Specifications

hide show
Circuit breaker application
distribution
Range
Acti 9
Range of product
Acti 9
Product name
Acti 9 iC60 RCBO
Product or component type
residual current breaker with overcurrent protection (RCBO)
Device short name
iC60N RCBO
Poles description
1P + N
[In] rated current
10 A at 50 °C
Earthing system
TN
Curve code
C
Earth-leakage sensitivity
30 mA
Breaking capacity
6000 A Icn at 240 V AC 50/60 Hz
Neutral position
left
Number of protected poles
1
Device location in system
outgoer
Network type
AC
Network frequency
50 Hz
[Ue] rated operational voltage
240 V AC 50/60 Hz
Trip unit technology
thermal-magnetic
Breaking capacity code
N
Residual current tripping technology
voltage dependent
Earth-leakage protection time delay
instantaneous
Earth-leakage protection class
type A
[Icw] rated short-time withstand current
Icw: 250 A during 8/20 µs impulse withstand
[Ics] rated service breaking capacity
6000 A at 240 V AC 50/60 Hz
Limitation class
3
[Ui] rated insulation voltage
400 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
4 kV
Surge current
250 A
Suitability for isolation
yes
Contact position indicator
yes
Control type
toggle
Local signalling
ON/OFF indication
Mounting mode
clip-on
Mounting support
DIN rail
Comb busbar and distribution block compatibility
NO
9 mm pitches
2
Height
110 mm
Width
18 mm
Depth
77.5 mm
Net weight
205 g
Mechanical durability
20000 cycles
Electrical durability
5000 cycles
Provision for padlocking
padlockable with padlock Ø 4 mm
Locking options description
ON/OFF locking facilities
Connections - terminals
  • screw clamp terminal (top) 1-25 mm² rigid without cable end
  • screw clamp terminal (top) 1-16 mm² flexible
  • screw clamp terminal (bottom) 1-16 mm² rigid without cable end
  • screw clamp terminal (bottom) 1-10 mm² flexible
    • Wire stripping length
    • power circuit: 13 mm for bottom connection
    • power circuit: 14 mm for top connection
      • Tightening torque
      • power circuit: 3.5-3.5 N.m top
      • power circuit: 2-2 N.m bottom
        • Earth-leakage protection
          integrated
          Standards
        • IEC 61009-2-2
        • AS/NZS 61009.1
        • IEC 61009-1
          • IP degree of protection
            IP20
            Tropicalisation
            2
            Relative humidity
            95-95 % at 55-55 °C
            Ambient air temperature for operation
            -15-60 °C
            Ambient air temperature for storage
            -40-85 °C
            Sustainable offer status
            Green Premium product
            REACh Regulation
            Free of Substances of Very High Concern above the threshold
            EU RoHS Directive
            Compliant
            Mercury free
            Yes
            RoHS exemption information
            Yes
            China RoHS Regulation
            Product out of China RoHS scope. Substance declaration for your information
            Environmental Disclosure
            ENVPEP121008EN
            Circularity Profile
            ENVEOLI121005EN

            Documents & downloads

            hide show
            Filter items
            • All

            • Product Brochures

            • CAD Files and Packs

            • Technical Data Catalogues

            • Installation Instruction

            • End of Life Manual

            • Product Environmental

            • Certificates (MSDS)

            • Declaration of Conformity

            Frequently Asked Questions

            hide show

            Does the A9D61816 RCBO have a neutral tail?

            Yes the A9D61816 and all that range have a neutral tail and also an Earth reference point.

            What is the replacement part for a 26896 RCB?

            The replacement part is a A9D61820.
            A9D11220 is best solution
            A9D11820 is an alternative 1 pole wide but no Neutral switching
            A9D61820 is an alternative 1 pole wide but no Neutral switching and only 6kA
             

            Does the A9D61816 RCBO have a neutral tail?

            Yes, the A9D61816 and all that range have a neutral tail and also an Earth reference point
            for more information see data sheet https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=a9d61816
            User-added image

            What is the part number for an A9D11810 but in "D" curve?

            need to build up with "D" curve circuit breaker A9F55110 and vigi unit A9V02663
            for more details see ....... https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9F55110
            and ............... https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9V02663
            User-added image    User-added image

            What is the alternative to the 4RCBE210/30?

