Package 1 Bare Product Quantity
1
Relay type
current control relay
Relay monitored parameters
overcurrent or undercurrent detection
Time delay type
- adjustable 1...20 s, 0 + 10 % on energisation Ti
- adjustable 0.3...30 s, 0 + 10 % on crossing the threshold Tt
Switching capacity in VA
1250 VA
Minimum switching current
10 mA at 5 V DC
Maximum switching current
5 A AC/DC
Maximum power consumption in VA
3.5 VA AC
Measurement range
- 0.15...1.5 A E1-M terminals
- 0.5...5 A E2-M terminals
- 1.5...15 A E3-M terminals
- 150 mA...15 A current
Utilisation category
- AC-12 conforming to IEC 60947-5-1
- AC-13 conforming to IEC 60947-5-1
- AC-14 conforming to IEC 60947-5-1
- AC-15 conforming to IEC 60947-5-1
- DC-12 conforming to IEC 60947-5-1
- DC-13 conforming to IEC 60947-5-1
- DC-14 conforming to IEC 60947-5-1
Contacts type and composition
2 C/O
[Uc] control circuit voltage
24...240 V
Reset time
1500 ms time delay
Maximum switching voltage
250 V AC/DC
[Us] rated supply voltage
24...240 V AC/DC 50/60 Hz +/- 10 %
Supply voltage limits
20.4...264 V AC/DC
Control circuit voltage limits
- 15 % + 10 % Un
Maximum power consumption in W
0.6 W DC
Control circuit frequency
40...70 Hz +/- 10 %
Resistance across terminals
- 0.005 Ohm at E3-M terminals
- 0.015 Ohm at E2-M terminals
- 0.05 Ohm at E1-M terminals
Nominal output current
5 A
Maximum measuring cycle
30 ms measurement cycle as true rms value
Hysteresis
5...50 % of threshold setting
Run-up delay at power-up
0.3 s
Measurement accuracy
+/- 10 % of the full scale value
Repeat accuracy
- +/- 0.5 % for input and measurement circuit
- +/- 2 % for time delay
Measurement error
- 0.05 %/°C with temperature variation
- 1 by volt over the whole range with voltage variation
Threshold setting
10...100 %
Overvoltage category
III conforming to IEC 60664-1
[Ui] rated insulation voltage
250 V conforming to IEC 60664-1
Operating position
any position without derating
Tightening torque
0.6...1 N.m conforming to IEC 60947...1
Housing material
self-extinguishing plastic
Operating rate
<= 360="" operations/hour="" full="">=>
Safety reliability data
- MTTFd = 296.8 years
- B10d = 270000
Functionality
overcurrent or undercurrent in window mode
Immunity to microbreaks
50 ms
Electromagnetic compatibility
- emission standard for industrial environments conforming to EN/IEC 61000-6-4
- emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
- immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Vibration resistance
- 0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6
- 1 gn (f= 57.6-150 Hz) conforming to IEC 60255-21-1
Shock resistance
15 gn for 11 ms conforming to IEC 60255-21-1
Pollution degree
3 conforming to IEC 60664-1
Dielectric test voltage
- 2 kV, 1 min AC 50 Hz conforming to IEC 60255-5
- 2 kV, 1 min AC 50 Hz conforming to IEC 60664-1
Non-dissipating shock wave
- 4 kV conforming to IEC 60255-5
- 4 kV conforming to IEC 60664-1
- 4 kV conforming to IEC 61000-4-5
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Unit Type of Package 2
S03
Number of Units in Package 2
48
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins