SOCKET SWITCHED SINGLE DOUBLE POLE 20A 250V
socket swt sing dp 20a 250v
SOCKET SWITCHED SINGLE DOUBLE POLE 20A 250V
socket swt sing dp 20a 250v

Single Switch Socket Outlet, 2 Pole, 20A, 250V

Catalogue Number: 2015D20
SOCKET SWITCHED SINGLE DOUBLE POLE 20A 250V
socket swt sing dp 20a 250v
SOCKET SWITCHED SINGLE DOUBLE POLE 20A 250V
socket swt sing dp 20a 250v
Colour: White Electric
Colour: Per UOM Std.
  • White Electric 1 PCE
Added to cart

Specifications

hide show
Product brand
Clipsal
Range of product
Series 2000
Control type
ON/OFF button
Number of gangs
1 gang
Pin number
3
Number of power socket outlets
1
Actuator
  • switch
  • rocker
    • Mounting position
      horizontal
      Fixing mode
      by screws
      Local signalling
      without light indicator
      Material
      plastic
      Surface finish
      glossy
      [Ue] rated operational voltage
      250 V AC
      [In] rated current
      20 A
      Depth
      12 mm
      Length
      116 mm
      Width
      76 mm
      Fixing center
      84 mm
      Standards
    • AS/NZS 3100
    • AS/NZS 3112
    • AS/NZS 3133:approval number S/1
      • Sustainable offer status
        Green Premium product
        EU RoHS Directive
        Compliant
        Mercury free
        Yes
        RoHS exemption information
        Yes
        China RoHS Regulation
        Product out of China RoHS scope. Substance declaration for your information
        Environmental Disclosure
        ENVPEP120506EN

        Frequently Asked Questions

        hide show

        What is the cover for a C2015/20?

        The cover for a C2015/20 is a C2015/20C.

        Is part number C2015/20 available in Red?

        Yes it is and the part number is C2015/20-RD.

        Do Clipsal make a 3 pin, 20 amp, switched outlet with flat pins?

        Yes, 20A 3 flat pin switched outlets are available in a few variants , most commonly the 2015/20, C2015/20 and 56C320F.

        For further information please visit:
        https://www.clipsal.com/Trade/Products/ProductDetail?catno=2015/20
        https://www.clipsal.com/Trade/Products/ProductDetail?catno=C2015/20
        https://www.clipsal.com/Trade/Products/ProductDetail?catno=56C320F

         

        Is there a double pole 15A outlet?

        Yes, the part number is a 2015D15

        What is part number for Stainless Steel cover to suit C2015/20?

        The part number for Stainless Steel cover to suit is a C2015/20C.

        Are there double GPO's that are individually wired on each side?

        Yes, there are a few GPO's that are individually wired, they are C2016/2, 16/2MF, 2015/2V and 15/2V. In a weather proof option we have the WSC227/1/2

        What is the part no for a double powerpoint with a larger space in between to use with power packs?

        The part no is 2015H2. It is 2 x single horizontal switched sockets side by side with a single frame.

         

        Is there a Brushed Aluminium( BA) cover for the C2015D4?

        Brushed Aluminium( BA) covers for C2015D4 are not available. Arctic Silver (3A) is the closest colour match to Brushed Aluminium (BA). Eg C2015D4C-3A
        For more information on this range please visit the Clipsal web site on the link provided
        https://www.clipsal.com/Trade/search-results?q=c2015d4
         

        What is the ATS48 line voltage operating range?

        Issue:
        What is the ATS48 line voltage operating range?

        Product line:
        Altistart 48, ATS48

        Environment:
        all

        Cause:
        n/a

        Resolution:
        The Altistart 48 is suitable for three phase supply voltages that range from 208VAC to 690VAC , 50/60Hz.  The tolerance of the voltage supply is -15% to +10%. 

         

        Is there a padlock device for the 9001KR9R?

        Issue:
        What Padlock Device can be used on the 9001KR9R E-stop Pushbutton?

