TeSys GB2 Circuit breaker 1P+N, 12A, Icu 1.5kA at 240V, Thermal magnetic, DIN rail mounted

TeSys GB2 Circuit breaker 1P+N, 12A, Icu 1.5kA at 240V, Thermal magnetic, DIN rail mounted

Item Number: GB2CD20

Datasheet

Product Dimensions

Width icon

Width15 mm

Height icon

Height74 mm

Depth icon

Depth67 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range TeSys
Product or component type circuit breaker
Device application control
Warranty 18 months

Physical

Mounting mode by clips
Mounting support
  • rail
  • plate
Mounting position
  • vertical
  • horizontal
Control type toggle
[in] rated current 12 A
[ue] rated operational voltage
  • 250 V AC 50/60 Hz conforming to IEC 60947-2
  • 277 V AC 60 Hz conforming to CSA C22.2 No 235
  • 277 V AC 60 Hz conforming to UL 1077
  • 48 V DC
Mechanical durability 8000 cycles
Electrical durability 8000 cycles
Connections - terminals
  • connector 1 cable(s) 0.75-6 mm²solid without cable end
  • connector 2 cable(s) 0.75-4 mm²solid without cable end
  • connector 1 cable(s) 0.75-4 mm²flexible with cable end
  • connector 2 cable(s) 0.75-2.5 mm²flexible with cable end
Quantity per set set of 6
Height 74 mm
Width 15 mm
Depth 67 mm
Net weight 0.07 kg
Standards
  • EN/IEC 60947-1
  • EN/IEC 60947-2
  • CSA C22.2 No 235
  • UL 1077
Product certifications
  • UL
  • CSA
Ip degree of protection IP20 conforming to IEC 60529
Ambient air temperature for operation -20...60 °C
Ambient air temperature for storage -40...80 °C
Reach free of svhc Yes
Toxic heavy metal free Yes
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP2306023EN
Reach regulation Free of Substances of Very High Concern above the threshold
China rohs regulation Product out of China RoHS scope
Eu rohs directive Compliant
California proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Life cycle assessment data Yes
Substance regulation data deliverable Yes
Legacy weee scope In
Warranty duration(in months) bmecat 18
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Weee applicability Finished product
Package 1 bare product quantity 1
Package 2 bare product quantity 6
Package 3 bare product quantity 72
Average percentage of recycled plastic content 0 %
At least in Europe
Product name TeSys GB2
Device short name GB2
Poles description 1P + N
Network type AC/DC
Utilisation category
  • category A conforming to IEC 60947-2
  • DC-12 conforming to IEC 60947-5-1
  • DC-13 conforming to IEC 60947-5-1
Network frequency 50/60 Hz conforming to IEC 60947-2
Breaking capacity 1 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
[ics] rated service short-circuit breaking capacity 75 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit technology thermal-magnetic
Magnetic tripping current 165 A
[uimp] rated impulse withstand voltage 4 kV conforming to IEC 60947-2
Power dissipation per pole 2 W
Tightening torque 1.2 N.m on connector
Mechanical robustness
  • shocks: 22 Gn for 20 ms conforming to IEC 60068-2-27
  • vibrations: 5 Gn, 5...110 Hz conforming to IEC 60068-2-6
9 mm pitches 2
Compatibility code GB2
Protective treatment TC
Fire resistance 960 °C conforming to IEC 60695-2-1
Operating altitude 3000 m
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 1.500 cm
Package 1 width 1.500 cm
Package 1 length 7.000 cm
Package 1 weight 60.000 g
Unit type of package 2 BB1
Number of units in package 2 6
Package 2 height 8.200 cm
Package 2 width 9.800 cm
Package 2 length 8.000 cm
Package 2 weight 380.000 g
Unit type of package 3 S02
Number of units in package 3 72
Package 3 height 15.000 cm
Package 3 width 30.000 cm
Package 3 length 40.000 cm
Package 3 weight 4.850 kg
Green premium status for reporting Green Premium product
Total lifecycle carbon footprint 3 kg CO2 eq.
Carbon footprint of the manufacturing phase [a1 to a3] 0.40726592069583606
Carbon footprint of the manufacturing phase [a1 to a3] 0.4 kg CO2 eq.
Carbon footprint of the distribution phase [a4] 0
Carbon footprint of the distribution phase [a4] 0 kg CO2 eq.
Carbon footprint of the installation phase [a5] 0.004183306690366238
Carbon footprint of the installation phase [a5] 0 kg CO2 eq.
Carbon footprint of the use phase [b2, b3, b4, b6] 2.363720566749677
Carbon footprint of the use phase [b2, b3, b4, b6] 2 kg CO2 eq.
Sustainable packaging Yes
Carbon footprint of the end-of-life phase [c1 to c4] 0.1552255178671008
Carbon footprint of the end-of-life phase [c1 to c4] 0.2 kg CO2 eq.
Pvc free Yes
Halogen-free status Halogen free plastic parts product
Energy efficiency optimized False
F-gas free N/A
Updatability N/A
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Total lifecycle carbon footprint 2.93039531200298
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
China rohs label 1
Halogen-free status Halogen free plastic parts product
Pvc free Yes
End of life manual availability N/A
Take-back No
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Environmental Disclosure

  • Certificates (MSDS)

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.