Maximum switching voltage
250 V AC/DC
[Us] rated supply voltage
24...240 V AC/DC
[Us] rated supply voltage
24...240 V AC/DC
Supply voltage limits
- 20.4...264 V AC
- 21.6...264 V DC
Maximum power consumption in W
0.6 W DC
Resistance across terminals
- 600 kOhm at 3-phase
- 1.33 kOhm at temperature
Nominal output current
5 A
Run-up delay at power-up
0.2 s
Measurement accuracy
+/- 2 °C
Response time
- <= 3.5="" s="" +="" tt="" (in="" case="" of="" temperature="">=>
- 500 ms (in case of 3-phase fault)
- 500 ms (on disappearance of fault)
Temperature probe type
Pt 100 - 3-wire
Installed device
Pt 100 probe cable length <= 10="">=>
Overvoltage category
III conforming to IEC 60664-1
[Ui] rated insulation voltage
400 V conforming to IEC 60664-1
Control circuit voltage limits
- - 10 % + 10 % Un DC
- - 15 % + 10 % Un AC
Supply frequency
50/60 Hz +/- 10 %
Operating position
any position without derating
Tightening torque
0.6...1 N.m conforming to IEC 60947...1
Housing material
self-extinguishing plastic
Status LED
- 1 LED green for power ON
- 1 LED yellow for correct temperature (high R1)/(low R2)
- 1 LED yellow for phases of relay
Operating rate
<= 360="" operations/hour="" full="">=>
Immunity to microbreaks
10 ms
Electromagnetic compatibility
- emission standard for industrial environments conforming to EN/IEC 61000-6-4
- emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
- immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Vibration resistance
- 0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
- 1 gn (f= 57.6-150 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
Shock resistance
15 gn for 11 ms conforming to IEC 60255-21-1
Pollution degree
3 conforming to IEC 60664-1
Dielectric test voltage
2 kV, 1 min AC 50 Hz
Non-dissipating shock wave
4 kV
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Unit Type of Package 2
S03
Number of Units in Package 2
48
Package 2 Weight
7.097 kg
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Relay type
temperature control relays
Product specific application
for elevator machine rooms and 3-phase supplies
Relay monitored parameters
- phase sequence
- phase failure detection
- undertemperature: -1...11°C
- overtemperature: 34...46°C
Time delay range
0.1...10 s adjustable delay (tolerance: 0...10 % of the full scale value)
Switching capacity in VA
1250 VA
Minimum switching current
10 mA at 5 V DC
Maximum power consumption in VA
3.5 VA AC
Utilisation category
- AC-12 conforming to IEC 60947-5-1
- AC-13 conforming to IEC 60947-5-1
- AC-14 conforming to IEC 60947-5-1
- AC-15 conforming to IEC 60947-5-1
- DC-12 conforming to IEC 60947-5-1
- DC-13 conforming to IEC 60947-5-1
- DC-14 conforming to IEC 60947-5-1
[Uc] control circuit voltage
24...240 V
Contacts type and composition
2 NO