Acti9 Earth leakage add-on block 1P + N, 63A, 30mA, A type

Home ProductsCircuit ProtectionActi9Earth leakage add-on block

Acti9 Earth leakage add-on block 1P + N, 63A, 30mA, A type

Item Number: A9V02663

Datasheet

Product Dimensions

Width icon

Width54 mm

Height icon

Height91 mm

Depth icon

Depth73.5 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Acti9

Range of product

iC60

Product or component type

add-on residual current device

Product compatibility

single terminal

Warranty

18 months

Physical

[in] rated current

63 A

[ue] rated operational voltage

  • 230...240 V AC 50/60 Hz conforming to EN/IEC 61009-1
  • 230...240 V AC 50/60 Hz conforming to EN/IEC 61009-2-1

Standards

  • EN/IEC 61009-1
  • EN/IEC 61009-2-1

Range compatibility

Acti 9 Acti9 iC60

Local signalling

trip indicator

Mounting mode

clip-on

Mounting support

DIN rail

Height

91 mm

Width

54 mm

Depth

73.5 mm

Net weight

0.165 kg

Connections - terminals

  • tunnel type terminal downside for 1 cable(s) 1-35 mm² rigid without cable end
  • tunnel type terminal downside for 1 cable(s) 1-25 mm² flexible without cable end
  • tunnel type terminal downside for 1 cable(s) 1-25 mm² flexible with cable end

Wire stripping length

14 mm for bottom connection

Ip degree of protection

  • IP20 conforming to IEC 60529
  • IP40 (modular enclosure) conforming to IEC 60529

Ambient air temperature for operation

-25...60 °C

Ambient air temperature for storage

-40...85 °C

Mercury free

Yes

Rohs exemption information

Yes

Environmental disclosure

ENVPEP1409017_V3-EN

Eu rohs directive

Compliant with Exemptions

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Compliant By Exemption

China rohs regulation

Product out of China RoHS scope. Substance declaration for your information

Others

Legacy weee scope

In

Package 1 bare product quantity

1

Average percentage of recycled plastic content

0 %

At least in Europe

Warranty duration(in months) bmecat

18

Weee label

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Product name

Acti9 Vigi iC60

Device short name

Vigi iC60

Poles description

2P

Neutral position

left

Earth-leakage sensitivity

30 mA

Earth-leakage protection time delay

instantaneous

Earth-leakage protection class

type A

Network type

AC

Network frequency

50/60 Hz

9 mm pitches

4

Device location in system

outgoer

Residual current tripping technology

voltage independent

[ui] rated insulation voltage

500 V AC 50/60 Hz conforming to IEC 60947-2

[uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947-2

Electrical connection to mcb

by screws

Comb busbar and distribution block compatibility

bottom: YES

Total power losses

4.6 W

Power losses per pole

2.3 W

Tightening torque

3.5...3.5 N.m bottom

Pollution degree

3 conforming to IEC 60947-2

Electromagnetic compatibility

8/20 µs impulse withstand, 250 A conforming to IEC 61009-1

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

8.5 cm

Package 1 width

11.3 cm

Package 1 length

14.5 cm

Package 1 weight

239.0 g

Unit type of package 2

S03

Number of units in package 2

15

Package 2 height

30.0 cm

Package 2 width

30.0 cm

Package 2 length

40.0 cm

Package 2 weight

4.087 kg

Green premium status for reporting

Green Premium product

Total lifecycle carbon footprint

6 kg CO2 eq.

Carbon footprint of the manufacturing phase [a1 to a3]

1.504442215944078

Carbon footprint of the manufacturing phase [a1 to a3]

2 kg CO2 eq.

Carbon footprint of the distribution phase [a4]

0.04657315748651767

Carbon footprint of the distribution phase [a4]

0 kg CO2 eq.

Carbon footprint of the installation phase [a5]

0.047619196229670216

Carbon footprint of the installation phase [a5]

0 kg CO2 eq.

Carbon footprint of the use phase [b2, b3, b4, b6]

3.963838609707238

Carbon footprint of the use phase [b2, b3, b4, b6]

4 kg CO2 eq.

Sustainable packaging

No

Carbon footprint of the end-of-life phase [c1 to c4]

0.4365456736597844

Carbon footprint of the end-of-life phase [c1 to c4]

0.4 kg CO2 eq.

Energy efficiency optimized

False

Take-back

No

Product contributes to saved and avoided emissions

No

Removable battery

N/A

Total lifecycle carbon footprint

5.999018853027288

Average percentage of recycled metal content

0 %

Packaging made with recycled cardboard

No

Packaging without single use plastic

Yes

Scip number

b078722f-7853-4e1e-a05b-29638f57b0ab

End of life manual availability

N/A

Take-back

No

Weee label

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Warranty (in months)

18
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Environmental Disclosure

  • Installation Instruction

  • Operating Manuals

  • Certificates (MSDS)

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.