12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
  • 12 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
Mechanical durability 15 Mcycles
Electrical durability
  • 2 Mcycles 12 A AC-3 at Ue <= 440 V
  • 0.8 Mcycles 25 A AC-1 at Ue <= 440 V
  • 2 Mcycles 12 A AC-3e at Ue <= 440 V
Connections - terminals
  • power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
  • power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
  • power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end
  • power circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
  • power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end
  • power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
  • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end
  • control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
  • control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end
  • control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
Insulation resistance > 10 MOhm for signalling circuit
Mounting support
  • rail
  • plate
Connections - terminals screw clamp terminals
Standards
  • CSA C22.2 No 14
  • EN 60947-4-1
  • EN 60947-5-1
  • IEC 60947-4-1
  • IEC 60947-5-1
  • UL 60947-4-1
  • IEC 60335-1:Clause 30.2
  • IEC 60335-2-40:Annex JJ
  • UL 60335-2-40:Annex JJ
  • CSA C22.2 No 60947-4-1
Product certifications
  • UL
  • CCC
  • CSA
  • Marine
  • UKCA
  • EAC
  • CB Scheme
Ip degree of protection IP20 front face conforming to IEC 60529
Climatic withstand
  • conforming to IACS E10 exposure to damp heat
  • conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Height 77 mm
Width 45 mm
Depth 86 mm
Net weight 0.325 kg
Reach free of svhc Yes
Toxic heavy metal free Yes
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP1501004EN
Reach regulation Free of Substances of Very High Concern above the threshold
China rohs regulation Product out of China RoHS scope
Eu rohs directive Compliant
California proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Life cycle assessment data Yes
Substance regulation data deliverable Yes
Package 1 bare product quantity 1
Package 2 bare product quantity 16
Legacy weee scope In
At least in Europe
Package 3 bare product quantity 256
Warranty duration(in months) bmecat 18
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Average percentage of recycled plastic content 0 %
Device short name LC1D
Contactor application
  • resistive load
  • motor control
Utilisation category
  • AC-3
  • AC-3e
  • AC-1
  • AC-4
Poles description 3P
[uc] control circuit voltage 220 V AC 50/60 Hz
Motor power kw
  • 3 kW at 220/230 V AC 50/60 Hz (AC-3)
  • 5.5 kW at 380/400 V AC 50/60 Hz (AC-3)
  • 5.5 kW at 415/440 V AC 50/60 Hz (AC-3)
  • 7.5 kW at 500 V AC 50/60 Hz (AC-3)
  • 7.5 kW at 660/690 V AC 50/60 Hz (AC-3)
  • 3 kW at 220/230 V AC 50/60 Hz (AC-3e)
  • 5.5 kW at 380/400 V AC 50/60 Hz (AC-3e)
  • 5.5 kW at 415/440 V AC 50/60 Hz (AC-3e)
  • 7.5 kW at 500 V AC 50/60 Hz (AC-3e)
  • 7.5 kW at 660/690 V AC 50/60 Hz (AC-3e)
  • 3.7 kW at 400 V AC 50/60 Hz (AC-4)
Motor power hp
  • 0.5 hp at 115 V AC 50/60 Hz for 1 phase motors
  • 2 hp at 230/240 V AC 50/60 Hz for 1 phase motors
  • 3 hp at 200/208 V AC 50/60 Hz for 3 phases motors
  • 3 hp at 230/240 V AC 50/60 Hz for 3 phases motors
  • 7.5 hp at 460/480 V AC 50/60 Hz for 3 phases motors
  • 10 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Compatibility code LC1D
Pole contact composition 3 NO
Protective cover with
[ith] conventional free air thermal current
  • 25 A (at 60 °C) for power circuit
  • 10 A (at 60 °C) for signalling circuit
Irms rated making capacity
  • 250 A at 440 V for power circuit conforming to IEC 60947
  • 140 A AC for signalling circuit conforming to IEC 60947-5-1
  • 250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity 250 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current
  • 105 A 40 °C - 10 s for power circuit
  • 210 A 40 °C - 1 s for power circuit
  • 30 A 40 °C - 10 min for power circuit
  • 61 A 40 °C - 1 min for power circuit
  • 100 A - 1 s for signalling circuit
  • 120 A - 500 ms for signalling circuit
  • 140 A - 100 ms for signalling circuit
Associated fuse rating
  • 10 A gG for signalling circuit conforming to IEC 60947-5-1
  • 40 A gG at <= 690 V coordination type 1 for power circuit
  • 25 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 2.5 mOhm - Ith 25 A 50 Hz for power circuit
Power dissipation per pole
  • 0.36 W AC-3
  • 1.56 W AC-1
  • 0.36 W AC-3e
[ui] rated insulation voltage
  • power circuit: 690 V conforming to IEC 60947-4-1
