Browse all
Browse all

Acti9 Arc fault detection switch Acti9 iARC, 1P+N, 25A, 10000A

Home ProductsCircuit ProtectionActi9Arc fault detection switch

Acti9 Arc fault detection switch Acti9 iARC, 1P+N, 25A, 10000A

Item Number: A9TS1225

Datasheet

Product Dimensions

Width icon

Width36 mm

Height icon

Height91 mm

Depth icon

Depth75 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Acti9

Product or component type

arc fault detection switch

Physical

[in] rated current

25 A

[ue] rated operational voltage

230...240 V AC 50 Hz conforming to IEC 62606

Control type

toggle

Local signalling

ON, OFF, fault trip

Mounting mode

clip-on

Mounting support

DIN rail

Mechanical durability

20000 cycles

Electrical durability

10000 cycles 240 V AC 50 Hz conforming to IEC 62606

Connections - terminals

  • tunnel type terminal2 cable(s) 2.5-2.5 mm² rigid
  • tunnel type terminal1 cable(s) 16-16 mm² rigid
  • tunnel type terminal2 cable(s) 2.5-2.5 mm² flexible
  • tunnel type terminal1 cable(s) 10-10 mm² flexible

Cable entry

top and bottom

Wire stripping length

14 mm

Height

91 mm

Width

36 mm

Depth

75 mm

Net weight

205 g

Ip degree of protection

IP20 conforming to IEC 60529

Relative humidity

95 % at 55 °C

Ambient air temperature for operation

-25...60 °C

Ambient air temperature for storage

-40...80 °C

Standards

IEC 62606

Mercury free

Yes

Rohs exemption information

Yes

Environmental disclosure

ENVPEP2205013EN

China rohs regulation

Product out of China RoHS scope

Eu rohs directive

Compliant By Exemption

Others

Package 1 bare product quantity

1

Legacy weee scope

In

Outside of Europe

Warranty duration(in months) bmecat

18

Weee label

N/A

Product specific application

arc fault detection

Product name

Acti9 iARC

Device short name

iARC

Poles description

1P + N

Neutral position

left

Network type

AC

Rated breaking and making capacity

Im = 500 A

Rated conditional short-circuit current

  • upstream MCB 25A: Inc 10 kA
  • upstream RCBO 25A: Inc 10 kA

Device location in system

outgoer

Network frequency

50 Hz

[ui] rated insulation voltage

  • 250 V AC 50 Hz between phase and neutral
  • 400 V AC 50 Hz between phases

[uimp] rated impulse withstand voltage

4 kV conforming to IEC 62606

Threshold tripping voltage

275 V for +/- 5 V

Contact position indicator

yes

Heat dissipation

4.38...4.38 W at 240 V - 25 A

Total power losses

4.4 W

Power losses per pole

4.4 W

Locking options description

padlocking device

Tightening torque

2 N.m

9 mm pitches

4

Pollution degree

2 conforming to IEC 62606

Overvoltage category

III

Tropicalisation

severity B conforming to IEC 60068-2-30 for 28 d

Operating altitude

2000 m

Quality labels

RCM

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

7.5 cm

Package 1 width

3.6 cm

Package 1 length

9.1 cm

Package 1 weight

240.0 g

Sustainable packaging

No

Halogen-free status

Halogen free plastic parts product

Take-back

No

Average percentage of recycled metal content

0 %

Scip number

8b63a121-e746-45cc-9c47-575c8603416f

Halogen-free status

Halogen free plastic parts product

End of life manual availability

ENVEOLI2205013EN

Take-back

No

Warranty (in months)

18
Show all specifications