Browse all
Browse all

Modicon M221 Logic controller 16 IO relay spring

Modicon M221 Logic controller 16 IO relay spring

Item Number: TM221M16RG

Datasheet

Product Dimensions

Width icon

Width70 mm

Height icon

Height90 mm

Depth icon

Depth70 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product Modicon M221
Product or component type logic controller

Physical

Inrush current 35 A
Electrical durability
  • 100000 cycles AC-12, 120 V, 240 VA, resistive
  • 100000 cycles AC-12, 240 V, 480 VA, resistive
  • 300000 cycles AC-12, 120 V, 80 VA, resistive
  • 300000 cycles AC-12, 240 V, 160 VA, resistive
  • 100000 cycles AC-15, cos phi = 0.35 , 120 V, 60 VA, inductive
  • 100000 cycles AC-15, cos phi = 0.35 , 240 V, 120 VA, inductive
  • 300000 cycles AC-15, cos phi = 0.35 , 120 V, 18 VA, inductive
  • 300000 cycles AC-15, cos phi = 0.35 , 240 V, 36 VA, inductive
  • 100000 cycles AC-14, cos phi = 0.7 , 120 V, 120 VA, inductive
  • 100000 cycles AC-14, cos phi = 0.7 , 240 V, 240 VA, inductive
  • 300000 cycles AC-14, cos phi = 0.7 , 120 V, 36 VA, inductive
  • 300000 cycles AC-14, cos phi = 0.7 , 240 V, 72 VA, inductive
  • 100000 cycles DC-12, 24 V, 48 W, resistive
  • 300000 cycles DC-12, 24 V, 16 W, resistive
  • 100000 cycles DC-13, 24 V, 24 W, inductive (L/R = 7 ms)
  • 300000 cycles DC-13, 24 V, 7.2 W, inductive (L/R = 7 ms)
Mechanical durability 20000000 cycles for relay output
Protection type without protection at 5 A
Backup time 1 year at 25 °C (by interruption of power supply)
Control signal type
  • A/B
  • pulse/direction
  • single phase
Integrated connection type
  • USB port with mini B USB 2.0 connector
  • non isolated serial link serial 1 with RJ45 connector and RS485 interface
  • non isolated serial link serial 2 with RJ45 connector and RS232/RS485 interface
Supply (serial 1)serial link supply: 5 V, <200 mA
Communication port protocol
  • USB port: USB - SoMachine-Network
  • non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network
Local signalling
  • 1 LED (green) for PWR
  • 1 LED (green) for RUN
  • 1 LED (red) for module error (ERR)
  • 1 LED (green) for SD card access (SD)
  • 1 LED (red) for BAT
  • 1 LED (green) for SL1
  • 1 LED (green) for SL2
  • 1 LED per channel (green) for I/O state
Marking CE
Mounting support
  • top hat type TH35-15 rail conforming to IEC 60715
  • top hat type TH35-7.5 rail conforming to IEC 60715
  • plate or panel with fixing kit
Height 90 mm
Depth 70 mm
Width 70 mm
Net weight 0.264 kg
Standards
  • IEC 61131-2
  • UL 508
  • CAN/CSA C22.2 No. 213
  • IACS E10
  • ANSI/ISA 12-12-01
Product certifications
  • RCM
  • LR
  • EAC
  • cULus
  • DNV-GL
  • ABS
  • CSA
  • CE
  • UKCA
  • cULus HazLoc
Environmental characteristic ordinary and hazardous location
Ambient air temperature for operation
  • -10...55 °C (horizontal installation)
  • -10...35 °C (vertical installation)
Ambient air temperature for storage -25...70 °C
Relative humidity
  • 10...95 %, without condensation (in operation)
  • 10...95 %, without condensation (in storage)
Ip degree of protection IP20 with protective cover in place
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP1403012EN
Reach regulation Reference contains Substances of Very High Concern above the threshold
China rohs regulation X
Eu rohs directive Compliant By Exemption
California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Others

