TeSys D Contactor 4P(2 NO + 2 NC) , AC-1 , <= 440V, 80 A , 32V AC 50 Hz coil
Item Number: LC1D65008C5
Specifications
Design
Range
Range of product
Product or component type
Warranty
Physical
[ue] rated operational voltage
- power circuit: <= 690 V AC 25...400 Hz
- power circuit: <= 300 V DC
[ie] rated operational current
Mechanical durability
Electrical durability
Connections - terminals
- control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end
- control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end
- control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end
- power circuit: screw clamp terminals 1 1-35 mm² - cable stiffness: flexible without cable end
- power circuit: screw clamp terminals 2 1-25 mm² - cable stiffness: flexible without cable end
- power circuit: screw clamp terminals 1 1-35 mm² - cable stiffness: flexible with cable end
- power circuit: screw clamp terminals 2 1-25 mm² - cable stiffness: flexible with cable end
- power circuit: screw clamp terminals 1 1-35 mm² - cable stiffness: solid without cable end
- power circuit: screw clamp terminals 2 1-25 mm² - cable stiffness: solid without cable end
Mounting support
- rail
- plate
Standards
- CSA C22.2 No 14
- EN 60947-4-1
- EN 60947-5-1
- IEC 60947-4-1
- IEC 60947-5-1
- UL 508
Product certifications
- CSA
- RINA
- UL
- BV
- GL
- LROS (Lloyds register of shipping)
- DNV
- GOST
- CCC
Ip degree of protection
Climatic withstand
Height
Width
Depth
Net weight
Reach free of svhc
Eu rohs directive
Toxic heavy metal free
Mercury free
Rohs exemption information
China rohs regulation
Environmental disclosure
Circularity profile
Others
Device short name
Contactor application
Utilisation category
Poles description
[uc] control circuit voltage
Compatibility code
Pole contact composition
Protective cover
[ith] conventional free air thermal current
Irms rated making capacity
Rated breaking capacity
[icw] rated short-time withstand current
- 520 A 40 °C - 10 s for power circuit
- 900 A 40 °C - 1 s for power circuit
- 110 A 40 °C - 10 min for power circuit
- 260 A 40 °C - 1 min for power circuit
Associated fuse rating
- 125 A gG at <= 690 V coordination type 1 for power circuit
- 125 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
Power dissipation per pole
[ui] rated insulation voltage
- power circuit: 600 V CSA certified
- power circuit: 600 V UL certified
- power circuit: 690 V conforming to IEC 60947-4-1
Overvoltage category
Pollution degree
[uimp] rated impulse withstand voltage
Safety reliability level
- B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
- B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Control circuit type
Coil technology
Control circuit voltage limits
- 0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz
- 0.3...0.6 Uc (-40-70 °C):drop-out AC 50 Hz
- 1...1.1 Uc (60-70 °C):operational AC 50 Hz
Inrush power in va
Hold-in power consumption in va
Heat dissipation
Operating time
- 4...19 ms opening
- 12...26 ms closing
Tightening torque
- control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
- control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
- power circuit: 8 N.m - on screw clamp terminals - cable 25-35 mm² hexagonal screw head 4 mm
- power circuit: 5 N.m - on screw clamp terminals - cable 1-25 mm² hexagonal screw head 4 mm
Contact compatibility
Protective treatment
Permissible ambient air temperature around the device
- -40...60 °C
- 60...70 °C with derating
Operating altitude
Fire resistance
Flame retardance
Mechanical robustness
- shocks contactor open (8 Gn for 11 ms)
- shocks contactor closed (10 Gn for 11 ms)
- vibrations contactor opened (2 Gn, 5...300 Hz)
- vibrations contactor closed (3 Gn, 5...300 Hz)
Unit type of package 1
Number of units in package 1
Weee
Pvc free
Pvc free
Documents & downloads
hide show-
All
-
CAD Files and Packs
-
Technical Data Catalogues
-
Certificates (MSDS)