            Within the Schneider Electric range, the alternative for the 4RCBE210/30 is A9D11210

            What is the part number for 2 pole 16amp RCBO 2 modules wide?

            The part name is A9D11216

            What is the plastic arm for LE1D18U7 stop button

            Part code LAD91810

            What is the part number for a 45amp chassis style RCD/MCB combo C/B?

            The part number for a 45amp chassis style RCD/MCB combo C/B is - 6kA - A9D61845 , 10kA - A9D11845
            For further information, visit the link below:-
            https://www.schneider-electric.com.au/en/search/A9D61845
            https://www.schneider-electric.com.au/en/search/A9D11845
            User-added image
            User-added image

            What is the difference between A9D32620 and A9D33620 RCBO Acti 9 devices?

             
             

            A9D33620 = SI (Super Immunised)
            A9D32620 = Type A (AC or pulsating DC)

            Type A RCBO = Tripping is ensured for residual sinusoidal alternating currents and residual pulsating direct currents, whether suddenly applied or slowly rising.
            Type Si RCBO = With all the features of a Type A device, “Si” type Super Immunised earth leakage protection range has been specially developed to be used with loads or in environments causing disturbances. Examples are lightning or switching surges, harmonics generated by increasing number of loads and constant load leakage current from electronic ballasts, speed drives, computers, etc. The Si increases safety and allows improved continuity of supply.
             

            ACDC1010 Hot Aisle Containment Rack Expansion Bundle Kit Installation (Manual)

            Issue:  ACDC1010 Hot Aisle Containment Rack Expansion Bundle Kit Installation (Manual)

             

            Product line: HACS

             

            Environment:  

             

             

            Cause:  Install, A Rack Expansion Bundle Kit is a complete set of racks, joining brackets, joining trim, hardware and ceiling panel required to extend an existing Hot Aisle Containment System.

              

             

            Resolution: 

             

            A Rack Expansion Bundle Kit is a complete set of racks, joining brackets, joining trim, hardware and ceiling panel required to extend an existing Hot Aisle Containment System.

             

             

            Ceiling panel assemblies come with Lexan® inserts that are not yet attached to the frames. Remove these and store them in a safe location until you begin the ceiling panel

            Installation process.

             

            Safety Instructions

             

            Potential electrical hazard exists when removing/installing side panels from a PDU, UPS, or XR Battery Cabinet. APC does not recommend performing any service to

            the PDU, UPS, or XR Battery Cabinet while it is energized. However, due to the critical nature of data center loads, this may occur. If you must perform this

            operation while the PDU, UPS, or XR Battery Cabinet is receiving input power, observe the following precautions to reduce the risk of electrical shock:

            1. Never work alone.

            2. Perform the work only if you are a certified electrician who is trained in the hazards of live electrical installation.

            3. Know the procedure for disconnecting electricity to the PDU, UPS, or XR Battery Cabinet, in case of an emergency.

            4. Wear appropriate personal protective equipment.

            5. Use double-insulated tools.

            6. Always follow local and site regulations when working on the PDU, UPS, or XR Battery Cabinet.

             

             

            Installation

             

            Each of the following procedures is required to correctly install your Rack Expansion Bundle Kit. Perform these procedures in this order.

             

            Side Panel Removal

             

            Remove the side panels at the end of the row of the Hot Aisle Containment System; each panel is connected by ground a strap that must be disconnected to completely remove each panel.

             

            Door and Door Frame Removal

             

            The door frame is heavy and requires at least two persons to safely remove and store it

             

            Remember to save all hardware that you remove so that it may be reused when you reinstall the door and door frame.

             

             

             

            5. Remove five M6×12 mm screws and M6 flange nuts on each doorframe upright to remove the door frame assembly from the equipment frames

             

            21U Side Panels

             

            Before attaching new racks to an existing system, install two 21 U side panels onto each NetShelter VS (900-mm) or NetShelter VX (1070-mm) enclosure. If grounding is required, there are two

            grounding studs on each 21U side panel.

             

             

            PSX/PDU side panel installation

             

            See the “Safety Instructions” on page 5 before installing any side panels on a PSX or PDU.

