Key Features & Specifications

hide show
Range of product
Altistart 01
Product or component type
soft starter
Product destination
asynchronous motors
Product specific application
simple machine
Device short name
ATS01
Network number of phases
1 phase
[Us] rated supply voltage
110...480 V - 10...10 %
Motor power kW
  • 3 kW, 3 phases at 400 V
  • 0.75 kW, 3 phases at 230 V
  • 1.1 kW, 3 phases at 230 V
  • 2.2 kW, 3 phases at 400 V
  • 0.75 kW, 1 phase at 230 V
    • Motor power hp
    • 1 hp, 3 phases at 230 V
    • 2 hp, 3 phases at 460 V
    • 3 hp, 3 phases at 460 V
    • 0.5 hp, 3 phases at 210 V
    • 1.5 hp, 3 phases at 230 V
      • IcL starter rating
        6 A
        Utilisation category
        AC-53B conforming to EN/IEC 60947-4-2
        Current consumption
        30 A at nominal load
        Type of start
        start with voltage ramp
        Power dissipation in W
      • 1 W at full load and at end of starting
      • 31 W in transient state
        • Assembly style
          with heat sink
          Function available
          integrated bypass
          Supply voltage limits
          99-528 V
          Supply frequency
          50...60 Hz - 5...5 %
          Network frequency
          47.5...63 Hz
          Output voltage
          <= power supply voltage
          [Uc] control circuit voltage
        • 110 V AC +/- 10 % at 30 mA
        • 24 V AC/DC +/- 10 % at 25 mA
        • 240 V AC +/- 10 % at 65 mA
          • Starting time
          • 1 s / 100
          • 5 s / 20
          • adjustable from 1 to 5 s
            • Starting torque
              30...80 % of starting torque of motor connected directly on the line supply
              Discrete output current
            • 2 A DC-13
            • 3 A AC-15
              • Tightening torque
                0.8-0.8 N.m
                Electrical connection
              • cage type connector - rigid 1 2.5 mm² AWG 14 control circuit
              • cage type connector - flexible with cable end 2 0.75 mm² AWG 18 power circuit
              • cage type connector - flexible without cable end 2 1 mm² AWG 17 control circuit
              • cage type connector - flexible without cable end 2 1 mm² AWG 17 power circuit
              • cage type connector - rigid 1 2.5 mm² AWG 14 power circuit
              • cage type connector - rigid 2 1 mm² AWG 17 control circuit
              • cage type connector - rigid 2 1 mm² AWG 17 power circuit
              • cage type connector - flexible with cable end 1 2.5 mm² AWG 14 control circuit
              • cage type connector - flexible with cable end 1 2.5 mm² AWG 14 power circuit
              • cage type connector - flexible without cable end 1 2.5 mm² AWG 14 control circuit
              • cage type connector - flexible without cable end 1 2.5 mm² AWG 14 power circuit
              • cage type connector - flexible with cable end 2 0.75 mm² AWG 18 control circuit
                • Marking
                  CE
                  Operating position
                  vertical +/- 10 degree
                  Height
                  100 mm
                  Width
                  23 mm
                  Depth
                  100 mm
                  Net weight
                  0.16 kg
                  Compatibility code
                  ATS01N1
                  Power range
                • 0.55-1 kW at 200-240 V 3 phases
                • 1.1-2 kW at 380-440 V 3 phases
                • 0.55-1 kW at 200-240 V 1 phase
                • 1.1-2 kW at 200-240 V 3 phases
                • 2.2-3 kW at 380-440 V 3 phases
                  • Motor starter type
                    soft starter
                    Electromagnetic compatibility
                  • conducted and radiated emissions level B conforming to CISPR 11
                  • immunity to electrical transients level 4 conforming to IEC 61000-4-4
                  • immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
                  • micro-cuts and voltage fluctuation conforming to IEC 61000-4-11
                  • voltage/current impulse level 3 conforming to IEC 61000-4-5
                  • conducted and radiated emissions level B conforming to IEC 60947-4-2
                  • damped oscillating waves level 3 conforming to IEC 61000-4-12
                  • electrostatic discharge level 3 conforming to IEC 61000-4-2
                  • EMC immunity conforming to EN 50082-1
                  • EMC immunity conforming to EN 50082-2
                  • harmonics conforming to IEC 1000-3-2
                  • harmonics conforming to IEC 1000-3-4
                  • immunity to conducted interference caused by radio-electrical fields level 3 conforming to IEC 61000-4-6
                    • Standards
                      EN/IEC 60947-4-2
                      Product certifications
                    • C-Tick
                    • CCC
                    • CSA
                    • B44.1-96/ASME A17.5 for starter wired to the motor delta terminal
                    • UL
                    • GOST
                      • IP degree of protection
                        IP20
                        Pollution degree
                        2 conforming to EN/IEC 60947-4-2
                        Vibration resistance
                      • 1 gn (f= 13-150 Hz) conforming to EN/IEC 60068-2-6
                      • 1.5 mm peak to peak (f= 3-13 Hz) conforming to EN/IEC 60068-2-6
                        • Shock resistance
                          15 gn for 11 ms conforming to EN/IEC 60068-2-27
                          Relative humidity
                          5-95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
                          Ambient air temperature for operation
                        • -10-40 °C (without)
                        • 40-50 °C (with current derating of 2 % per °C)
                          • Ambient air temperature for storage
                            -25-70 °C conforming to EN/IEC 60947-4-2
                            Operating altitude
                          • <= 1000 m without
                          • > 1000 m with current derating of 2.2 % per additional 100 m
                            • REACh Regulation
                              Reference contains Substances of Very High Concern above the threshold
                              REACh free of SVHC
                              Yes
                              EU RoHS Directive
                              Pro-active compliance (Product out of EU RoHS legal scope)
                              Toxic heavy metal free
                              Yes
                              Mercury free
                              Yes
                              RoHS exemption information
                              Yes
                              China RoHS Regulation
                              X
                              Circularity Profile
                              ENVEOLI100217EN
                              WEEE
                              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                              Warranty
                              18 months