Legacy weee scope In
Package 1 bare product quantity 1
Package 2 bare product quantity 24
Average percentage of recycled plastic content 0 %
At least in Europe
Warranty duration(in months) bmecat 18
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
[us] rated supply voltage 24 V DC
Discrete input number 8 , discrete input conforming to IEC 61131-2 Type 1
Analogue input number 2 at 0...10 V
Discrete output type relay normally open
Discrete output number 8 relay
Discrete output voltage
  • 5...125 V DC
  • 5...250 V AC
Discrete output current 2 A
Discrete i/o number 16
Maximum number of i/o expansion module
  • 7 (local I/O-Architecture)
  • 14 (remote I/O-Architecture)
Supply voltage limits 20.4...28.8 V
Maximum power consumption in w
  • 22.5 W at 24 V (with max number of I/O expansion module)
  • 3.6 W at 24 V (without I/O expansion module)
Power supply output current
  • 0.52...0.52 A 5 V for expansion bus
  • 0.46...0.46 A 24 V for expansion bus
Discrete input logic sink or source (positive/negative)
Discrete input voltage 24 V
Discrete input voltage type DC
Analogue input resolution 10 bits
Lsb value 10 mV
Conversion time 1 ms per channel + 1 controller cycle time for analogue input analog input
Permitted overload on inputs
  • +/- 30 V DC for 5 min (maximum) for analog input
  • +/- 13 V DC (permanent) for analog input
Voltage state 1 guaranteed >= 15 V for input
Voltage state 0 guaranteed <= 5 V for input
Discrete input current
  • 7 mA for discrete input
  • 5 mA for fast input
Input impedance
  • 100 kOhm for analog input
  • 3.4 kOhm for input
  • 4.9 kOhm for fast input
Response time
  • 35 µs turn-off, I2...I5 terminal(s) for input
  • 10 ms turn-on for output
  • 10 ms turn-off for output
  • 5 µs turn-on, I0, I1, I6, I7 terminal(s) for fast input
  • 35 µs turn-on, other terminals terminal(s) for input
  • 5 µs turn-off, I0, I1, I6, I7 terminal(s) for fast input
  • 100 µs turn-off, other terminals terminal(s) for input
Configurable filtering time
  • 0 ms for input
  • 3 ms for input
  • 12 ms for input
Output voltage limits
  • 125 V DC
  • 277 V AC
Maximum current per output common 7 A
Absolute accuracy error +/- 1 % of full scale for analog input
Switching frequency 20 switching operations/minute with maximum load
Minimum load 1 mA at 5 V DC for relay output
Reset time 1 s
Memory capacity
  • 256 kB for user application and data RAM with 10000 instructions
  • 256 kB for internal variables RAM
Data backed up 256 kB built-in flash memory for backup of application and data
Data storage equipment 2 GB SD card (optional)
Battery type BR2032 or CR2032X lithium non-rechargeable
Execution time for 1 kinstruction
  • 0.3 ms for event and periodic task
  • 0.7 ms for other instruction
Execution time per instruction 0.2 µs Boolean
Exct time for event task 60 µs response time
Application structure
  • 8 interrupt tasks
  • 1 cyclic auxiliary task
  • 1 configurable freewheeling/cyclic master task
Maximum size of object areas
  • 8000 %MW memory words
  • 255 %TM timers
  • 255 %C counters
  • 512 %KW constant words
  • 512 %M memory bits
Realtime clock with
Clock drift <= 30 s/month at 25-25 °C
Regulation loop adjustable PID regulator up to 14 simultaneous loops
Counting input number 4 fast input (HSC mode) at 100 kHz 32 bits
Transmission rate
  • 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15-15 m for RS485
  • 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3-3 m for RS232
  • 480 Mbit/s for USB
Communication service
  • Modbus slave
  • Modbus master
Electrical connection
  • terminal block, 3 terminal(s) for connecting the 24 V DC power supply
  • connector, 4 terminal(s) for analogue inputs
  • mini B USB 2.0 connector for a programming terminal
  • removable spring terminal block, 10 terminal(s) for inputs
  • removable spring terminal block, 11 terminal(s) for outputs
Maximum cable distance between devices
  • shielded cable: <10 m for fast input
  • unshielded cable: <30 m for output
  • unshielded cable: <30 m for digital input
  • unshielded cable: <1 m for analog input
Insulation
  • between input and internal logic at 500 V AC
  • between fast input and internal logic at 500 V AC
  • non-insulated between inputs
  • between output and internal logic at 500 V AC
  • between output groups at 500 V AC
