Item Number: LC1D1156B5

Datasheet

Product Dimensions

Width icon

Width120 mm

Height icon

Height158 mm

Depth icon

Depth136 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range TeSys
Range of product TeSys Deca
Product or component type contactor
Warranty 18 months

Physical

[ue] rated operational voltage
  • power circuit: <= 1000 V AC 25...400 Hz
  • power circuit: <= 300 V DC
[ie] rated operational current
  • 200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
  • 115 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
  • 115 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
Mechanical durability 8 Mcycles
Electrical durability
  • 0.8 Mcycles 200 A AC-1 at Ue <= 440 V
  • 0.95 Mcycles 115 A AC-3 at Ue <= 440 V
  • 0.95 Mcycles 115 A AC-3e at Ue <= 440 V
Connections - terminals
  • control circuit: lugs-ring terminals - external diameter: 8 mm
  • power circuit: lugs-ring terminals - external diameter: 25 mm
  • power circuit: bars 1 - busbar cross section: 5 x 25 mm
Insulation resistance > 10 MOhm for signalling circuit
Mounting support
  • rail
  • plate
Standards
  • CSA C22.2 No 14
  • EN 60947-4-1
  • EN 60947-5-1
  • IEC 60947-4-1
  • IEC 60947-5-1
  • UL 508
Product certifications
  • UL
  • GL
  • DNV
  • GOST
  • LROS (Lloyds register of shipping)
  • BV
  • CSA
  • RINA
  • CCC
Ip degree of protection IP20 front face conforming to IEC 60529
Climatic withstand
  • conforming to IACS E10 exposure to damp heat
  • conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Height 158 mm
Width 120 mm
Depth 136 mm
Net weight 2.5 kg
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP060301EN
China rohs regulation Product out of China RoHS scope
Eu rohs directive Compliant

Others

Legacy weee scope In
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty duration(in months) bmecat 18
At least in Europe
Package 1 bare product quantity 1
Device short name LC1D
Contactor application
  • resistive load
  • motor control
Utilisation category
  • AC-1
  • AC-4
  • AC-3
  • AC-3e
Poles description 3P
[uc] control circuit voltage 24 V AC 50 Hz
Motor power kw
  • 30 kW at 220...230 V AC 50/60 Hz (AC-3)
  • 55 kW at 380...400 V AC 50/60 Hz (AC-3)
  • 59 kW at 415...440 V AC 50/60 Hz (AC-3)
  • 75 kW at 500 V AC 50/60 Hz (AC-3)
  • 80 kW at 660...690 V AC 50/60 Hz (AC-3)
  • 65 kW at 1000 V AC 50/60 Hz (AC-3)
  • 18.5 kW at 400 V AC 50/60 Hz (AC-4)
  • 30 kW at 220...230 V AC 50/60 Hz (AC-3e)
  • 55 kW at 380...400 V AC 50/60 Hz (AC-3e)
  • 59 kW at 415...440 V AC 50/60 Hz (AC-3e)
  • 75 kW at 500 V AC 50/60 Hz (AC-3e)
  • 80 kW at 660...690 V AC 50/60 Hz (AC-3e)
  • 65 kW at 1000 V AC 50/60 Hz (AC-3e)
Motor power hp
  • 30 hp at 200/208 V AC 50/60 Hz for 3 phases motors
  • 40 hp at 230/240 V AC 50/60 Hz for 3 phases motors
  • 75 hp at 460/480 V AC 50/60 Hz for 3 phases motors
  • 100 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Compatibility code LC1D
Pole contact composition 3 NO
Contact compatibility M13
Protective cover with
[ith] conventional free air thermal current 200 A (at 60 °C) for power circuit
Irms rated making capacity
  • 1260 A at 440 V for power circuit conforming to IEC 60947
  • 140 A AC for signalling circuit conforming to IEC 60947-5-1
  • 250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity 1100 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current
  • 250 A 40 °C - 10 min for power circuit
  • 550 A 40 °C - 1 min for power circuit
  • 950 A 40 °C - 10 s for power circuit
  • 1100 A 40 °C - 1 s for power circuit
  • 100 A - 1 s for signalling circuit
  • 120 A - 500 ms for signalling circuit
  • 140 A - 100 ms for signalling circuit
Associated fuse rating
  • 250 A gG at <= 690 V coordination type 1 for power circuit
  • 200 A gG at <= 690 V coordination type 2 for power circuit
  • 10 A gG for signalling circuit
Average impedance 0.6 mOhm - Ith 200 A 50 Hz for power circuit
Power dissipation per pole
  • 24 W AC-1
  • 7.9 W AC-3
  • 7.9 W AC-3e
[ui] rated insulation voltage
  • power circuit: 600 V CSA certified
  • power circuit: 600 V UL certified
  • power circuit: 1000 V conforming to IEC 60947-4-1
  • signalling circuit: 690 V conforming to IEC 60947-1
  • signalling circuit: 600 V CSA certified
  • signalling circuit: 600 V UL certified
Overvoltage category III
Pollution degree 3
[uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947
Safety reliability level
  • B10d = 684932 cycles contactor with nominal load conforming to EN/ISO 13849-1
  • B10d = 10000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Control circuit type AC at 50 Hz
Coil technology without built-in suppressor module
Control circuit voltage limits
  • 0.3...0.6 Uc (-40-70 °C):drop-out AC 50 Hz
  • 0.85...1.1 Uc (-40-55 °C):operational AC 50 Hz
  • 1...1.1 Uc (55-70 °C):operational AC 50 Hz
Inrush power in va 300 VA 50 Hz cos phi 0.8 (at 20 °C)
Hold-in power consumption in va 22 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation 3...8 W at 50 Hz
Operating time
  • 6...20 ms opening
  • 20...50 ms closing
Tightening torque
  • control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5
  • control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5
  • power circuit: 12 N.m - on lugs-ring terminals hexagonal screw head 13 mm M8
  • power circuit: 12 N.m - on bars hexagonal screw head 13 mm M8
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type
  • type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
  • type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Non-overlap time
  • 1.5 ms on de-energisation between NC and NO contact
  • 1.5 ms on energisation between NC and NO contact
Protective treatment TH conforming to IEC 60068-2-30
Permissible ambient air temperature around the device
  • -40...60 °C
  • 60...70 °C with derating
Operating altitude 0...3000 m
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness
  • vibrations contactor open (2 Gn, 5...300 Hz)
  • vibrations contactor closed (4 Gn, 5...300 Hz)
  • shocks contactor closed (15 Gn for 11 ms)
  • shocks contactor open (6 Gn for 11 ms)
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 16.8 cm
Package 1 width 20.8 cm
Package 1 length 18.5 cm
Package 1 weight 2.11 kg
Sustainable packaging No
Pvc free Yes
Pvc free Yes
End of life manual availability ENVEOLI100405EN
Weee label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Warranty (in months) 18

Documents & downloads

Filter items
  • All

  • Technical Data Catalogues

  • Installation Instruction

  • Certificates (MSDS)

  • Declaration of Conformity

  • Declaration of Conformity (Sustainability)

  • Product Change Notification