iACT24  Contactor auxiliary

Acti 9 Iact, 24V, Control and Auxiliary Contact, 1 NO With Ti24 PLC interface

Catalogue Number: A9C15924
iACT24  Contactor auxiliary
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
iCT
Range
Acti 9
Product or component type
control and indication auxiliary
Device short name
iACT24
Signal contacts composition
1 NO
Signalling circuit voltage
24 V DC: - 20...20 % 0.002...0.1 A
[Uc] control circuit voltage
  • 230 V AC 50/60 Hz maintained >= 200 ms
  • 24 V DC falling edge
  • 24 V DC rising edge
    • Control type
      remote control
      [Us] rated supply voltage
      230 V AC at 50/60 Hz
      Mounting mode
      fixed, on the left of CT
      Mounting support
      DIN rail
      Comb busbar and distribution block compatibility
    • bottom: YES
    • top: NO
      • 9 mm pitches
        2
        Height
        81 mm
        Width
        18 mm
        Depth
        68 mm
        Overvoltage category
        III
        [Uimp] rated impulse withstand voltage
        4 kV
        [Ui] rated insulation voltage
        440 V
        Immunity to microbreaks
        10 ms
        Undervoltage behaviour
        no opening if loss of 24 V DC
        Standards
        IEC 60947-1 annex S
        Quality labels
        CE
        Electrical durability
        250000 cycles conforming to IEC 60947-5-1
        Connections - terminals
      • control circuit: tunnel type terminals 2 cable(s) 2.5-2.5 mm² flexible
      • control circuit: tunnel type terminals 2 cable(s) 1.5-1.5 mm² rigid
      • auxiliary supply: tunnel type terminals 2 cable(s) 2.5-2.5 mm² flexible
      • auxiliary supply: tunnel type terminals 2 cable(s) 1.5-1.5 mm² rigid
      • control circuit: spring-loaded terminal Ti24 2 cable(s) 0.25-0.75 mm² flexible
      • control circuit: spring-loaded terminal Ti24 1 cable(s) 0.5-1.5 mm² flexible
        • Wire stripping length
        • control circuit: 10 mm for bottom connection
        • auxiliary supply: 10 mm for bottom connection
        • control circuit: 10 mm for top connection
          • Tightening torque
          • control circuit: 1-1 N.m bottom
          • auxiliary supply: 1-1 N.m bottom
            • Product compatibility
            • iCT 230/240 V 50 Hz
            • with PLC
            • iCT 220 V 50 Hz
            • Acti 9 Smartlink
            • iCT 220/240 V 50 Hz
              • Market segment
              • residential
              • small commercial
                • Compatibility code
                  iACT24
                  IP degree of protection
                • IP20 conforming to IEC 60529
                • IP40 (modular enclosure) conforming to IEC 60529
                  • Pollution degree
                    3 conforming to IEC 60439-1
                    Tropicalisation
                    2 conforming to IEC 60947-5-1
                    Relative humidity
                    93-93 % at 40-40 °C conforming to IEC 60068-2
                    Ambient air temperature for operation
                    -25-60 °C
                    Ambient air temperature for storage
                    -40-80 °C
                    Sustainable offer status
                    Green Premium product
                    EU RoHS Directive
                    Compliant
                    Mercury free
                    Yes
                    RoHS exemption information
                    Yes
                    China RoHS Regulation
                    Product out of China RoHS scope. Substance declaration for your information
                    Environmental Disclosure
                    ENVPEP120425EN
                    Circularity Profile
                    ENVEOLI120411EN
                    WEEE
                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                    Warranty
                    18 months

                    Documents & downloads

                    hide show
                    Filter items
                    • All

                    • CAD Files and Packs

                    • Product Brochures

                    • Technical Data Catalogues

                    • Installation Instruction

                    • End of Life Manual

                    • Product Environmental

                    • Operating Manuals

                    • Application Solutions

                    • Certificates (MSDS)

                    • Declaration of Conformity

                    Frequently Asked Questions

                    hide show

                    What is the Alternative for the Merlin Gerin 15913?

                    A9C15913

                    What is the dimensions of the load shedding device A9C15906 ?

                    Height = 77 mm  Width = 145 mm Depth = 60 mm

                    What is the replacement for Merlin Gerin 15322 ?

                    A9A15322

                    Are the A9N18359 and A9A26924 compatible?

                    The ref A9N18359 is C120 MCB (Multi9 design in the white material).

                    The ref A9A26924 is iOF auxiliary (Aciti9 design for iC60 MCB).

                    I can confirm that the parts A9N18359 and A9A26924 are not compliant with each other

                     

                    Wanted to know if A9N18524 can be used as 3 pole breaker instead of 4 pole?

                    Yes, customer can use the 3 pole and leave 4 pole open.

                    Getting error 5603 on LXM32 when I run a BMH motor

                    Issue:
                    Getting error 5603 on LXM32 when I try to run a BMH motor

                    Product Line:
                    Lexium 32
                    LXM32


                    Resolution:
                    Error 5603 is a commutation error. This is usually due to a bad encoder. The BMH motor has to be sent back for repair or replacement.

                    what is the maximum current for the R2 relay contacts on all sizes of ATS48 range of soft start

                    Goals and Symptoms

                    what is the maximum current for the R2 relay contacts on all sizes of ATS48 range of soft start

                    Facts and Changes

                    maximum current
                    R2 relay
                    soft start

                    Causes and Fixes


                    Characteristics of ATS48 relay :
                    max voltage : 400Vac (0.2A max)
                    thermal current : 5A
                    During life :
                    AC load
                    AC1 5A 250V 10E5 cycles (resistor)
                    AC15-14 : 0.5A (240Vac) 10E6 cycles (contactor)
                    Cos 0.5 1.8A (240Vac) 10E5 cycles (inductive)

                    DC load
                    DC13 : 0.5A (48Vdc) 10E6 cycles (contactor)
                    L/R 20mS 1.8A (30Vdc) 10E5 cycles (inductive)
                    minima commutation capacities :
                    6Vdc 10mA 10E7 cycles (PLC low level)

                    It's availble for all range.


                    Legacy KB System (APS) Data: RESL156323 V4.0, Originally authored by on , Last Edited by on
                    Related ranges: Altistart 48