Quantcast

Zelio Relay Solid State, DIN Rail Mount, Input 18-36VAC, Output 24-280VAC, 6A

Zelio Relay Solid State, DIN Rail Mount, Input 18-36VAC, Output 24-280VAC, 6A

Zelio Relay Solid State, DIN Rail Mount, Input 18-36VAC, Output 24-280VAC, 6A

Item Number: SSM1A16B7

Retail
N/A
RRP (Inc. GST)

Product Dimensions

Width icon

Width11 mm

Height icon

Height90.3 mm

Depth icon

Depth83.7 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Harmony Solid State Relays

Product or component type

solid state relay up to 10 A

Sustainable offer status

Green Premium product

Physical

Number of channels

1

Connections - terminals

screw connectors

Mounting support

symmetrical DIN rail

[In] rated current

6 A

Connections - terminals

  • screw terminals: 1 x 0.3...1 x 1.5 mm², (AWG 22...AWG 16) for input
  • screw terminals: 1 x 0.3...1 x 2.5 mm², (AWG 22...AWG 14) for output
    • Insulation resistance

      1000 MOhm at 500 V DC

      Local signalling

      LED (green) for input status

      Width

      11 mm

      Height

      90.3 mm

      Depth

      83.7 mm

      Net weight

      0.05 kg

      Device presentation

      complete product

      Standards

    • IEC 60950-1
    • IEC 61000
    • IEC 62314
      • Product certifications

      • CSA
      • UL
        • Marking

          CE

          IP degree of protection

          IP20

          Ambient air temperature for operation

          -30-80 °C

          Ambient air temperature for storage

          -30-100 °C

          REACh Regulation

          Free of Substances of Very High Concern above the threshold

          REACh free of SVHC

          Yes

          EU RoHS Directive

          Pro-active compliance (Product out of EU RoHS legal scope)

          Mercury free

          Yes

          RoHS exemption information

          Yes

          China RoHS Regulation

          X

          Environmental Disclosure

          ENVPEP1307069EN

          Circularity Profile

          ENVEOLI1307069EN

          California proposition 65

          WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

          Others

          Device short name

          SSM

          Network number of phases

          1 phase

          [Uc] control circuit voltage

          18...36 V

          Output switching mode

          zero voltage switching

          Output voltage

          24...280 V AC

          [Uc] control circuit voltage

          18...36 V AC

          Tightening torque

        • 0.5...0.8 N.m for input
        • 0.5...0.8 N.m for output
          • Capacitance unbalance

            10 pF for input/output

            Minimum switching voltage

            18 V AC turn-on

            Maximum switching voltage

            4 V AC turn-off

            Input current limits

            3.5-8.5 mA

            Solid state output type

          • zero voltage switching
          • SCR output
            • Load current

              0.15-6 A

              Absolute maximum voltage

              600 V

              Surge current

            • 285 A for 16.6 ms
            • 300 A for 20 ms
              • Maximum voltage drop

                <1.3 V on-state

                Motor power hp

                0.16 hp 40 °C 240 V AC

                Maximum I²t for fusing

              • 410 A².s for 10 ms at 50 Hz
              • 375 A².s for 8.33 ms at 60 Hz
                • Maximum leakage current

                  0.1 mA off-state

                  DV/dt

                  500 V/µs off-state at maximum voltage

                  Response time

                • 0.5 cycle (turn-on)
                • 30 ms (turn-off)
                  • Cos phi

                    0.5-0.5 (with maximum load)

                    Overvoltage category

                    III

                    Flame retardance

                    V0 conforming to UL 94

                    Dielectric strength

                  • 4 kV AC for input/output
                  • 4 kV AC for input or output to case
                    • Pollution degree

                      2

                      Unit Type of Package 1

                      PCE

                      Number of Units in Package 1

                      1

                      Package 1 Weight

                      74 g

                      Package 1 Height

                      2 cm

                      Package 1 width

                      9 cm

                      Package 1 Length

                      9 cm

                      Unit Type of Package 2

                      S02

                      Number of Units in Package 2

                      96

                      Package 2 Weight

                      7.218 kg

                      Package 2 Height

                      15 cm

                      Package 2 width

                      30 cm

                      Package 2 Length

                      40 cm
                      Show all specifications

                      Documents & downloads

                      hide show
                      Filter items
                      • All

                      • CAD Files and Packs

                      • Product Brochures

                      • Technical Data Catalogues

                      • Installation Instruction

                      • Product Environmental

                      • End of Life Manual

                      • Technical Drawing

                      • Certificates (MSDS)

                      • Declaration of Conformity

                      • eTechPub