  • non-insulated between analogue input and internal logic
  • non-insulated between analogue inputs
Resistance to electrostatic discharge
  • 8 kV in air conforming to IEC 61000-4-2
  • 4 kV on contact conforming to IEC 61000-4-2
Resistance to electromagnetic fields
  • 10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3
  • 3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3
  • 1 V/m 2...2.7 GHz conforming to IEC 61000-4-3
Resistance to magnetic fields 30 A/m 50/60 Hz conforming to IEC 61000-4-8
Resistance to fast transients
  • 2 kV (power lines) conforming to IEC 61000-4-4
  • 2 kV (relay output) conforming to IEC 61000-4-4
  • 1 kV (I/O) conforming to IEC 61000-4-4
  • 1 kV (Ethernet line) conforming to IEC 61000-4-4
  • 1 kV (serial link) conforming to IEC 61000-4-4
Surge withstand
  • 2 kV power lines (AC) common mode conforming to IEC 61000-4-5
  • 2 kV relay output common mode conforming to IEC 61000-4-5
  • 1 kV I/O common mode conforming to IEC 61000-4-5
  • 1 kV shielded cable common mode conforming to IEC 61000-4-5
  • 0.5 kV power lines (DC) differential mode conforming to IEC 61000-4-5
  • 1 kV power lines (AC) differential mode conforming to IEC 61000-4-5
  • 1 kV relay output differential mode conforming to IEC 61000-4-5
  • 0.5 kV power lines (DC) common mode conforming to IEC 61000-4-5
Resistance to conducted disturbances
  • 10 V 0.15...80 MHz conforming to IEC 61000-4-6
  • 3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL)
  • 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
Electromagnetic emission
  • conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15-0.5 MHz conforming to IEC 55011
  • conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5-300 MHz conforming to IEC 55011
  • conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10-150 kHz conforming to IEC 55011
  • conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5-30 MHz conforming to IEC 55011
  • radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30-230 MHz conforming to IEC 55011
  • conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150-1500 kHz conforming to IEC 55011
  • radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 200-1000 MHz conforming to IEC 55011
Immunity to microbreaks 10 ms
Pollution degree <= 2
Operating altitude 0...2000 m
Storage altitude 0...3000 m
Vibration resistance
  • 3.5 mm at 5-8.4 Hz on symmetrical rail
  • 3.5 mm at 5-8.4 Hz on panel mounting
  • 1 gn at 8.4-150 Hz on symmetrical rail
  • 1 gn at 8.4-150 Hz on panel mounting
Shock resistance 98 m/s² for 11 ms
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 12.000 cm
Package 1 width 10.000 cm
Package 1 length 12.500 cm
Package 1 weight 426.000 g
Unit type of package 2 S04
Number of units in package 2 24
Package 2 height 30.000 cm
Package 2 width 40.000 cm
Package 2 length 60.000 cm
Package 2 weight 10.990 kg
Green premium status for reporting Green Premium product
Total lifecycle carbon footprint 90 kg CO2 eq.
Carbon footprint of the manufacturing phase [a1 to a3] 14.118333626518424
Carbon footprint of the manufacturing phase [a1 to a3] 14 kg CO2 eq.
Carbon footprint of the distribution phase [a4] 0.8735419807898985
Carbon footprint of the distribution phase [a4] 0.9 kg CO2 eq.
Carbon footprint of the installation phase [a5] 0.006485561285977588
Carbon footprint of the installation phase [a5] 0 kg CO2 eq.
Carbon footprint of the use phase [b2, b3, b4, b6] 73.9342071114959
Carbon footprint of the use phase [b2, b3, b4, b6] 74 kg CO2 eq.
Sustainable packaging Yes
Carbon footprint of the end-of-life phase [c1 to c4] 0.8310721524708329
Carbon footprint of the end-of-life phase [c1 to c4] 0.8 kg CO2 eq.
Pvc free Yes
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Total lifecycle carbon footprint 89.76364043256103
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard Yes
Packaging without single use plastic No
China rohs label 5
Pvc free Yes
End of life manual availability ENVEOLI1403012EN
Take-back No
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • End of Life Manual

  • Environmental Disclosure

  • Operating Manuals

  • Safety Data Sheet (SDS or MSDS)

  • Certificates (MSDS)

  • eTechPub

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

  • Software - Release

Important: Some software files may need a mySchneider or Club login to download.