TeSys H Ultra compact starter TeSys Hybrid, Safe Torque Off, 3P, 500VAC, 3kW at 400V, 110 to 230VAC
Item Number: LZ7H6X5FU
Specifications
Design
Range
Product or component type
Physical
[ue] rated operational voltage
[ie] rated operational current
- 6.5 A at 500 V AC-53A
- 9 A at 500 V AC-51
- 4.5 A at 500 V AC-53A mounting side by side
- 6 A at 500 V AC-51 mounting side by side
Electrical durability
Mounting mode
Mounting support
Connections - terminals
- screw clamp terminals 1 cable(s) 0.2-2.5 mm² - rigid
- screw clamp terminals 1 cable(s) 0.25-2.5 mm² - flexible - with cable end
- screw clamp terminals 1 cable(s) 0.2-2.5 mm² - flexible - without cable end
Standards
- IEC 60947-4-2
- UL 60947-4-1
Width
Height
Depth
Net weight
Ip degree of protection
Ambient air temperature for operation
- -25...30 °C without derating
- 30...70 °C with derating
Ambient air temperature for storage
Reach free of svhc
Eu rohs directive
Toxic heavy metal free
Mercury free
Rohs exemption information
China rohs regulation
California proposition 65
Others
Package 1 bare product quantity
Product name
Device short name
Motor starter type
Poles description
Thermal protection adjustment range
Motor power kw
- 1.5 kW at 220 V AC 0.65
- 1.5 kW at 230 V AC 0.65
- 2.2 kW at 380 V AC 0.65
- 3 kW at 400 V AC 0.65
- 3 kW at 415 V AC 0.65
- 3 kW at 440 V AC 0.65
- 3 kW at 500 V AC 0.65
Motor power hp
- 1 hp at 200 V AC
- 1.5 hp at 230 V AC
- 3 hp at 460 V AC
[uc] control circuit voltage
Safety level
- SIL 3 conforming to IEC 61508-1 stop function
- PL = e conforming to ISO 13849-1 stop function
- SIL 2 conforming to IEC 61508-1 motor protection
Safety reliability data
- SFF = 99 % stop function
- SFF = 99 % motor protection
- MTTFd = 289 years stop function
- MTTFd = 273 years motor protection
- PFHd = 6.27E-9 1/h stop function
Thermal overload class
Auxiliary contact composition
Control circuit voltage limits
Current consumption
Reset
- manual
- electrical reset
Maximum operating rate
- 120 cyc/mn AC-51 50 % ON
- 6 cyc/mn AC-53A 50 % ON
Tightening torque
Certifications
- CE
- ATEX as associated device for motor protection in zones 1 and 21
- cULus
[ui] rated insulation voltage
[uimp] rated impulse withstand voltage
Pollution degree
Protective treatment
Unit type of package 1
Number of units in package 1
Package 1 height
Package 1 width
Package 1 length
Package 1 weight
Unit type of package 2
Number of units in package 2
Package 2 height
Package 2 width
Package 2 length
Package 2 weight
Weee