Browse all
Browse all

Harmony Control Relays Modular 1 phase current Control Relay 5A, 2CO, 0.15…15A, 24…240V AC/DC

Home ProductsIndustrialHarmonyModular 1 phase current Control Relay

Harmony Control Relays Modular 1 phase current Control Relay 5A, 2CO, 0.15…15A, 24…240V AC/DC

Item Number: RM35JA32MW

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product Harmony Control Relays
Product or component type current control relay
Warranty 18 months

Physical

Connections - terminals screw connectors
[in] rated current 5 A
Marking
  • CE : EMC 89/336/EEC
  • CE : 73/23/EEC
Insulation resistance
  • > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5
  • > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1
  • > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5
  • > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1
  • > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5
  • > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1
Connections - terminals
  • screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
  • screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
  • screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end
  • screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Local signalling
  • LED (green) for power ON
  • LED (yellow) for relay ON
Mounting support 35 mm symmetrical DIN rail conforming to IEC 60715
Electrical durability 100000 cycles
Mechanical durability 30000000 cycles
Width 35 mm
Control type without test button
Net weight 0.13 kg
Standards IEC 60255-6
Product certifications
  • GL
  • UL
  • GOST
  • C-Tick
  • CSA
Ambient air temperature for storage -40...70 °C
Ambient air temperature for operation -20...50 °C
Relative humidity 95 % at 55 °C conforming to IEC 60068...2-30
Ip degree of protection
  • IP20 (terminals) conforming to IEC 60529
  • IP30 (casing) conforming to IEC 60529
Mercury free Yes
Environmental disclosure ENVPEP1601004EN
Reach regulation Reference contains Substances of Very High Concern above the threshold
China rohs regulation X
Eu rohs directive Compliant By Exemption
California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Material

Contacts material cadmium free

Others

Legacy weee scope Out
Average percentage of recycled plastic content 0 %
Package 2 bare product quantity 48
Weee label No
Package 1 bare product quantity 1
At least in Europe
Warranty duration(in months) bmecat 18
Relay type current control relay
Relay name RM35JA
Relay monitored parameters overcurrent or undercurrent detection
Time delay type
  • adjustable 0.3...30 s, 0 + 10 % Tt- time delay upon fault
  • adjustable 1...20 s, 0 + 10 % Ti- inhibition time delay upon startup
Switching capacity in va 1250 VA
Minimum switching current 10 mA at 5 V DC
Maximum switching current 5 A AC/DC
Maximum power consumption in va 3.5 VA AC
Measurement range 150 mA...15 A current AC/DC
Utilisation category
  • AC-12 conforming to IEC 60947-5-1
  • AC-13 conforming to IEC 60947-5-1
  • AC-14 conforming to IEC 60947-5-1
  • AC-15 conforming to IEC 60947-5-1
  • DC-12 conforming to IEC 60947-5-1
  • DC-13 conforming to IEC 60947-5-1
  • DC-14 conforming to IEC 60947-5-1
Contacts type and composition 2 C/O
[uc] control circuit voltage 24...240 V
Reset time 1500 ms time delay
Maximum switching voltage 250 V AC/DC
Supply voltage limits 20.4...264 V AC/DC
Control circuit voltage limits - 15 % + 10 % Un
Maximum power consumption in w 0.6 W DC
Control circuit frequency 40...70 Hz +/- 10 %
Resistance across terminals
  • 0.005 Ohm at E3-M terminals
  • 0.015 Ohm at E2-M terminals
  • 0.05 Ohm at E1-M terminals
Output contacts 2 C/O
Nominal output current 5 A
Maximum measuring cycle 30 ms measurement cycle as true rms value
Hysteresis 5...50 % of threshold setting
Run-up delay at power-up 0.3 s
Measurement accuracy +/- 10 % of the full scale value
Repeat accuracy
  • +/- 0.5 % for input and measurement circuit
  • +/- 2 % for time delay
Measurement error
  • 0.05 %/°C with temperature variation
  • 1 by volt over the whole range with voltage variation
Polarity no DC
Threshold setting 10...100 %
Overvoltage category III conforming to IEC 60664-1
[ui] rated insulation voltage 250 V conforming to IEC 60664-1
Insulation between supply and measurement
Operating position any position without derating
Tightening torque 0.6...1 N.m conforming to IEC 60947...1
Housing material polycarbonate
Operating rate <= 360 operations/hour full load
[us] rated supply voltage 24...240 V AC/DC 50/60 Hz, non self-powered
Safety reliability data
  • MTTFd = 296.8 years
  • B10d = 270000
Functionality overcurrent or undercurrent in window mode
Compatibility code RM3
Immunity to microbreaks 50 ms
Electromagnetic compatibility
  • emission standard for industrial environments conforming to IEC 61000-6-4
  • emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3
  • immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Vibration resistance
  • 0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6
  • 1 gn (f= 57.6-150 Hz) conforming to IEC 60255-21-1
Shock resistance 15 gn for 11 ms conforming to IEC 60255-21-1
Pollution degree 3 conforming to IEC 60664-1
Dielectric test voltage
  • 2 kV, 1 min AC 50 Hz conforming to IEC 60255-5
  • 2 kV, 1 min AC 50 Hz conforming to IEC 60664-1
Non-dissipating shock wave
  • 4 kV conforming to IEC 60255-5
  • 4 kV conforming to IEC 60664-1
  • 4 kV conforming to IEC 61000-4-5
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 4.500 cm
Package 1 width 8.000 cm
Package 1 length 9.500 cm
Package 1 weight 136.000 g
Unit type of package 2 S03
Number of units in package 2 48
Package 2 height 30.000 cm
Package 2 width 30.000 cm
Package 2 length 40.000 cm
Package 2 weight 7.291 kg
Green premium status for reporting Green Premium product
Total lifecycle carbon footprint 58 kg CO2 eq.
Carbon footprint of the manufacturing phase [a1 to a3] 2.6720909091
Carbon footprint of the manufacturing phase [a1 to a3] 3 kg CO2 eq.
Carbon footprint of the distribution phase [a4] 0.0167723636
Carbon footprint of the distribution phase [a4] 0 kg CO2 eq.
Carbon footprint of the installation phase [a5] 0.0006485936
Carbon footprint of the installation phase [a5] 0 kg CO2 eq.
Carbon footprint of the use phase [b2, b3, b4, b6] 54.9367466667
Carbon footprint of the use phase [b2, b3, b4, b6] 55 kg CO2 eq.
Sustainable packaging Yes
Carbon footprint of the end-of-life phase [c1 to c4] 0.0755394545
Carbon footprint of the end-of-life phase [c1 to c4] 0.1 kg CO2 eq.
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Total lifecycle carbon footprint 57.7017979876
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
Scip number 5e3fdf99-611b-4d07-ad17-6eba84ab488b
China rohs label 5
End of life manual availability ENVEOLI1601004EN
Take-back No
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • End of Life Manual

  • Environmental Disclosure

  • Technical illustration

  • Application Notes

  • Certificates (MSDS)

  • eTechPub

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.