Compact NSX <630, Circuit breaker, ComPact NSX400F, 36kA/415VAC, MicroLogic 2.3 trip unit 400A, 3 poles 3d

Compact NSX <630, Circuit breaker, ComPact NSX400F, 36kA/415VAC, MicroLogic 2.3 trip unit 400A, 3 poles 3d

Item Number: LV432676

Datasheet

Product Dimensions

Width icon

Width140 mm

Height icon

Height255 mm

Depth icon

Depth110 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

ComPact

Range of product

ComPact NSX400...630

Product or component type

circuit breaker

Device application

distribution

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[in] rated current

400 A at 40 °C

[ue] rated operational voltage

690 V AC 50/60 Hz

Control type

toggle

Mounting mode

fixed

Mechanical durability

15000 cycles

Electrical durability

3000 cycles at 690 V In|6000 cycles at 690 V In/2|6000 cycles at 440 V In|12000 cycles at 440 V In/2

Mounting support

backplate

Protection type

L : for overload protection (long time)|So : for short time short-circuit protection with fixed delay|I : for instantaneous short-circuit protection

Local signalling

flashing LED (green) for ready to operate|LED 105 % Ir (red) for overload|LED 90 % Ir (orange) for overload

Width

140 mm

Height

255 mm

Depth

110 mm

Net weight

6.05 kg

Standards

EN/IEC 60947

Product certifications

CCC|EAC|Marine

Ip degree of protection

IP40 conforming to IEC 60529

Ik degree of protection

IK07 conforming to IEC 62262

Ambient air temperature for operation

-25...70 °C

Ambient air temperature for storage

-50...85 °C

Relative humidity

0...95 %

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Compliant with Exemptions

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental disclosure

ENVPEP2304018EN

Circularity profile

ENVEOLI2304018EN

California proposition 65

WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov

Others

Commercial status history

SESA301466 | Tue Jan 09 21:02:00 EST 2024 | From Import Local | From 18 to 19

Important message

This product has been switched to new ComPacT range and is no longer commercialized.

Package 1 bare product quantity

1

Product name

ComPact NSX

Device short name

NSX400F

Poles description

3P

Protected poles description

3t

Network type

AC

Network frequency

50/60 Hz

Suitability for isolation

yes conforming to EN/IEC 60947-2

Utilisation category

category A

Breaking capacity

40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2|85 kA at 240 V AC 50/60 Hz conforming to UL 508|25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2|36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2|10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2|35 kA at 480 V AC 50/60 Hz conforming to UL 508|20 kA at 600 V AC 50/60 Hz conforming to UL 508|20 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2|30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2

Breaking capacity code

F 36 kA 415 V AC

Trip unit name

MicroLogic 2.3

Trip unit technology

electronic

Trip unit protection functions

LSoI

[ui] rated insulation voltage

800 V AC 50/60 Hz

[uimp] rated impulse withstand voltage

8 kV

[ics] rated service breaking capacity

40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2|36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2|10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2|10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2|25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2|30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2

Upside connection

front

Downside connection

front

Connection pitch

45 mm

Trip unit rating

400 A at 40 °C

Long time pick-up adjustment type ir

adjustable 9 settings

Long time pick-up adjustment range

160...400 A

Long time delay adjustment type

fixed

[tr] long-time delay adjustment range

16 s at 6 x Ir

Thermal memory

20 minutes before and after tripping

Short-time pick-up adjustment type isd

adjustable 9 settings

[isd] short-time pick-up adjustment range

1.5...10 x Ir

Short-time delay adjustment type

fixed

Instantaneous pick-up adjustment type ii

fixed

Instantaneous pick-up adjustment range

4800 A

Earth-leakage protection

without

Zone selective interlocking zsi

without

Number of slots

6 slot(s)

Compatibility code

NSX400

Overvoltage category

class II

Electrical shock protection class

class II

Pollution degree

3 conforming to IEC 60664-1

Operating altitude

0...2000 m without derating|2000 m...5000 m with derating

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

15 cm

Package 1 width

16 cm

Package 1 length

29 cm

Package 1 weight

5.589 kg

Unit type of package 2

S04

Number of units in package 2

3

Package 2 height

30 cm

Package 2 width

40 cm

Package 2 length

60 cm

Package 2 weight

17.434 kg

Unit type of package 3

P12

Number of units in package 3

12

Package 3 height

80 cm

Package 3 width

80 cm

Package 3 length

120 cm

Package 3 weight

80 kg

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Product Brochures

  • Technical Data Catalogues

  • Installation Instruction

  • End of Life Manual

  • Environmental Disclosure

  • Operating Manuals

  • Technical Drawing

  • Declaration of Conformity