Package 1 Bare Product Quantity
1
Relay type
multifunction voltage control relay
Relay monitored parameters
overvoltage or undervoltage detection
Time delay type
adjustable 0.3...30 s, 0 + 10 % on crossing the threshold
Switching capacity in VA
1250 VA
Minimum switching current
10 mA at 5 V DC
Maximum switching current
5 A AC/DC
Power consumption in VA
0...3.5 VA AC
Measurement range
15...600 V voltage
Utilisation category
- AC-12 conforming to IEC 60947-5-1
- AC-13 conforming to IEC 60947-5-1
- AC-14 conforming to IEC 60947-5-1
- AC-15 conforming to IEC 60947-5-1
- DC-12 conforming to IEC 60947-5-1
- DC-13 conforming to IEC 60947-5-1
- DC-14 conforming to IEC 60947-5-1
Contacts type and composition
2 C/O
[Uc] control circuit voltage
24...240 V
Reset time
1500 ms time delay
Maximum switching voltage
250 V AC/DC
[Us] rated supply voltage
24...240 V AC/DC 50/60 Hz +/- 10 %
Supply voltage limits
20.4...264 V AC/DC
Maximum power consumption in W
0.6 W DC
Immunity to microbreaks
10 ms
Control circuit frequency
40...70 Hz +/- 10 %
Resistance across terminals
- 150 mOhm at E1-M terminals
- 300 mOhm at E2-M terminals
- 600 mOhm at E3-M terminals
Nominal output current
5 A
Maximum measuring cycle
30 ms measurement cycle as true rms value
Hysteresis
5...50 % of threshold setting
Run-up delay at power-up
600 ms
Measurement accuracy
+/- 10 % of the full scale value
Repeat accuracy
- +/- 0.5 % for input and measurement circuit
- +/- 2 % for time delay
Measurement error
- +/- 0.05 %/°C with temperature variation
- < 1="" %="" over="" the="" whole="" range="" with="" voltage="">
Polarity
non reversible polarity on DC supply
Sensitivity scale
- 15...150 V E1-M terminals
- 30...300 V E2-M terminals
- 60...600 V E3-M terminals
Threshold setting
10...100 %
Overvoltage category
III conforming to IEC 60664-1
[Ui] rated insulation voltage
- 250 V conforming to IEC 60664-1
- 600 V conforming to IEC 60664-1
Control circuit voltage limits
- 15 % + 10 % Un
Operating position
any position without derating
Tightening torque
0.6...1 N.m conforming to IEC 60947...1
Housing material
self-extinguishing plastic
Operating rate
<= 360="" operations/hour="" full="">=>
Safety reliability data
- B10d = 290000
- MTTFd = 308.2 years
Electromagnetic compatibility
- emission standard for industrial environments conforming to EN/IEC 61000-6-4
- emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
- immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Directives
- 73/23/EEC - low voltage directive
- 89/336/EEC - electromagnetic compatibility
Vibration resistance
- 0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6
- 1 gn (f= 57.6-150 Hz) conforming to IEC 60255-21-1
Shock resistance
5 gn conforming to IEC 60068-2-27
Pollution degree
3 conforming to IEC 60664-1
Dielectric test voltage
- 2 kV, 1 min AC 50 Hz conforming to IEC 60255-5
- 2 kV, 1 min AC 50 Hz conforming to IEC 60664-1
Non-dissipating shock wave
- 4 kV conforming to IEC 60255-5
- 4 kV conforming to IEC 60664-1
- 4 kV conforming to IEC 61000-4-5
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Unit Type of Package 2
S03
Number of Units in Package 2
48
Package 2 Weight
7.271 kg
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins