Reset time
1500 ms time delay
Maximum switching voltage
250 V AC/DC
[Us] rated supply voltage
12 V DC +/- 10 %
Supply voltage limits
7...20 V DC
Maximum power consumption in W
1 W DC
Immunity to microbreaks
20 ms at 12 V
Nominal output current
5 A
Hysteresis
5...20 % of threshold setting
Run-up delay at power-up
1000 ms DC
Measurement accuracy
+/- 10 % of the full scale value
Repeat accuracy
- +/- 0.5 % for input and measurement circuit
- +/- 1 % for time delay
Measurement error
- < 1="" %="" over="" the="" whole="" range="" with="" voltage="">
- 0.2 %/°C with temperature variation
Polarity
non reversible polarity on DC supply
Overvoltage category
III conforming to IEC 60664-1
[Ui] rated insulation voltage
- 250 V conforming to IEC 60664-1
- 400 V conforming to IEC 60664-1
Operating position
any position without derating
Tightening torque
0.6...1 N.m conforming to IEC 60947...1
Housing material
self-extinguishing plastic
Operating rate
<= 360="" operations/hour="" full="">=>
Electromagnetic compatibility
- emission standard for industrial environments conforming to EN/IEC 61000-6-4
- emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
- immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Directives
- 73/23/EEC - low voltage directive
- 89/336/EEC - electromagnetic compatibility
Vibration resistance
- 0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6
- 1 gn (f= 57.6-150 Hz) conforming to IEC 60255-21-1
Shock resistance
5 gn conforming to IEC 60068-2-27
Pollution degree
3 conforming to IEC 60664-1
Dielectric test voltage
- 2 kV, 1 min AC 50 Hz conforming to IEC 60255-5
- 2 kV, 1 min AC 50 Hz conforming to IEC 60664-1
Non-dissipating shock wave
- 4 kV conforming to IEC 60255-5
- 4 kV conforming to IEC 60664-1
- 4 kV conforming to IEC 61000-4-5
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Unit Type of Package 2
S02
Number of Units in Package 2
48
Package 2 Weight
4.487 kg
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Relay type
voltage control relay
Product specific application
for single-phase and DC supply
Relay monitored parameters
- overvoltage or undervoltage detection
- self-powered
Time delay type
adjustable 0.1...10 s, 0 + 10 % on crossing the threshold
Switching capacity in VA
1250 VA
Minimum switching current
10 mA at 5 V DC
Maximum switching current
5 A AC/DC
Measurement range
9...15 V voltage DC
Utilisation category
- AC-12 conforming to IEC 60947-5-1
- AC-13 conforming to IEC 60947-5-1
- AC-14 conforming to IEC 60947-5-1
- AC-15 conforming to IEC 60947-5-1
- DC-12 conforming to IEC 60947-5-1
- DC-13 conforming to IEC 60947-5-1
- DC-14 conforming to IEC 60947-5-1
Contacts type and composition
1 C/O
[Uc] control circuit voltage
110...240 V