Package 1 Bare Product Quantity
1
Relay type
voltage control relay
Product specific application
for 3-phase supply
Relay monitored parameters
overvoltage and undervoltage between phases
Time delay type
adjustable 0.3...30 s, 0 + 10 % on crossing the threshold
Switching capacity in VA
1250 VA
Minimum switching current
10 mA at 5 V DC
Maximum switching current
5 A AC/DC
Power consumption in VA
0...22 VA at 400 V AC 50 Hz
Measurement range
194...528 V voltage AC 50/60 Hz
Utilisation category
- AC-12 conforming to IEC 60947-5-1
- AC-13 conforming to IEC 60947-5-1
- AC-14 conforming to IEC 60947-5-1
- AC-15 conforming to IEC 60947-5-1
- DC-12 conforming to IEC 60947-5-1
- DC-13 conforming to IEC 60947-5-1
- DC-14 conforming to IEC 60947-5-1
Contacts type and composition
2 C/O
[Uc] control circuit voltage
220...480 V
Reset time
1500 ms time delay
Maximum switching voltage
250 V AC/DC
[Us] rated supply voltage
220...480 V AC 50/60 Hz +/- 10 %
Supply voltage limits
194...528 V AC
Voltage detection threshold
194 V
Control circuit frequency
50...60 Hz +/- 15 %
Output contacts
1 C/O + 1 C/O, 1 per threshold
Nominal output current
5 A
Maximum measuring cycle
150 ms measurement cycle as true rms value
Run-up delay at power-up
650 ms
Measurement accuracy
+/- 10 % of the full scale value
Repeat accuracy
- +/- 0.5 % for input and measurement circuit
- +/- 1 % for time delay
Measurement error
- < 1="" %="" over="" the="" whole="" range="" with="" voltage="">
- 0.05 %/°C with temperature variation
Response time
< 200="" ms="" (in="" the="" event="" of="" a="">
Overvoltage category
III conforming to IEC 60664-1
[Ui] rated insulation voltage
400 V conforming to IEC 60664-1
Operating position
any position without derating
Tightening torque
0.6...1 N.m conforming to IEC 60947...1
Housing material
self-extinguishing plastic
Operating rate
<= 360="" operations/hour="" full="">=>
Safety reliability data
- B10d = 300000
- MTTFd = 319.6 years
Functionality
overvoltage and undervoltage detection
Electromagnetic compatibility
- emission standard for industrial environments conforming to EN/IEC 61000-6-4
- emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
- immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Directives
- 73/23/EEC - low voltage directive
- 89/336/EEC - electromagnetic compatibility
Vibration resistance
- 0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6
- 1 gn (f= 57.6-150 Hz) conforming to IEC 60255-21-1
Shock resistance
5 gn conforming to IEC 60068-2-27
Pollution degree
3 conforming to IEC 60664-1
Dielectric test voltage
2 kV, 1 min AC 50 Hz
Non-dissipating shock wave
4 kV
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Unit Type of Package 2
S03
Number of Units in Package 2
48
Package 2 Weight
6.649 kg