TeSys GV auxiliary contact block, for motor circuit breakers GV2 and GV3. 1NO or 1NC instantaneous auxiliary contacts depending on the mounting orientation of the block. Rated for operation up to 2A/240V AC and 1A/60V DC. To be installed on front side of the circuit breaker, connection by screw clamp terminals. Sold in lots of 10 units. Multi standards certified (IEC, UL, CSA, CCC, EAC),

Datasheet

Product Dimensions

Width icon

Width45 mm

Height icon

Height11 mm

Depth icon

Depth29 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

  • TeSys
  • TeSys Deca

Product or component type

auxiliary contact block

Product compatibility

  • GV2L
  • GV2P
  • GV2RT
  • GV3P
  • GV3L
  • GV2LE
  • GV2ME

Warranty

18 months

Physical

Quantity per set

set of 10

[ue] rated operational voltage

  • 24...240 V AC
  • 24...60 V DC

Mechanical durability

100000 cycles

Protection type

  • gG fuse 10 A
  • GB2CB06 circuit breaker 10 A

Height

11 mm

Width

45 mm

Depth

29 mm

Net weight

0.02 kg

Environmental characteristic

normal environment

Product certifications

UKCA

Reach regulation

Free of Substances of Very High Concern above the threshold

Reach free of svhc

Yes

Eu rohs directive

Compliant

Toxic heavy metal free

Yes

Mercury free

Yes

China rohs regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Rohs exemption information

Yes

Environmental disclosure

ENVPEP2207006

Circularity profile

ENVEOLI2207006

California proposition 65

WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Others

Package 1 bare product quantity

1

Substance regulation data deliverable

Yes

Life cycle assessment data

Yes

Device short name

GVAE

Mounting location

front side

Pole contact composition

1 NO/NC

[ui] rated insulation voltage

  • 300 V conforming to UL 508
  • 300 V conforming to CSA C22.2 No 14
  • 250 V conforming to IEC 60947-1

[ith] conventional free air thermal current

2.5 A

Minimum switching current

5 mA

Minimum switching voltage

17 V

Rated operational power in va

  • 120 VA at 110-120 V AC-15 - electrical durability: 100000 cycles
  • 120 VA at 230-240 V AC-15 - electrical durability: 100000 cycles
  • 48 VA at 24-24 V AC-15 - electrical durability: 100000 cycles
  • 60 VA at 48-48 V AC-15 - electrical durability: 100000 cycles

Rated operational power in w

  • 15 W at 48 V DC-13 - electrical durability: 100000 cycles
  • 24 W at 24 V DC-13 - electrical durability: 100000 cycles
  • 9 W at 60 V DC-13 - electrical durability: 100000 cycles

Tightening torque

1.4 N.m - on screw clamp terminals

Compatibility code

GVAE

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

1.100 cm

Package 1 width

6.000 cm

Package 1 length

8.000 cm

Package 1 weight

13.000 g

Unit type of package 2

BB1

Number of units in package 2

10

Package 2 height

2.000 cm

Package 2 width

16.000 cm

Package 2 length

17.000 cm

Package 2 weight

140.000 g

Unit type of package 3

S02

Number of units in package 3

220

Package 3 height

15.000 cm

Package 3 width

30.000 cm

Package 3 length

40.000 cm

Package 3 weight

3.385 kg

Packaging made with recycled cardboard

Yes

Green premium status for reporting

Green Premium product

Packaging without single use plastic

No

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

F-gas usage performance

N/A

Take-back

No

Take-back

No

Product contributes to saved and avoided emissions

No

Removable battery

N/A

Global warming ; total life cycle​

1 kg CO2 eq.

Carbon footprint (kg.eq.co2 per cr, total life cycle)

0.1338511664267523

Minimum percentage of recycled plastic content

0
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • End of Life Manual

  • Environmental Disclosure

  • Installation Instruction

  • Technical illustration

  • Technical Drawing

  • Certificates (MSDS)

  • Declaration of Conformity

Frequently Asked Questions

Can GVAE1, GVAE11 or GVAE20 be used with GV3 starters?

Hide Show
Issue:
Are the front mount auxiliary contacts GVAE1, GVEA11 and GVAE20 be used for GV3M devices?
 
Product Line:

Tesys GV Manual Starter and Protectors

Environment:
TeSys GV, GVA, GV2, GV3P

Resolution:
These auxiliary contacts can only be used with the rotary handled GV3P devices. They cannot be applied with the pushbutton GV3M devices.