        Product Line:
        Harmony Pushbuttons

        Environment:
        All Products

        Resolution:
        9001K62, 9001K162
        NOTE: These attachments will not work when the operator is supplied with a 2 1/4 inch diameter mushroom.

        Who provides support for Class 9045 Type BG Magnetic Unloader products?

        Issue:
        Replacement for a defective magnetic unloader

        Product Line:
        Pressure, Float and Limit switches

        Environment:
        Pressure Switches

        Cause:
        Support for obsolete pressure switch  

        Resolution:
        The 9045 BG Magnetic unloaders were electrically activated relief valves used to relieve head pressure on compressors. These devices have been obsolete for several years with no replacement. Users should contact the compressor OEM for suggested replacement.

        What is EUSERC and what does it mean?

        Issue:
        Acronym meaning

        Product Line:
        Metering Equipment

        Resolution:

        EUSERC is an acronym for Electric Utility Service Equipment Requirements Committee. Formed in 1983, the purpose of the organization is to promote uniform electric service requirements among the member utilities, publish existing utility service requirements for electric service equipment and provide direction for development of future metering technology. There are approximately 80 utilities involved in EUSERC from 12 states. Not all EUSERC member utilities accept all metering devices that meet EUSERC specifications. So, although a device may meet EUSERC specifications, it may not be accepted for use by a specific utility company. Always check with the utility company for approval before using any metering device.


         

        Customer asked if the manual transfer switches are available with an interlocked receptacle option?

        No


        CTA-ID : 2015863

        What is the PDL version of the 2015XX?

        The PDL version of the 2015XX is a PDL694XXWH.

         

        Is there a white (WE) cover available for the C2015D4?

        YES -there is a white cover plate available for the C2015D4. The code is C2015D4-WE.

        Click here to see more information about the product at clipsal.com.
         

        What is the part number for a mounting block for C2015D4?

        The mounting block to suit a C2015D4 is C2015D4MB.
        PLease see link below for more information.

        https://www.clipsal.com/Trade/Products/ProductDetail?catno=C2015D4MB

        What is the part number for a Chrome Shadow cover for the C2015D4?

        The part number for a Chrome Shadow cover for the C2015D4 is - C2015D4C-3S

        For further information, visit the link below:-
        https://www.clipsal.com/Trade/search-results?q=C2015D4C-3S
        User-added image

        What is the part number for a mounting block to suit 2025H2?

        There is no mounting block available for the 2025H2

        What is the part number for a conduit bending spring

        266MD20 - for 20mm medium duty conduit.
        266MD25 - for 25mm medium duty conduit.

        What is part no for 15amp vertical single GPO

        PART NO 2015V15

        Can the LR9 solid state overload relay for F-Line contactors be used on single phase loads ?

        No, it will trip on a phase unbalance.


        CTA-ID : 2005929

        What are the torque requirements for a Multi-9 C120, Merlin Gerin breaker?

        C120 torque is 3.5 N-M.


        CTA-ID : 2055521

        In the 600 Series, is the 691/15 available in RED

        Not available, but Clipsal 2015/15 is available in red but it's horizontal.

        Is C2015D4, quad outlet , C2000 series, a double pole outlet?

        C2015D4 is double pole for extra safety (10A 250V a.c.). Ideal for caravan and marine applications.
        For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=C2015D4

        Is there a solid mounting block for the C2015D4?

        Not directly, It can be made up of 2 parts, use a C2015D4MB mounting block and a C2015D4P backing plate to suit.
        For more information on this range please visit the Clipsal website on the link provided.
        https://www.clipsal.com/Trade/Products/ProductDetail?catno=C2015D4P

        Will the XVBC11 tulip fit with XVBL beacons?

        Issue:
        Will the XVBC11 tulip fit with  XVBL beacons?

        Product Line:
        Harmony Tower Lights

        Environment:
        All Products

        Cause:
        Product Features

        Resolution:
        Yes, the XVBC11 tulip base will work with XVBL beacons when used with a support tube.


        CTA-ID : 2011190

        What is the maximum voltage rating of the Wiggy voltage tester.