  • power circuit: 600 V CSA certified
  • power circuit: 600 V UL certified
  • signalling circuit: 690 V conforming to IEC 60947-1
  • signalling circuit: 600 V CSA certified
  • signalling circuit: 600 V UL certified
Overvoltage category III
Pollution degree 3
[uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
Safety reliability level
  • B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
  • B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Control circuit type AC at 50/60 Hz standard
Coil technology without built-in suppressor module
Control circuit voltage limits
  • 0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz
  • 0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz
  • 0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz
  • 1...1.1 Uc (60-70 °C):operational AC 50/60 Hz
Inrush power in va
  • 70 VA 60 Hz cos phi 0.75 (at 20 °C)
  • 70 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in va
  • 7.5...7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
  • 7 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation 2...3 W at 50/60 Hz
Operating time
  • 12...22 ms closing
  • 4...19 ms opening
Maximum operating rate 3600 cyc/h at 60 °C
Tightening torque
  • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
  • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
  • control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
  • power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type
  • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
  • type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Non-overlap time
  • 1.5 ms on de-energisation between NC and NO contact
  • 1.5 ms on energisation between NC and NO contact
Contact compatibility M2
[uc] control circuit voltage 220 V
Maximum motor phase current 12 A
Protective treatment TH conforming to IEC 60068-2-30
Permissible ambient air temperature around the device
  • -40...60 °C
  • 60...70 °C with derating
Operating altitude 0...3000 m
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness
  • vibrations contactor open (2 Gn, 5...300 Hz)
  • vibrations contactor closed (4 Gn, 5...300 Hz)
  • shocks contactor open (10 Gn for 11 ms)
  • shocks contactor closed (15 Gn for 11 ms)
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 5.500 cm
Package 1 width 10.000 cm
Package 1 length 12.000 cm
Package 1 weight 360.000 g
Unit type of package 2 S02
Number of units in package 2 16
Package 2 height 15.000 cm
Package 2 width 30.000 cm
Package 2 length 40.000 cm
Package 2 weight 6.295 kg
Unit type of package 3 P06
Number of units in package 3 256
Package 3 height 75.000 cm
Package 3 width 60.000 cm
Package 3 length 80.000 cm
Package 3 weight 104.868 kg
Green premium status for reporting Green Premium product
Total lifecycle carbon footprint 23 kg CO2 eq.
Carbon footprint of the manufacturing phase [a1 to a3] 1.3477959823131842
Carbon footprint of the manufacturing phase [a1 to a3] 1 kg CO2 eq.
Carbon footprint of the distribution phase [a4] 0.15063591165520598
Carbon footprint of the distribution phase [a4] 0.2 kg CO2 eq.
Carbon footprint of the installation phase [a5] 0.05308452752054227
Carbon footprint of the installation phase [a5] 0.1 kg CO2 eq.
Carbon footprint of the use phase [b2, b3, b4, b6] 21.825019899655352
Carbon footprint of the use phase [b2, b3, b4, b6] 22 kg CO2 eq.
Sustainable packaging Yes
Pvc free Yes
F-gas free N/A
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Total lifecycle carbon footprint 23.376536321144286
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
China rohs label 1
Pvc free Yes
End of life manual availability ENVEOLI1501004
Take-back No
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Environmental Disclosure

  • End of Life Manual

  • Data Bulletin

  • Installation Instruction

  • Technical illustration

  • Technical Drawing

  • Certificates (MSDS)

  • Declaration of Conformity

  • eTechPub

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.

Frequently Asked Questions

What is the coil tolerance for Tesys D-line contactors LC1D09 - LC1D38?

Hide Show
Issue:
LC1D09 - LC1D38 Coil tolerance

Product Line:
Contactors and Starters, IEC

Environment:
Tesys D Contactors

Cause:
Needs the coil tolerance for Tesys D-line contactors LC1D09 - LC1D38.

Resolution:
AC single frequency coils: 50Hz and 60 Hz (-20% / +10%);
AC dual frequency coils: 50Hz (-20% / +10%) ; 60Hz (-15% / +10%)
DC standard coil for LC1D09 -D38 and LC1DT20 to DT40: (-30% / +25%)
DC standard coil for LP1D12 and D25: (-20% / +10%)
DC wide range coil for LP1D12 and D25 : (-30% to +25%)