What is the difference between the iC60N and the iC60H Circuit Breakers?

FA298511

26 August 2025

The differences between the iC60N and iC60H series of circuit breakers is the iC60N has a breaking capacity of 6kA at 240/415V, C Curve in accordance with AS/NZS60898.1, where as the iC60H has a breaking capacity of 10kA at 240/415V B, C & D Curve in accordance with AS/NZS60898.1.

In Australia the iC60N is only available in C Curve where as the iC60H is available in B, C & D Curve.
 
iC60N & iC60H Dimensions
 iC60N 
Connection: Tunnel terminals for the following cables

- up to 25A : 25mm2 stranded
- 32 to 63A : 35mm2 stranded


For further information please visit https://www.schneider-electric.com.au/en/product-subcategory/1605-acti-9-miniature-circuit-breakers---mcbs/


 

;