        Issue:
        Application

        Product Line:
        Wiggy Voltage Tester

        Cause:
        Clarifying maximum voltage

        Resolution:
        600 volts AC, 250 volts DC maximum.


        CTA-ID : 2010590

        Can a 9013FS ``water switch`` be used on an air compressor load ?

        Yes ....as long as the switch meets the pressure range requirements . The switches designed for water pressure, as a group, will have a lower range of pressures. Note that a pressure relief valve, which is often desired for compressor loads , is not available with 9013FS products


        CTA-ID : 2023020

        What is the part number for a surround /cover for the 2025H2?

        The part number for a surround /cover for the 2025H2 is - 2000H2

         

        What is part number for cover to suit C2015D4 metal finish?

        The part number for cover to suit is a C2015D4C-3A.

        What is the altitude derating for a TeSys D-Line contactor?

        Issue:​
        What is the altitude derating for a TeSys D-Line contactor?

        Product Line:
        Digest 177 Section 18 : Contactors and Starters, IEC

        Environment:
        North American Products

        Resolution:
        The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

        Voltage
        3500m x 0.90
        4000m x 0.80
        4500m x 0.70
        5000m x 0.60

        Current
        3500m x 0.92
        4000m x 0.90
        4500m x 0.88
        5000m x 0.86

        For example, an LC1D80 at 5000 meters:
        - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
        - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



         

        Is there a wall box for a 2025H2?

        The wall box for the 2025H2 is the 2157H2.

        Some of the key features are:
        • 2 gang
        • 84 mm (2 sets)
        • With sliding nuts for accurate alignment of accessory
        • Precision stamped from 0.9 mm strip bright electrogalvanised, for 2000H2 series

        For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=2157H2

         

        Do you do anything larger than a C2015D4?

        Unfortunately that is the largest size available. If you need more outlets you would need to mount 2 side by side.

        Why will LA1SK11 adder deck not fit on CA2SK11 relay?

        Issue:
        Why will LA1SK11 adder deck not fit on CA2SK11 relay?

        Product Line:
        Tesys Relays

        Environment:
        All Products

        Cause:
        Product Features

        Resolution:
        No, LA1SK11 mounts only on the CA2SK20 relay.




        CTA-ID : 2014524

        What is the part number of a replacement button cap for an XB4BA21?

        Issue:
        What is the part number of a replacement button cap for an  XB4BA21?

        Product Line:
        Harmony Pushbuttons

        Environment:
        All Products

        Cause:
        Product selection

        Resolution:
        Use a ZBA2 black cap or otherwise the black cap from a universal ZBA9 kit


        CTA-ID : 2015097

        What is the part number for a diode for a CA3KN relay?

        Issue:
        What is  the part number for a diode for a CA3KN relay?

        Product Line:
        Tesys Relays

        Environment:
        All Products

        Cause:
        Product selection

        Resolution:
        LA4KC1B or LA4KC1E is the diode and zener diode for the CA3KN relay.


        CTA-ID : 2015604

        Do the DC operated 3 pole D-LINE Tesys contactors come with surge suppression as standard?

        Issue:
        Do the DC operated 3 pole D-LINE Tesys contactors come with surge suppression as standard?

        Product Line:
        D line contactors.

        Environment:
        Products sold in the United States.

        Cause:
        Product features.

        Resolution:
        The LC1D09 - D32 contactors with DC coils come with coil suppression as standard


        CTA-ID : 2049420

        What would be the part number for a C2015D4 brushed aluminium cover

        We do not do a Brushed Aluminium Cover for the C2015D4
        The closest we could do would be a C2015D4C-3A which is arctic silver.
        Also comes in a range of other colours.
        please see following link for entire colour range and further documentation.
        https://www.clipsal.com/Trade/Products/ProductDetail?catno=C2015D4

        Which version of C2015D4 is double pole?

        The C2015D4-WE is double pole switching.

        Does the ATV28 have Profibus communication capability?

        Issue:  Does the ATV28 have Profibus communication capability?
         
        Product Line:  ATV28
         
        Environment:  All
         
        Cause:  N/A
         
        Resolution:  No.


         

        What is the part code for a very old PDL Shaver Socket Conversion Plate

        The conversion plate is no longer available but you can use the below part numbers for the Clipsal version
        2000/3-WE + 2015-WE + 2727-WE + 2031RC30-WE

        Does the C2025D15 have separate feeds for each side ?

        No - 1 feed for both.

        For more information on this range please visit the Clipsal.com web site on the link provided
        https://www.clipsal.com/Trade/search-results?q=c2025d15

        Is there an enclosed mounting block for C2015D4, classic quad outlet?

        C2015D4P backing plate is available to provide additional safety on conducting surfaces. The backing plate can be used with C2015D4MB mounting block to suit C2015D4 outlets.
        Features:
        • Entries on all sides for total flexibility.
        • Mounting block enables surface wiring with either conduit or mini duct.
        • Four sturdy fixing points for easy mounting.
        • Plenty of wiring room for easy installation

         

        What are the dimensions for the C2015D4 quad outlet?

        The dimensions for the C2015D4 are 196mm (w) 75.5 (H) 23mm (D) 

        For further information on this product please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=C2015D4​

         

        What LED`s can be used in a 22mm direct supply light module like a ZB2BV6?

        Issue:
        What LED`s can be used in a 22mm direct supply light module like a ZB2BV6?

        Product Line:
        Harmony Pushbuttons

        Environment:
        All Products

        Cause:
        Product selection

        Resolution:
        Any BA9 bayonnet style LED. We offer the following:

        6 volt DL1CJUS0063 green 12 volt DL1CJUS0123 green
        6 volt DL1CJUS0064 red 12 volt DL1CJUS0124 red
        6 volt DL1CJUS0065 amber 12 volt DL1CJUS0125 amber

        24 volt DL1CJUS0243 green 120 volt DL1CJUS1203 green 24 volt DL1CJUS0244 red 120 volt DL1CJUS1204 red
        24 volt DL1CJUS0245 amber 120 volt DL1CJUS1205 amber




        CTA-ID : 2012660

        Can a factory-installed provision for a keylock be ordered with an NW breaker?

        Issue:
        Factory installation of key interlock provisions on NW Masterpact circuit breakers.

        Product Line:
        Circuit Breakers

        Environment:
        Products sold and used in the United States

        Cause:
        Factory installed key interlock on NW Masterpact circuit breakers

        Resolution:
        It is possible to order "provision-only" for an NW breaker key interlock. The provision is also available as a field-installable kit. See pricing guide for catalog numbers.

        CTA-ID : 2015133

        Why is the drive not responding to the 4-20mA feedback signal when the Pump Switching Card is installed?

        Most common issue is Parameter o19 must be set to the maximum pressure of the sensor in Bars.  Parameter o20 is set to the PI setpoint in Bars.

        To get the pressure in Bars, divide the pressure in PSI by 14.504.


        CTA-ID : 2015151

        What is the maximum ambient temperature that the ATV28 can operate at?

        Issue: What is the maximum ambient temperature that the ATV28 can operate at?  
         
        Product Line:   ATV28
         
        Environment:  All
         
        Cause:   N/A
         
        Resolution:   +14 to +104 F (-10 to +40 C) without grey tape removed
        +14 to +122F (-10 to +50C) with grey tape removed


         

        What are the altitude considerations for the ATV28 and any required sizing criteria?

        Issue:   What are the altitude considerations for the ATV28 and any required sizing criteria?
         
        Product Line:   ATV28
         
        Environment:  All
         
        Cause:   N/A
         
        Resolution:   Up to 3,300 ft (1,000 m) without derating;
        derate by 3% for each additional 3,300 ft (1,000 m)


         

        Where can people purchase Stab-Lok breakers?

        Issue:
        Are Federal Pioneer / Federal Pacific Stab-Lok breakers available? 

        Product Line:
        Moulded Case Breakers

        Environment:
        Stab-Lok

        Cause:
        FP Product Availability

        Resolution:
        Contact American Circuit Breaker Corporation (ACB) at 704-463-7361 as they are the exclusive distributor of the Stab-Lok breaker.