Quantcast

Control Station Emergency Stop Function

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Sustainable offer status

Green Premium product

Warranty

18 months

Range of product

Harmony XALK

Product or component type

complete control station

Product destination

for XB5 Ø 22 mm control and signalling units

Physical

Cable entry

  • 1 knock-out for cable entry 0-14 mm
  • 2 knock-outs for Pg 13 cable gland and ISO M20 0-12 mm

Net weight

0.194 kg

Mechanical durability

300000 cycles

Connections - terminals

  • screw clamp terminals, <= 2="" x="" 1.5="" mm²="" with="" cable="" end="" conforming="" to="" en/iec="">
  • screw clamp terminals, >= 1 x 0.22 mm² without cable end conforming to EN/IEC 60947-1

[Ie] rated operational current

  • 3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
  • 6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
  • 0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
  • 0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
  • 0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
  • 1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1

Electrical durability

  • 1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h,="" load="" factor:="" 0.5="" conforming="" to="" en/iec="" 60947-5-1="" appendix="">
  • 1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h,="" load="" factor:="" 0.5="" conforming="" to="" en/iec="" 60947-5-1="" appendix="">
  • 1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h,="" load="" factor:="" 0.5="" conforming="" to="" en/iec="" 60947-5-1="" appendix="">
  • 1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h,="" load="" factor:="" 0.5="" conforming="" to="" en/iec="" 60947-5-1="" appendix="">
  • 1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h,="" load="" factor:="" 0.5="" conforming="" to="" en/iec="" 60947-5-1="" appendix="">

Ambient air temperature for storage

-40...70 °C

Ambient air temperature for operation

-40...70 °C

IP degree of protection

  • IP66 conforming to IEC 60529
  • IP67
  • IP69
  • IP69K

IK degree of protection

IK03 conforming to EN 50102

Standards

  • EN/IEC 60204-1
  • EN/IEC 60947-1
  • EN/IEC 60947-5-4
  • EN/ISO 13850
  • JIS C 4520
  • IEC 60364-5-53
  • EN/IEC 60947-5-5
  • UL 508
  • CSA C22.2 No 14
  • EN/IEC 60947-5-1

REACh Regulation

Free of Substances of Very High Concern above the threshold

REACh free of SVHC

Yes

EU RoHS Directive

Pro-active compliance (Product out of EU RoHS legal scope)

Toxic heavy metal free

Yes

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

X

Environmental Disclosure

ENVPEP1806010EN

Circularity Profile

ENVEOLI1806010EN

Material

Contacts material

silver alloy (Ag/Ni)

Material

polycarbonate

Others

Resistance to high pressure washer

7000000 Pa at 55 °C, distance : 0.1 m

Positive opening

with conforming to EN/IEC 60947-5-1 appendix K

Operating travel

  • 1.5 mm (NC changing electrical state)
  • 2.6 mm (NO changing electrical state)
  • 4.3 mm (total travel)

Operating force

44 N NC + NO changing electrical state

Tightening torque

0.8...1.2 N.m conforming to EN/IEC 60947...1

Shape of screw head

  • cross compatible with Philips no 1 screwdriver
  • cross compatible with pozidriv No 1 screwdriver
  • slotted compatible with flat Ø 4 mm screwdriver
  • slotted compatible with flat Ø 5.5 mm screwdriver

Short-circuit protection

10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1

[Ith] conventional free air thermal current

10 A conforming to EN/IEC 60947-5-1

[Ui] rated insulation voltage

600 V (pollution degree 3) conforming to EN/IEC 60947-1

[Uimp] rated impulse withstand voltage

6 kV conforming to EN/IEC 60947-1

Electrical reliability

  • λ < 10exp(-6)="" at="" 5="" v,="" 1="" ma="" conforming="" to="" en/iec="">
  • λ < 10exp(-8)="" at="" 17="" v,="" 5="" ma="" conforming="" to="" en/iec="">

Compatibility code

XALK

Protective treatment

TH

Overvoltage category

class II conforming to IEC 60536

NEMA degree of protection

  • NEMA 13
  • NEMA 4X

Vibration resistance

5 gn (f= 12-500 Hz) conforming to IEC 60068-2-6

Shock resistance

  • 30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27
  • 50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

158.0 g

Package 1 Height

9.7 cm

Package 1 width

7 cm

Package 1 Length

7 cm

Unit Type of Package 2

P06

Number of Units in Package 2

320

Package 2 Weight

62.788 kg

Package 2 Height

75 cm

Package 2 width

60 cm

Package 2 Length

80 cm

Unit Type of Package 3

S03

Number of Units in Package 3

40

Package 3 Weight

6.786 kg

Package 3 Height

30 cm

Package 3 width

30 cm

Package 3 Length

40 cm

WEEE

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Device short name

XALK

Control station application

  • emergency switching off function
  • emergency stop function

Colour of base of enclosure

light grey (RAL 7035)

Colour of cover

yellow (RAL 1021)

Operator profile

1 mushroom head push-button

Operators description

red unmarked 1 NC

Reset

turn to release

Control station composition

1 mushroom head Ø 40 mm push-button, red 1 NC unmarked marking

Contact operation

slow-break
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Product Brochures

  • Technical Data Catalogues

  • Installation Instruction

  • End of Life Manual

  • Product Environmental

  • Certificates (MSDS)

  • Declaration of Conformity

  • eTechPub

Frequently Asked Questions

hide show

Are the XAL type push button enclosures waterproof?

Issue:
What is the enclosure or IP rating for the XAL series enclosures?

Product Line:
22mm Harmony Enclosures

Environment:

Resolution:
The XAL type pushbutton enclosures are rated at IP65
If using booted operators they are rated IP66.


The first digit - 6 indicates dust tight.

The second digit - 5 indicates protection against water jets.
The second digit - 6 indicates protection against heavy seas.