TeSys K Control Relay 3 NO + 1 NC , <= 690 V , 230 V AC coil

TeSys K Control Relay 3 NO + 1 NC , <= 690 V , 230 V AC coil

Item Number: CA2KN313P7

Datasheet

Product Dimensions

Width icon

Width45 mm

Height icon

Height58 mm

Depth icon

Depth57 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys K control relay

Range

TeSys

Product or component type

control relay

Warranty

18 months

Physical

[ue] rated operational voltage

<= 690 V <= 400 Hz

Mounting support

  • plate
  • rail

Connections - terminals

  • spring terminals 1 cable(s) 0.75-1.5 mm²solid
  • spring terminals 1 cable(s) 0.75-1.5 mm²flexible without cable end

Mechanical durability

10 Mcycles

Insulation resistance

> 10 MOhm

Height

58 mm

Width

45 mm

Depth

57 mm

Net weight

0.18 kg

Standards

  • EN/IEC 60947-4-1
  • GB/T 14048.4
  • UL 60947-4-1
  • CSA C22.2 No 60947-4-1
  • JIS C8201-4-1

Product certifications

  • CB Scheme
  • CCC
  • UL
  • CSA
  • EAC
  • CE
  • UKCA

Ambient air temperature for operation

-25...50 °C

Ambient air temperature for storage

-50...80 °C

Reach free of svhc

Yes

Eu rohs directive

Compliant

Toxic heavy metal free

Yes

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental disclosure

ENVPEP1503003EN

Circularity profile

ENVEOLI1503003EN

California proposition 65

WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Package 1 bare product quantity

1

Product name

TeSys CAK

Device short name

CA2K

Contactor application

control circuit

Utilisation category

  • AC-15
  • DC-13

Pole contact composition

3 NO + 1 NC

Control circuit type

AC at 50/60 Hz

[uc] control circuit voltage

230 V AC 50/60 Hz

[ith] conventional free air thermal current

10 A (at 50 °C)

Irms rated making capacity

110 A conforming to IEC 60947

Associated fuse rating

  • 10 A gG conforming to IEC 60947
  • 10 A gG conforming to VDE 0660

[ui] rated insulation voltage

  • 690 V conforming to IEC 60947
  • 750 V conforming to VDE 0110 group C
  • 690 V conforming to BS 5424
  • 600 V conforming to CSA C22.2 No 14

Control circuit voltage limits

  • drop-out: 0.2...0.75 Uc (at <50 °C)
  • operational: 0.8...1.15 Uc (at <50 °C)

Operating time

  • 10...20 ms coil de-energisation and NO opening
  • 10...20 ms coil energisation and NO closing
  • 15...25 ms coil de-energisation and NC closing
  • 5...15 ms coil energisation and NC opening

Maximum operating rate

10000 cyc/h

Immunity to microbreaks

2 ms

Inrush power in va

30 VA (at 20 °C)

Hold-in power consumption in va

4.5...4.5 VA (at 20 °C)

Heat dissipation

1.3...1.3 W

Minimum switching voltage

17 V

Minimum switching current

5 mA

Non overlap distance

0.5 mm

Compatibility code

CA2K

Protective treatment

TC conforming to IEC 60068

Operating altitude

2000 m without derating

Flame retardance

  • V1 conforming to UL 94
  • requirement 2 conforming to NF F 16-101
  • requirement 2 conforming to NF F 16-102

Mechanical robustness

  • vibrations contactor open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
  • vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
  • shocks contactor open: 10 Gn for 11 ms conforming to IEC 60068-2-27
  • shocks contactor closed: 15 Gn for 11 ms conforming to IEC 60068-2-27

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

4.8 cm

Package 1 width

6.5 cm

Package 1 length

6.2 cm

Package 1 weight

207 g

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • Technical Drawing

  • Certificates (MSDS)

  • Declaration of Conformity