Quantcast

TeSys Vario, Switch Body for Switch Disconnector, 3 Poles, 32A

TeSys Vario, Switch Body for Switch Disconnector, 3 Poles, 32A

TeSys Vario, Switch Body for Switch Disconnector, 3 Poles, 32A

Item Number: V1

Product Dimensions

Width icon

Width55 mm

Height icon

Height74 mm

Depth icon

Depth60 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Sustainable offer status

Green Premium product

Warranty

18 months

Range

TeSys

Product or component type

switch body

Physical

Mounting support

  • symmetrical rail
  • plate

[Ue] rated operational voltage

690 V AC 50/60 Hz

[Ie] rated operational current

21.8 A AC-23 Ue: 400 V

Mechanical durability

100000 cycles

Electrical durability

  • 100000 cycles AC-21
  • 30000 cycles DC-1...5

Connections - terminals

  • power circuit: screw clamp terminals10-10 mm² - solid
  • power circuit: screw clamp terminals6-6 mm² - flexible - with cable end

Height

74 mm

Width

55 mm

Depth

60 mm

Net weight

0.2 kg

Standards

IEC 60947-3

Product certifications

  • UL
  • CSA
  • GL
  • UKCA

IP degree of protection

IP20 conforming to IEC 60529

Ambient air temperature for operation

-20...50 °C

REACh Regulation

Free of Substances of Very High Concern above the threshold

REACh free of SVHC

Yes

EU RoHS Directive

Compliant

Toxic heavy metal free

Yes

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental Disclosure

ENVPEP110227EN

Others

Compatibility code

V

Performance level

high performance

Poles description

3P

Contacts type and composition

3 NO

Network type

  • AC
  • DC

Network frequency

50/60 Hz

Rated operational power in W

  • 11 kW at 500 V (AC-23A)
  • 15 kW at 690 V (AC-23A)
  • 1.5 kW at 230...240 V (AC-3)
  • 7.5 kW at 500 V (AC-3)
  • 7.5 kW at 690 V (AC-3)
  • 5.5 kW at 230...240 V (AC-23A)
  • 11 kW at 400...415 V (AC-23A)
  • 7.5 kW at 400...415 V (AC-3)

[Ith] conventional free air thermal current

32 A

[Ithe] conventional enclosed thermal current

25 A

Making capacity

  • 320 A at 400 V AC-21A
  • 320 A at 400 V AC-22A
  • 320 A at 400 V AC-23A

Breaking capacity

  • 250 A at 400 V (AC-21A)
  • 250 A at 400 V (AC-22A)
  • 250 A at 400 V (AC-23A)

Rated conditional short-circuit current

  • 10 kA at 400 V - associated fuse 35 A aM
  • 10 kA at 400 V - associated fuse 35 A gG

[Icm] rated short-circuit making capacity

1 kA at 400 V at Ipeak

Intermittent duty class

30

Suitability for isolation

yes

[Uimp] rated impulse withstand voltage

8 kV

[Icw] rated short-time withstand current

384 A at 400 V duration: 1 s

Tightening torque

power circuit: 2.1...2.1 N.m - on screw clamp terminals

Protective treatment

TC

Mechanical robustness

  • vibrations 10...150 Hz (1 gn) conforming to IEC 60068-2-6
  • shocks 11 ms (30 Gn) conforming to IEC 60068-2-27

Fire resistance

960 °C conforming to IEC 60695-2-1

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

176.0 g

Package 1 Height

11.9 cm

Package 1 width

7.9 cm

Package 1 Length

8.5 cm

Unit Type of Package 2

P06

Number of Units in Package 2

192

Package 2 Weight

46.652 kg

Package 2 Height

77 cm

Package 2 width

80 cm

Package 2 Length

60 cm

Unit Type of Package 3

S03

Number of Units in Package 3

24

Package 3 Weight

4.712 kg

Package 3 Height

30 cm

Package 3 width

30 cm

Package 3 Length

40 cm

WEEE

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

PVC free

Yes

Halogen content performance

Halogen free product

Product name

TeSys VARIO

Device short name

V
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Product Brochures

  • Technical Data Catalogues

  • Installation Instruction

  • Product Environmental

  • Technical Drawing

  • Declaration of Conformity

Frequently Asked Questions

hide show

What does the parameter nCr on Altivar Drives work for?