             

            IF you plan to install a Rack Expansion Bundle Kit next to a PDU or UPS, then a PSX/PDU side panel (ACDC1008, not included) must be installed on the PDU or UPS. A PSX/PDU side panel kit is

            available from APC. Attach the ground strap (previously removed from the side panel) to the new PSX/PDU side panel.

            Rear joining brackets for two 1070-mm enclosures

             

            When joining two NetShelter VX (1070-mm) enclosures:

             

            1. Remove the rear doors of the enclosures before you install the joining brackets.

             

             

            Rear joining brackets for two 1070-mm enclosures

             

            When joining two NetShelter VX (1070-mm) enclosures:

             

            1. Remove the rear doors of the enclosures before you install the joining brackets

             

            See the instructions included with your equipment to remove the rear doors.

             

            Do not remove the rear doors of the UPS, PDU, or XR Battery Cabinet

             

                  2. Use appropriate rear joining brackets. Orient the brackets so that the two round holes are at the top position, and the slots are located in the middle and lower positions. Use six M6 × 12-mm

            screws.

            Rear joining brackets and trim for 900-mm and 1070-mm enclosures

             

            When joining a NetShelter VS (900-mm) to a NetShelter VX (1070-mm) enclosure, use rear joining brackets and trim.

             

            Remove the rear doors of the enclosures before you install the joining brackets

             

            See the instructions included with your equipment to remove the rear doors

             

                             1. Attach two trim brackets to the side of the enclosure. Align each bracket’s mounting hole with the bottom hole of the top and bottom set of holes (as shown) in the enclosure.

                                 Use an M6 × 12-mm screw and a flange nut for each bracket. Use 1070-mm joining brackets for 1070-mm enclosures and 900-mm brackets for 900-mm enclosures.

             

             

            The use of the top or bottom hole depends on the placement of the enclosures.

            If the 900-mm and 1070-mm enclosures are switched (900-mm on the left and 1070-mm on the right), turn the 1070-mm joining bracket 180°, and attach it to the

            top hole of the 1070-mm enclosure. Turn the 900-mm joining bracket 180°, and attach it to the lower hole of the 900-mm enclosure. Finally, turn the the joining trim 180°

             

             

             

             

            Ceiling Panels

             

            Types of ceiling panels and required hardware

            The ceiling panels are configured in two different widths based on the size of the enclosures they span..

             

             

            Ceiling panels are not intended to support weight. Do not use ceiling panels to support power or data cables

             

            See the instructions that come with your equipment for proper installation of the ladders.

             

            Preparing for ceiling panel installation

             

            Install Plasti-Grommets into the tops of the equipment (two grommets per enclosure top).

             

             

            Ceiling panel installation

             

            1. Apply the ceiling panel gasket material to the edge of the ceiling panel that will face the door frame

             

             

            Ceiling panel inserts

             

            1. Remove the adhesive backing film from the panel frame; remove the protective plastic from both sides of the Lexan and carefully set the Lexan panel in place, pressing the edges firmly.

             

            2. Attach the next ceiling panel securely to the previously installed ceiling panel. Use five M6 × 30-mm screws, ceiling panel brackets, and threaded ceiling panel brackets to secure the

            panels at each connection point, as shown.

             

             

             

            Door Frame and Door Installation

             

            To attach the door frame to the end of the aisle:

            1. Attach the door frame assembly to the equipment frames. Use five M6 × 12-mm screws and M6 flange nuts on each upright.

             

             

             

            3. Attach the plinth blocks to the enclosures, using four M8 × 25-mm screws

             

             

            Side Panels

             

            Install the side panels at the ends of each row of the Hot Aisle Containment System.

             

            Grounding side panels

             

            Attach one end of a ground strap to the grounding stud on each panel, and then attach the other end of the grounding strap to a grounding stud on the enclosure.

            APC offers an optional grounding kit (AR8390) for grounding an enclosure. na1334a

            See also

            See the instructions included with your new equipment for information on installation, joining, side panel placement, and grounding stud locations

             

            APC offers an optional grounding kit (AR8390) for grounding an enclosure

             

            Data Troughs

             

            Troughs are supplied separately from the Rack Expansion Bundle Kit.

             

            Install the troughs into the slots located in the ceiling panel frames.

             

            See the instructions supplied with the troughs.