Item Number: RM35UA13MW

Datasheet

Product Dimensions

Width icon

Width35 mm

Height icon

Height90 mm

Depth icon

Depth72 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product Harmony Control Relays
Product or component type voltage control relay
Warranty 18 months

Physical

Connections - terminals screw connectors
[in] rated current 5 A
Insulation resistance
  • > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5
  • > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1
  • > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5
  • > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1
  • > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5
  • > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1
Local signalling
  • LED (green) for power ON
  • LED (yellow) for relay ON
Connections - terminals
  • screw terminals, 1 x 0.5...1 x 4 mm² (20 AWG...11 AWG) solid without cable end
  • screw terminals, 2 x 0.5...2 x 2.5 mm² (20 AWG...14 AWG) solid without cable end
  • screw terminals, 1 x 0.2...2 x 2.5 mm² (24 AWG...12 AWG) flexible with cable end
  • screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end
Mounting support 35 mm symmetrical DIN rail conforming to IEC 60715
Electrical durability 100000 cycles
Mechanical durability 30000000 cycles
Control type without test button
Width 35 mm
Height 90 mm
Depth 72 mm
Net weight 0.13 kg
Ambient air temperature for operation -20...50 °C
Standards IEC 60255-6
Product certifications
  • GOST
  • UL
  • GL
  • C-Tick
  • CSA
Ambient air temperature for storage -40...70 °C
Relative humidity 95 % at 55 °C conforming to IEC 60068...2-30
Ip degree of protection
  • IP20 (terminals) conforming to IEC 60529
  • IP30 (casing) conforming to IEC 60529
Mercury free Yes
Environmental disclosure ENVPEP1601004EN
Eu rohs directive Compliant By Exemption
California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Others

Legacy weee scope Out
Average percentage of recycled plastic content 0 %
Package 1 bare product quantity 1
At least in Europe
Warranty duration(in months) bmecat 18
Weee label No
Relay type multifunction voltage control relay
Relay name RM35UA
Relay monitored parameters overvoltage or undervoltage detection
Time delay type adjustable 0.3...30 s, 0 + 10 % Tt- time delay upon fault
Switching capacity in va 1250 VA
Measurement range 15...600 V AC/DC
Contacts type and composition 2 C/O
[uc] control circuit voltage 24...240 V
Reset time 1500 ms time delay
Maximum switching voltage 250 V AC/DC
Minimum switching current 10 mA at 5 V DC
Maximum switching current 5 A AC/DC
Supply voltage limits 20.4...264 V AC/DC
Control circuit voltage limits - 15 % + 10 % Un
Power consumption in va 0...3.5 VA AC
Maximum power consumption in w 0.6 W DC
Control circuit frequency 40...70 Hz +/- 10 %
Resistance across terminals
  • 150 mOhm at E1-M terminals
  • 300 mOhm at E2-M terminals
  • 600 mOhm at E3-M terminals
Output contacts 2 C/O
Nominal output current 5 A
Hysteresis 5...50 % of threshold setting
Measurement accuracy +/- 10 % of the full scale value
Polarity non reversible polarity on DC supply
Run-up delay at power-up 600 ms
Maximum measuring cycle 30 ms measurement cycle as true rms value
Repeat accuracy
  • +/- 0.5 % for input and measurement circuit
  • +/- 2 % for time delay
Measurement error
  • +/- 0.05 %/°C with temperature variation
  • < 1 % over the whole range with voltage variation
Sensitivity scale
  • 15...150 V E1-M terminals
  • 30...300 V E2-M terminals
  • 60...600 V E3-M terminals
Quality labels CE
Threshold setting 10...100 %
Operating position any position without derating
Overvoltage category III conforming to IEC 60664-1
[ui] rated insulation voltage
  • 250 V conforming to IEC 60664-1
  • 600 V conforming to IEC 60664-1
Tightening torque 0.6...1 N.m conforming to IEC 60947...1
Housing material polycarbonate
Utilisation category
  • AC-12 conforming to IEC 60947-5-1
  • AC-13 conforming to IEC 60947-5-1
  • AC-14 conforming to IEC 60947-5-1
  • AC-15 conforming to IEC 60947-5-1
  • DC-12 conforming to IEC 60947-5-1
  • DC-14 conforming to IEC 60947-5-1
Operating rate <= 360 operations/hour full load
[us] rated supply voltage 24...240 V AC/DC 50/60 Hz, non self-powered
Safety reliability data
  • B10d = 290000
  • MTTFd = 308.2 years
Compatibility code RM3
Electromagnetic compatibility
  • emission standard for industrial environments conforming to IEC 61000-6-4
  • emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3
  • immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Vibration resistance
  • 0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6
  • 1 gn (f= 57.6-150 Hz) conforming to IEC 60255-21-1
Shock resistance 5 gn conforming to IEC 60068-2-27
Pollution degree 3 conforming to IEC 60664-1
Directives
  • 73/23/EEC - low voltage directive
  • 89/336/EEC - electromagnetic compatibility
Dielectric test voltage
  • 2 kV, 1 min AC 50 Hz conforming to IEC 60255-5
  • 2 kV, 1 min AC 50 Hz conforming to IEC 60664-1
Non-dissipating shock wave
  • 4 kV conforming to IEC 60255-5
  • 4 kV conforming to IEC 60664-1
  • 4 kV conforming to IEC 61000-4-5
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 4.5 cm
Package 1 width 7.8 cm
Package 1 length 9.6 cm
Package 1 weight 136.0 g
Unit type of package 2 S03
Number of units in package 2 48
Package 2 height 30.0 cm
Package 2 width 30.0 cm
Package 2 length 40.0 cm
Package 2 weight 7.271 kg
Green premium status for reporting Green Premium product
Total lifecycle carbon footprint 64 kg CO2 eq.
Carbon footprint of the manufacturing phase [a1 to a3] 1.6443636364
Carbon footprint of the manufacturing phase [a1 to a3] 2 kg CO2 eq.
Carbon footprint of the distribution phase [a4] 0.0103214545
Carbon footprint of the distribution phase [a4] 0 kg CO2 eq.
Carbon footprint of the installation phase [a5] 0.0003991345
Carbon footprint of the installation phase [a5] 0 kg CO2 eq.
Carbon footprint of the use phase [b2, b3, b4, b6] 61.80384
Carbon footprint of the use phase [b2, b3, b4, b6] 62 kg CO2 eq.
Sustainable packaging Yes
Carbon footprint of the end-of-life phase [c1 to c4] 0.0464858182
Carbon footprint of the end-of-life phase [c1 to c4] 0 kg CO2 eq.
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Total lifecycle carbon footprint 63.5054100436
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
Scip number 5e3fdf99-611b-4d07-ad17-6eba84ab488b
End of life manual availability ENVEOLI1601004EN
Take-back No
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • End of Life Manual

  • Environmental Disclosure

  • Installation Instruction

  • Technical illustration

  • Application Notes

  • eTechPub

  • Certificates (MSDS)

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.