Issue:
nCr parameter on Altivar Drives

Product Line:
Altivar 

Environment:
ATV312, ATV61, ATV71, ATV32, ATV12

Cause:
Programming

Resolution:
nCr is the Rated motor current.
Its adjustment range goes from 0.25 to 1.5 In (1) and factory setting According to drive rating and [Standard mot. freq] (bFr).
Rated motor current can be found on the motor's nameplate.

What will cause an error in Somove,when downloading a saved file to a VFD?

Issue:
Somove error while downloading a saved file to a VFD

Product Line:
ATV61, ATV71, ATV312, ATV212, ATV12, ATV31, ATV21, ATV32

Environment:
All models and serial numbers

Cause:
Possible issues with downloading Saved Projects to a new VFD.
The drive is of a different type
The drive versions and the file version are not compatible
The drive or drive version is not supported by the version of Somove
The project file is corrupt
There is not an active connection between Somove the VFD

Resolution:

1). Verify the VFD and the version is support by the version of Somove
2).  Check that the Project Product Version is the same as the Current Drive Product Version. 
3). Verify the comm port setting on the project is the same as the comm port setting being used on the current connection
4).  Verify connection to the VFD is possible without downloading a project.
       a).  Close current project
       b).  Under File Menu select Go To Start Page
       c).  Edit Connection and then select the connection type 
       d).  Go to Advanced setting, make the appropriate selection for the connection and press OK
       e).  Scan Network and wait for somove to scan for devices
       f).  Select the device to connection
       g).  Press connect and follow prompt on screen

Where can I find Altivar ATV12 and Altivar ATV32 firmware update instructions?

Issue:
ATV12 and ATV32 firmware update instructions.

Product Line:
Altivar ATV12 and ATV32

Environment:
All

Cause:
Needs to get the instructions on how to update the firmware on the ATV12 and ATV32 drives.

Resolution:
To update the ATV12 or the ATV32 firmware revision you will need a VW3A8121 Multiloader and a VW3A8122 cable.
and see the attached file for instructions.

Why is the ATV312 tripping on SCF or short circuit fault on power up?

Issue:
ATV312 tripping SCF 

Product line:
Altivar 312, ATV312, ATV31

Environment:
All models, all serial numbers 

Cause:
The drive trips on a SCF or a Short Circuit Fault if the drive detects a short circuit on the output of the drive.       

Resolution:
-Make sure all of the motor parameters are set in the DRC menu to match the motor name plate.  
-Check to make sure you don't have a long cable run of more than 100 feet. If you do, we recommend installing a output load reactor.
-Test the drive operation without the motor connected; turn off OPL (output phase loss) in the FLT menu. Try running the drive open circuit at 15, 30, 45, and 60Hz checking the output voltage phase to phase with a true RMS digital meter for balance at each frequency level.
Set Output Phase Loss attachment

-Check the motor and cables connecting to the drive for shorts phase to phase and phase to ground. 
-Check connections in the motor junction box for proper wiring.  
-Install a motor protecting output filter or load reactor at the output of the drive.
-Reduce the switching frequency (SFR in the SEt- menu). 
Set switching frequency attachment

If the SCF fault occurs with no motor or wiring connected to the drive, the drive will need to be replaced.

Refer to the attached ATV312 Programming manual BBV46385.

Note: Similar steps apply to the ATV12, ATV11, ATV32 and other Altivar Drive Products.

What is an InF3 fault on an Altivar 12 drive?

Issue:
Altivar 12 with InF3 fault.

Product Line:
ATV12

Environment:
All serial numbers for ATV12

Cause:
N/A

Resolution:
This is an internal issue with the drive. 
Power the drive down. 
Once the display is blank, power the drive back up. 
If the drive faults on InF3, a factory reset can be done by going to ConF menu and set FCS to InI (hold for 2 seconds). 
Power cycle the drive.
If this does not fix the issue, it is recommended that the drive be replaced.
Show More