The breaking capacity and operating time of the Acti9 iMX+OF shunt trip release module (Ref: A9A26946).

FAQ000278670

04 December 2025

Issue: 

What is the breaking capacity and operating time of the Acti9 iMX+OF shunt trip release module (Ref: A9A26946)?

 

Product Line:

Acti9 iMX+OF Auxiliary Trip Units

 

Environment:

Used with Acti9 circuit breakers (e.g., iC60, iC65) for remote tripping applications.

 

Resolution:

Breaking Capacity:

The A9A26946 module does not have its own breaking capacity because it is not a circuit breaker. It operates in conjunction with the associated protection device (e.g., Acti9 iC60/iC65), which determines the system’s breaking capacity.

 

Operating Time:

• Depends on the control voltage applied.

• For a sudden voltage application (0 → 100% of Un), the iMX operating time can be <10 ms.

• Combined with the associated circuit breaker, the total power circuit breaking time can be approximately <18 ms.

For detailed specifications, refer to Global Module CA908029E.

;