                              Documents & downloads

                              hide show
                              Filter items
                              • All

                              • CAD Files and Packs

                              • Product Brochures

                              • Technical Data Catalogues

                              • End of Life Manual

                              • Installation Instruction

                              • Handout

                              • Product Environmental

                              • Data Bulletin

                              • Certificates (MSDS)

                              • eTechPub

                              Frequently Asked Questions

                              hide show

                              What are the adjustment ranges for the dials on an ATS01N1..FT?

                              For the START TIME dial, setpoint A is 1second and setpoint E is 5seconds.  There is a linear relationship from A to E setpoints.
                              For the INITIAL VOLTAGE dial, setpoint A is 30% and setpoint E is 80% of full voltage.  There is a linear relationship from A to E setpoints.



                              CTA-ID : 2061387

                              Does Schneider offer a soft start for a single phase motor?

                              Issue:
                              Soft start for a single phase motor?

                              Product Line:
                              ATS01

                              Environment:
                              All

                              Cause:
                              Needs a soft starter for a single phase motor. 

                              Resolution:
                              Yes, the ATS01N1**FT products are rated for single phase motors up to 2HP at 240V.

                              Does the ATS01 come with a shorting contactor?

                              Issue:
                              Does the ATS01 come with a shorting contactor?

                              Product Line:
                              Altistat 01

                              Environment:
                              All

                              Cause:
                              N/A

                              Resolution:
                              All of the ALTISTART 01 models, except the ATS01N103FT and ATS01N106FT, have an internal shorting contactor as standard.

                              Is the LH4N still available?

                              Issue:
                              Is the LH4N still available?

                              Product Line:
                              LH4N

                              Environment:
                              All models and all serial numbers

                              Cause:
                              Customer was looking for purchasing the LH4N112RT7.

                              Resolution:
                              No, the LH4N soft starter is obsolete. Please replace with the appropriate ATS01 or ATS22 soft starter. Consider application needs and features of currently-offered products.


                               

                              Are Softstarters acceptable for use in a Fire Pump applications?

                              Issue:
                              Are Softstarters acceptable for use in a Fire Pump applications?

                              Product line:
                              Altistart 22 48 ATS22 ATS48

                              Environment:
                              all

                              Cause:
                              Fire pump systems typically require the motors to run until they fail, without faulting the controller

                              Resolution: