Adjustable range of switching point on falling pressure
0.3...10.3 bar
Adjustment range high setting
1.3...12 bar
Possible differential minimum at low setting
1 bar
Possible differential minimum at high setting
1.7 bar
Possible differential maximum at high setting
8.4 bar
Destruction pressure
30 bar
Type of decompression valve
straight valve instant connection
Terminal block type
6 terminals
Pressure actuator
diaphragm
Materials in contact with fluid
- canvas covered nitrile
- chromated zinc alloy
Enclosure material
PA impregnated with fibreglass
Operating position
any position
Maximum operating rate
10 cyc/mn
[Ui] rated insulation voltage
500 V conforming to EN/IEC 60947-1
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-1
Maximum resistance across terminals
- 25 MOhm conforming to IEC 60255-7 category 3
- 25 MOhm conforming to NF C 93-050 method A
Setting
knurled knob and nut
Terminals description ISO n°1
Vibration resistance
3 gn conforming to IEC 60068-2-6 (f = 10-500 Hz)
Shock resistance
50 gn conforming to IEC 60068-2-27
Electrical shock protection class
class I conforming to IEC 60536
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Unit Type of Package 2
S02
Number of Units in Package 2
8
Package 2 Weight
4.567 kg
Pressure sensor type
electromechanical pressure sensor
Pressure sensor size
12 bar
Fluid connection type
G 1/4 (female) conforming to ISO 228
Controlled fluid
- air (0-70 °C)
- fresh water (0-70 °C)
- sea water (0-70 °C)
Contacts type and composition
3 NC snap action
Product specific application
-
Pressure switch type of operation
regulation between 2 thresholds
Electrical connection
screw-clamp terminals, clamping capacity: minimum : 2 x 4 mm²
Electrical circuit type
power circuit
Scale type
adjustable differential