Acti9 SAU Chassis 3PH 400A, 18mm for iC60 MCB & RCBO, 84 Poles, Top or Bottom Feed

Acti9 SAU Chassis 3PH 400A, 18mm for iC60 MCB & RCBO, 84 Poles, Top or Bottom Feed

Item Number: SAU40084183

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range Acti9
Product or component type chassis
Device application distribution

Physical

[in] rated current 400 A
Rated voltage 415 V AC
Number of poles 84
Number of poles 84 x 18 mm
Width 245 mm
Length 950 mm
Depth 95 mm
Net weight 6.96 kg
Standards AS/NZS 61439
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP1602010_V1
Eu rohs directive Compliant By Exemption
California proposition 65 WARNING: This product can expose you to chemicals including: Lead, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Others

Legacy weee scope Out
Package 1 bare product quantity 1
Average percentage of bio-based plastic content 0 %
Average percentage of recycled plastic content 0 %
Weee applicability Finished product
Weee label N/A
Outside of Europe
Busbar type standard
Incomer device
  • switch disconnector - 3P
  • MCCB - 3P
Protection device type
  • miniature circuit breaker (MCB) as outgoer
  • residual current circuit breaker with overcurrent protection (RCBO) as outgoer
Network type AC
Number of ways
  • 1 way (incomer) - 3P
  • 1 way (outgoer) - 1P or 3P
Short-circuit withstand 25 kA 0.1 s
[ui] rated insulation voltage 500 V
[uimp] rated impulse withstand voltage 6 kV
Busbar pitch 18 mm
Location of connection top or bottom
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 9.5 cm
Package 1 width 24.3 cm
Package 1 length 95 cm
Package 1 weight 5.956 kg
Total lifecycle carbon footprint 31 kg CO2 eq.
Carbon footprint of the manufacturing phase [a1 to a3] 29.5090847222
Carbon footprint of the manufacturing phase [a1 to a3] 30 kg CO2 eq.
Carbon footprint of the distribution phase [a4] 0.7684480833
Carbon footprint of the distribution phase [a4] 0.8 kg CO2 eq.
Carbon footprint of the installation phase [a5] 0.0194595756
Carbon footprint of the installation phase [a5] 0 kg CO2 eq.
Carbon footprint of the use phase [b2, b3, b4, b6] 0
Carbon footprint of the use phase [b2, b3, b4, b6] 0 kg CO2 eq.
Sustainable packaging No
Carbon footprint of the end-of-life phase [c1 to c4] 0.571776
Carbon footprint of the end-of-life phase [c1 to c4] 0.6 kg CO2 eq.
Pvc free No
Energy efficiency optimized False
F-gas free N/A
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Total lifecycle carbon footprint 30.8687683811
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard No
Packaging without single use plastic No
Pvc free No
Take-back No
Warranty (in months) 18