Resimax Isolating Switch, 100A, 3 Pole, 500V

Resimax Isolating Switch, 100A, 3 Pole, 500V

Resimax Isolating Switch, 100A, 3 Pole, 500V

Item Number: SW3100

Retail
$294.65
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Sustainable offer status

Green Premium product

Product brand

Clipsal

Physical

Environmental Disclosure

ENVPEP121216EN

Mercury free

Yes

REACh free of SVHC

Yes

REACh Regulation

Free of Substances of Very High Concern above the threshold

China RoHS Regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

EU RoHS Directive

Compliant

RoHS exemption information

Yes

Toxic heavy metal free

Yes

Others

Package 1 Height

79 mm

Package 1 Length

92 mm

Package 1 Weight

254 g

Package 1 width

18 mm
Show all specifications

Frequently Asked Questions

hide show

Do you have a 3 pole 100A isolator in the WHB or 56 Series?

Only the WMS3100, however you could also use the SW3100 in the 56CB4 enclosure.

Do you have a replacement for MSW3100?

The replacement is SW3100

Please click on this link for more information
https://www.clipsal.com/Trade/Products/ProductDetail?catno=SW3100

User-added image

Where can I find information on the sw100, sw101, sw102 and sw103 dip switches on the ATV212 drives?

Issue:
ATV212 information from the SW101, SW102, and SW103 dip switches.

Product Line:
Altivar ATV212

Environment:
Altivar 212 drive

Cause:
Needs to know where they can find information on the dip switch settings.

Resolution:
There are 5 dip switches on the ATV212 drives
SW101= FM analog output U= voltage output I = current output
SW102= Sink Source switch
SW103= Term Switch. Selection of communication terminal resistor. When SW103 is set to Term, internal 120 Ohm termination resistor is connected between A and B terminals.
SW100= VIA= VIA analog input switch (U= voltage input or I= current input)
    VIB= VIB analog input switch (0-10-vdc input or PTC input)

  

    

 

What is the catalog number for the green 12-pin connector for Micrologic trip units on Powerpact P and R frame breakers?

Product Line:
Circuit Breakers

Environment:
Electrical Distribution Equipment

Resolution:
The trip unit connector is cat. no. S33100. It includes terminal identification markings.

Can a 5.0P or 5.0H trip unit be used for ground fault alarm without tripping?

Product Line:
Circuit Breakers

Environment:
Electrical Distribution Equipment.

Resolution:
Yes. To have ground-fault alarm without tripping, add a programmable contact module (M2C or M6C), and program the trip unit for alarm.
Neither the 5.0 nor 5.0A trip units can be used because those trip units do not have the required programming functionality.
If replacing a standard trip unit (not A, P or H), the 12-pin connector for the trip unit (kit S33101 for Masterpact, S33100 for Powerpact) must also be ordered.

How can a Powerpact P or R frame breaker with a 3.0 trip unit be modified to have ground-fault indication.

Product Line:
Circuit Breakers

Environment:
Electrical Distribution Equipment

Resolution:
Replace the trip unit with a 5.0P trip unit (S163A) and use a M2C (S64273) or M6C (S64204) programmable contact module. When replacing a standard trip unit (not A, P or H), the 12-pin connector for the trip unit (kit S33101 for Masterpact, S33100 for Powerpact) must also be ordered.

Set alarm up via trip unit Amperage Protection menu (trip curve button). Then set up S1 or S2 contact on 2PCM programmable contact module in MAINTENANCE menu (wrench button). Need neutral CT if it is a 4 wire system.


See instruction bulletins.
Powerpact P, R, and Masterpact NW, NT Micrologic™ 5.0P and 6.0P Trip Units, see 48049-137-05
M2C Programmable Contact Module Kits, see 48049-227-02
M6C Programmable Contact Module Kits, see 48049-337-02
Show More