TeSys D Contactor Coil LXD1, 21 V AC 50/60 Hz for 9… 38 A Contactor

TeSys D Contactor Coil LXD1, 21 V AC 50/60 Hz for 9… 38 A Contactor

Item Number: LXD1Z7

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys Deca

Range

TeSys

Product or component type

contactor coil

Product compatibility

  • LC1DT20...DT40
  • LC1D09...D38
  • CAD

Warranty

18 months

Physical

Mechanical durability

15 Mcycles

Ambient air temperature for operation

-5...60 °C

Net weight

0.07 kg

Reach free of svhc

Yes

Eu rohs directive

Pro-active compliance (Product out of EU RoHS legal scope)

Toxic heavy metal free

Yes

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

California proposition 65

WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Device short name

LXD1

Control circuit type

AC at 50/60 Hz

[uc] control circuit voltage

21 V AC 50/60 Hz

Average resistance

4.17 Ohm at 20 °C

Inductance of closed circuit

0.17 H

Maximum operating rate

3600 cyc/h 60 °C

Coil technology

without built-in suppressor module

Control circuit voltage limits

  • drop-out: 0.3...0.6 Uc at 50/60 Hz (at <60 °C)
  • operational: 0.8...1.1 Uc at 50 Hz (at <60 °C)
  • operational: 0.85...1.1 Uc at 60 Hz (at <60 °C)

Inrush power in va

  • 70 VA 60 Hz cos phi 0.75 (at 20 °C)
  • 70 VA 50 Hz cos phi 0.75 (at 20 °C)

Hold-in power consumption in va

  • 7.5...7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
  • 7 VA 50 Hz cos phi 0.3 (at 20 °C)

Heat dissipation

2...3 W at 50/60 Hz

Unit type of package 1

PCE

Number of units in package 1

1

Pvc free

Yes

Pvc free

Yes
Show all specifications

Documents & downloads

hide show

Frequently Asked Questions

What is the replacement AC coil for CAD32 and CAD50 relay?

Hide Show
Issue:
AC coil replacement for CAD32 and CAD50

Product Line:
Relays

Environment:
Tesys CAD Control Relays

Cause:
Product selection

Resolution:
Volt = coil part number
12 = LXD1J7
21 = LXD1Z7
24 = LXD1B7
32 = LXD1C7
36 = LXD1CC7
42 = LXD1D7
48 = LXD1E7
60 = LXD1EE7
100 = LXD1K7
110 = LXD1F7
115 = LXD1FE7
120 = LXD1G7
127 = LXD1FC7
200 = LXD1L7
208 = LXD1LL7
220/230 = LXD1M7
230 595 21 LXD1P7
230/240 = LXD1U7
277 781 30 LXD1W7
380/400 = LXD1Q7
400 = LXD1V7
415 = LXD1N7
440 = LXD1R7
480 = LXD1T7
600 = LXD1X7
690 = LXD1Y7