Reset time
1500 ms time delay
Maximum switching voltage
250 V AC/DC
[Us] rated supply voltage
24...240 V AC/DC 50/60 Hz +/- 10 %
Supply voltage limits
20.4...264 V AC/DC
Control circuit voltage limits
- 15 % + 10 % Un
Maximum power consumption in W
0.6 W DC
Control circuit frequency
40...70 Hz +/- 10 %
Resistance across terminals
- 0.005 Ohm at E3-M terminals
- 0.015 Ohm at E2-M terminals
- 0.05 Ohm at E1-M terminals
Nominal output current
5 A
Maximum measuring cycle
30 ms measurement cycle as true rms value
Hysteresis
5...50 % of threshold setting
Run-up delay at power-up
0.3 s
Measurement accuracy
+/- 10 % of the full scale value
Repeat accuracy
- +/- 0.5 % for input and measurement circuit
- +/- 2 % for time delay
Measurement error
- 0.05 %/°C with temperature variation
- 1 by volt over the whole range with voltage variation
Threshold setting
10...100 %
Overvoltage category
III conforming to IEC 60664-1
[Ui] rated insulation voltage
250 V conforming to IEC 60664-1
Operating position
any position without derating
Tightening torque
0.6...1 N.m conforming to IEC 60947...1
Housing material
self-extinguishing plastic
Operating rate
<= 360="" operations/hour="" full="">=>
Safety reliability data
- MTTFd = 296.8 years
- B10d = 270000
Functionality
overcurrent or undercurrent in window mode
Immunity to microbreaks
50 ms
Electromagnetic compatibility
- emission standard for industrial environments conforming to EN/IEC 61000-6-4
- emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
- immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Vibration resistance
- 0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6
- 1 gn (f= 57.6-150 Hz) conforming to IEC 60255-21-1
Shock resistance
15 gn for 11 ms conforming to IEC 60255-21-1
Pollution degree
3 conforming to IEC 60664-1
Dielectric test voltage
- 2 kV, 1 min AC 50 Hz conforming to IEC 60255-5
- 2 kV, 1 min AC 50 Hz conforming to IEC 60664-1
Non-dissipating shock wave
- 4 kV conforming to IEC 60255-5
- 4 kV conforming to IEC 60664-1
- 4 kV conforming to IEC 61000-4-5
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
4.705 cm
Unit Type of Package 2
S03
Number of Units in Package 2
48
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Relay type
current control relay
Relay monitored parameters
overcurrent or undercurrent detection
Time delay type
- adjustable 1...20 s, 0 + 10 % on energisation Ti
- adjustable 0.3...30 s, 0 + 10 % on crossing the threshold Tt
Switching capacity in VA
1250 VA
Minimum switching current
10 mA at 5 V DC
Maximum switching current
5 A AC/DC
Maximum power consumption in VA
3.5 VA AC
Measurement range
- 0.15...1.5 A E1-M terminals
- 0.5...5 A E2-M terminals
- 1.5...15 A E3-M terminals
- 150 mA...15 A current
Utilisation category
- AC-12 conforming to IEC 60947-5-1
- AC-13 conforming to IEC 60947-5-1
- AC-14 conforming to IEC 60947-5-1
- AC-15 conforming to IEC 60947-5-1
- DC-12 conforming to IEC 60947-5-1
- DC-13 conforming to IEC 60947-5-1
- DC-14 conforming to IEC 60947-5-1
Contacts type and composition
2 C/O
[Uc] control circuit voltage
24...240 V