Browse all
Browse all

MAX9 Miniature Circuit Breaker 1P+N, 10A, C curve, 6000A

Home ProductsCircuit ProtectionMax9Miniature Circuit Breaker

MAX9 Miniature Circuit Breaker 1P+N, 10A, C curve, 6000A

Item Number: MX9MN110

Datasheet

Product Dimensions

Width icon

Width18 mm

Height icon

Height85 mm

Depth icon

Depth71 mm

Clipsal MAX9 Phase Neutral MCBs.

Features

  • MAX Speed compatible with MAXBAR and MAX9 PRO chassis for faster installation up to 15 times vs traditional install
  • MAX Ease terminate active and neutral load cables to device
  • MAX Space active and neutral switched MCB in compact 1 and 3 module devices
  • MAX Professionalism positive contact indication brings visibility on contact closing and opening

Specifications

Design

Range MAX9
Product or component type miniature circuit-breaker
Device application distribution

Physical

[in] rated current 10 A at 30 °C
[ue] rated operational voltage 240 V AC 50/60 Hz
Control type toggle
Local signalling ON/OFF indication
Height 85 mm
Width 18 mm
Depth 71 mm
Mechanical durability 20000 cycles
Electrical durability 20000 cycles
Connections - terminals
  • tunnel type terminals (top or bottom) 1-10 mm² flexible
  • tunnel type terminals (top or bottom) 1-16 mm² rigid
Wire stripping length 14 mm for top or bottom connection
Ip degree of protection IP20
Relative humidity 95 % at 55 °C
Ambient air temperature for operation -25...70 °C
Ambient air temperature for storage -40...85 °C
Toxic heavy metal free Yes
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP2407001EN
Eu rohs directive Compliant

Others

Legacy weee scope In
Average percentage of bio-based plastic content 0 %
Average percentage of recycled plastic content 0 %
Package 4 bare product quantity 1296
Package 3 bare product quantity 108
Package 2 bare product quantity 12
Package 1 bare product quantity 1
Outside of Europe
Warranty duration(in months) bmecat 18
Weee label N/A
Weee applicability Finished product
Poles description 1P + N
Number of protected poles 1
Network type AC
Network frequency 50/60 Hz
Curve code C
Magnetic tripping limit 5...10 x In
Breaking capacity 6000 A Icn at 240 V AC 50/60 Hz conforming to AS/NZS 60898
[ics] rated service breaking capacity 6000 A 100 % - 240 V AC 50/60 Hz
Limitation class 3
[uimp] rated impulse withstand voltage 4 kV
[ui] rated insulation voltage 400 V
Contact position indicator yes
Tightening torque 2 N.m
Grid distance 45 mm
Quality labels RCM
Pollution degree 2
Operating altitude 0...2000 m
Temperature derating table
  • -25 °C ( 12.05 A )
  • -20 °C ( 11.88 A )
  • -15 °C ( 11.71 A )
  • -10 °C ( 11.53 A )
  • -5 °C ( 11.35 A )
  • 0 °C ( 11.17 A )
  • 5 °C ( 10.98 A )
  • 10 °C ( 10.79 A )
  • 15 °C ( 10.6 A )
  • 20 °C ( 10.4 A )
  • 25 °C ( 10.2 A )
  • 30 °C ( 10.0 A )
  • 35 °C ( 9.79 A )
  • 40 °C ( 9.58 A )
  • 45 °C ( 9.36 A )
  • 50 °C ( 9.14 A )
  • 55 °C ( 8.91 A )
  • 60 °C ( 8.68 A )
  • 65 °C ( 8.47 A )
  • 70 °C ( 8.24 A )
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 7.4 cm
Package 1 width 1.8 cm
Package 1 length 9.4 cm
Package 1 weight 115 g
Unit type of package 2 BB1
Number of units in package 2 12
Package 2 height 22 cm
Package 2 width 9.9 cm
Package 2 length 8.7 cm
Package 2 weight 1.49 kg
Unit type of package 3 S03
Number of units in package 3 108
Package 3 height 30 cm
Package 3 width 30 cm
Package 3 length 40 cm
Package 3 weight 13.95 kg
Green premium status for reporting Green Premium product
Total lifecycle carbon footprint 5 kg CO2 eq.
Carbon footprint of the manufacturing phase [a1 to a3] 1.088030528192829
Carbon footprint of the manufacturing phase [a1 to a3] 1 kg CO2 eq.
Carbon footprint of the distribution phase [a4] 0.01918408862395865
Carbon footprint of the distribution phase [a4] 0 kg CO2 eq.
Carbon footprint of the installation phase [a5] 0.0001855871961538998
Carbon footprint of the installation phase [a5] 0 kg CO2 eq.
Carbon footprint of the use phase [b2, b3, b4, b6] 3.2971104637631807
Carbon footprint of the use phase [b2, b3, b4, b6] 3 kg CO2 eq.
Sustainable packaging No
Carbon footprint of the end-of-life phase [c1 to c4] 0.3753222570025987
Carbon footprint of the end-of-life phase [c1 to c4] 0.4 kg CO2 eq.
Pvc free No
Silicone-free  No
Energy efficiency optimized False
F-gas free N/A
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Total lifecycle carbon footprint 4.779832924778721
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard No
Packaging without single use plastic No
Pvc free No
Silicone-free No
End of life manual availability N/A
Take-back No
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Environmental Disclosure

  • Technical illustration

  • Declaration of Conformity

  • Certificates (MSDS)

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.