Datasheet
Specifications
Design
Product brand
Physical
Reach regulation
Eu rohs directive
Mercury free
Rohs exemption information
China rohs regulation
Environmental disclosure
Circularity profile
Others
Package 1 bare product quantity
Unit type of package 1
Number of units in package 1
Package 1 height
Package 1 width
Package 1 length
Package 1 weight
Packaging made with recycled cardboard
Packaging without single use plastic
Scip number
Take-back
Take-back
Product contributes to saved and avoided emissions
Recycled metal content at cr level
Removable battery
Carbon footprint (kg.eq.co2 per cr, total life cycle)
Global warming ; total life cycle
Minimum percentage of recycled plastic content
Documents & downloads
hide show-
All
-
Product Brochures
-
Environmental Disclosure
-
Specification Guide
Frequently Asked Questions
What is the difference between S33595 full function test kit and S33594 hand-held test kit
Hide ShowCircuit Breaker Test Set
Resolution:
HHTK - The S33594 hand-held test kit will test the trip function of the breaker and may be used for inhibiting ground fault and thermal imaging, and enable zone selective interlocking (ZSI) self restraint during primary injection testing.
FFTK - The S33595 full function test kit will test LSIG functions as well as the same functions as listed above.
Additional details below:
Can the Micrologic X internal battery (LV833593SP) be replaced while breaker is energised?
Hide ShowThe internal battery is dedicated to the supply of the trip causes LEDs and the internal clock, and there is no effect to the protection setting of the breaker.
Please see below description from the Masterpact MTZ Catalogue.
Are EasyPact MVS circuit breakers for sale in the USA or Canada?
Hide ShowWhere can I buy a EasyPact MVS breaker?
Product Line:
EasyPact MVS circuit breakers
Resolution:
There are no plans for a general release of the EasyPact MVS circuit breaker line in the US.
Masterpact breaker passes all FFTK tests except for ground fault, yet produces error codes on the trip unit; what is the problem?
Hide ShowMasterpact NW
RESOLUTION
Find out if this breaker is used in a MDGF (Modified Differential Ground Fault) system. If so, disconnect wire going to M1 on the secondary block and retest. M1 enables MDGF and disables residual GF, and removing it puts the breaker back into residual mode where it can be tested with the FFTK.
Can the Micrologic FFTK (Full Function Test Kit) be repaired?
Hide ShowMicrologic test equipment
Environment:
Electrical Distribution Equipment
Resolution:
Yes, the FFTK can be repaired in most cases. Have the distributor contact Customer Service for a "Return for Repair" RMA and send it back.
(see internal FA289579)
How can calibration of the S33595 be checked?
Hide ShowCircuit Breaker
Resolution:
The calibration of the test set is checked each time it is used. The S33595 microprocessor is designed with a power-up self check sequence. Each time the unit is powered up, it does a self diagnostic. This checks the health of all electronics, as well as positions of relays and switches inside the test kit. The self diagnostic also checks communications to the screen and the voltage level supplying the test kit. The test kit will not proceed to the test screens until all of these are verified.
The test kit also looks at calibration before each secondary injection test and if the microprocessor determines that it cannot reliably inject the correct signal, an error message will appear on the screen "Test kit calibration error, Test aborted". When this occurs, the test kit must be returned to the factory for repair. Return through your local Schneider Electric (Square D) distributor.
For more details see instruction bulletin for the FFTK:
http://www.schneider-electric.us/en/download/document/48049-183-06/