Harmony Control Relays, Modular 1-phase voltage Control Relay, 5 A, 1 CO, 20…80 V AC/DC

Home ProductsIndustrialHarmonyModular 1-phase voltage Control Relay

Harmony Control Relays, Modular 1-phase voltage Control Relay, 5 A, 1 CO, 20…80 V AC/DC

Item Number: RM17UAS16

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Harmony Control Relays

Product or component type

voltage control relay

Warranty

18 months

Physical

Connections - terminals

screw connectors

[in] rated current

5 A

Insulation resistance

> 500 MOhm at 500 V DC conforming to IEC 60255-5|> 500 MOhm at 500 V DC conforming to IEC 60664-1

Local signalling

LED (green) for power ON|LED (yellow) for relay ON

Connections - terminals

screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end|screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end|screw terminals, 1 x 0.2...2 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end|screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end

Mounting support

35 mm symmetrical DIN rail conforming to IEC 60715

Electrical durability

100000 cycles

Mechanical durability

30000000 cycles

Control type

without test button

Width

17.5 mm

Net weight

0.08 kg

Ambient air temperature for operation

-20...50 °C

Standards

IEC 60255-6

Product certifications

CSA|GL|UL|GOST|C-Tick

Ambient air temperature for storage

-40...70 °C

Relative humidity

95 % at 55 °C conforming to IEC 60068...2-30

Ip degree of protection

IP20 (terminals) conforming to IEC 60529|IP30 (casing) conforming to IEC 60529

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Pro-active compliance (Product out of EU RoHS legal scope)

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

X

Environmental disclosure

ENVPEP1504008EN

Circularity profile

ENVEOLI1504008EN

California proposition 65

WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Others

Package 1 bare product quantity

1

Relay type

voltage control relay

Product specific application

for single-phase and DC supply

Relay name

RM17UAS

Relay monitored parameters

overvoltage or undervoltage detection

Time delay type

adjustable 0.1...10 s, 0 + 10 % Tt- time delay upon fault

Switching capacity in va

1250 VA

Measurement range

20...80 V AC/DC

Contacts type and composition

1 C/O

[uc] control circuit voltage

24...48 V

Reset time

1500 ms time delay

Maximum switching voltage

250 V AC/DC

Minimum switching current

10 mA at 5 V DC

Maximum switching current

5 A AC/DC

Supply voltage limits

15...100 V AC/DC

Power consumption in va

0...3.9 VA AC

Maximum power consumption in w

1.6 W DC

Control circuit frequency

50...60 Hz +/- 10 %

Immunity to microbreaks

20 ms

Output contacts

1 C/O

Nominal output current

5 A

Hysteresis

5...20 % of threshold setting

Measurement accuracy

+/- 10 % of the full scale value

Polarity

non reversible polarity on DC supply

Run-up delay at power-up

1000 ms DC|500 ms AC

Maximum measuring cycle

150 ms measurement cycle as true rms value

Repeat accuracy

+/- 0.5 % for input and measurement circuit|+/- 1 % for time delay

Measurement error

< 1 % over the whole range with voltage variation|0.2 %/°C with temperature variation

Quality labels

CE

Operating position

any position without derating

Overvoltage category

III conforming to IEC 60664-1

[ui] rated insulation voltage

250 V conforming to IEC 60664-1|400 V conforming to IEC 60664-1

Tightening torque

0.6...1 N.m conforming to IEC 60947...1

Housing material

self-extinguishing plastic

Utilisation category

AC-12 conforming to IEC 60947-5-1|AC-13 conforming to IEC 60947-5-1|AC-14 conforming to IEC 60947-5-1|AC-15 conforming to IEC 60947-5-1|DC-12 conforming to IEC 60947-5-1|DC-13 conforming to IEC 60947-5-1|DC-14 conforming to IEC 60947-5-1

Operating rate

<= 360 operations/hour full load

[us] rated supply voltage

, self-powered

Compatibility code

RM17

Electromagnetic compatibility

emission standard for industrial environments conforming to IEC 61000-6-4|emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3|immunity for industrial environments conforming to NF EN/IEC 61000-6-2

Vibration resistance

0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6|1 gn (f= 57.6-150 Hz) conforming to IEC 60255-21-1

Shock resistance

5 gn conforming to IEC 60068-2-27

Pollution degree

3 conforming to IEC 60664-1

Directives

73/23/EEC - low voltage directive|89/336/EEC - electromagnetic compatibility

Dielectric test voltage

2 kV, 1 min AC 50 Hz conforming to IEC 60255-5|2 kV, 1 min AC 50 Hz conforming to IEC 60664-1

Non-dissipating shock wave

4 kV conforming to IEC 60255-5|4 kV conforming to IEC 60664-1|4 kV conforming to IEC 61000-4-5

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

2.8 cm

Package 1 width

7.9 cm

Package 1 length

9.6 cm

Package 1 weight

88.0 g

Unit type of package 2

S02

Number of units in package 2

48

Package 2 height

15.0 cm

Package 2 width

30.0 cm

Package 2 length

40.0 cm

Package 2 weight

4.664 kg

Scip number

5e3fdf99-611b-4d07-ad17-6eba84ab488b

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Take-back

No

Product contributes to saved and avoided emissions

No

Removable battery

N/A

Carbon footprint (kg.eq.co2 per cr, total life cycle)

30.7174346245
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • Environmental Disclosure

  • End of Life Manual

  • Technical illustration

  • Application Notes

  • eTechPub

  • Certificates (MSDS)

  • Declaration of Conformity