Package 1 Bare Product Quantity
1
Relay type
frequency control relays
Relay monitored parameters
overfrequency and underfrequency 50 or 60 Hz
Time delay type
adjustable 0.1...10 s, +/- 10 % on crossing the threshold
Switching capacity in VA
1250 VA
Minimum switching current
10 mA at 5 V DC
Maximum power consumption in VA
6 VA AC
Measurement range
40...70 Hz frequency
Utilisation category
- AC-12 conforming to IEC 60947-5-1
- AC-13 conforming to IEC 60947-5-1
- AC-14 conforming to IEC 60947-5-1
- AC-15 conforming to IEC 60947-5-1
- DC-12 conforming to IEC 60947-5-1
- DC-13 conforming to IEC 60947-5-1
- DC-14 conforming to IEC 60947-5-1
[Uc] control circuit voltage
120...277 V
Contacts type and composition
2 C/O
Reset time
2000 ms time delay
Maximum switching voltage
250 V AC/DC
[Us] rated supply voltage
120...277 V AC
[Us] rated supply voltage
120...277 V AC
Supply voltage limits
102...308 V AC
Control circuit frequency
40...70 Hz
Output contacts
1 C/O + 1 C/O
Nominal output current
5 A
Maximum measuring cycle
200 ms measurement cycle as true rms value
Run-up delay at power-up
0.5 s
Hysteresis
0.3...0.3 % fixed
Measurement accuracy
- +/- 10 % of the full scale value in input
- +/- 10 % of the full scale value in time delay
Repeat accuracy
- +/- 0.5 % for input and measurement circuit
- +/- 0.5 % for time delay
Measurement error
- +/- 0.05 %/°C with temperature variation
- < +/-="" 1="" %="" over="" the="" whole="" range="" with="" voltage="">
Overvoltage category
III conforming to IEC 60664-1
[Ui] rated insulation voltage
400 V conforming to IEC 60664-1
Control circuit voltage limits
- 15 % + 10 % Un
Supply frequency
50/60 Hz +/- 10 %
Insulation
no galvanic insulation between supply and measurement
Operating position
any position without derating
Tightening torque
0.6...1 N.m conforming to IEC 60947...1
Housing material
self-extinguishing plastic
Status LED
- 1 LED green for power ON
- 1 LED yellow for correct frequency (high R1)
- 1 LED yellow for correct frequency (low R2)
Operating rate
<= 360="" operations/hour="" full="">=>
Immunity to microbreaks
10 ms
Electromagnetic compatibility
- emission standard for industrial environments conforming to EN/IEC 61000-6-4
- emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
- immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Vibration resistance
- 0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
- 1 gn (f= 57.6-150 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
Shock resistance
15 gn for 11 ms conforming to IEC 60255-21-1
Pollution degree
3 conforming to IEC 60664-1
Dielectric test voltage
2 kV AC 50 Hz
Non-dissipating shock wave
4 kV
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
4.600 cm
Package 1 Length
9.700 cm
Package 1 Weight
126.000 g
Unit Type of Package 2
S03
Number of Units in Package 2
48
Package 2 Height
30.000 cm
Package 2 Width
30.000 cm
Package 2 Length
40.000 cm
Package 2 Weight
6.838 kg