Quantcast

Harmony Control Relays, Modular multifunction 3 phase supply control relay, 5A, 1CO, 183…528V AC

Harmony Control Relays, Modular multifunction 3 phase supply control relay, 5A, 1CO, 183…528V AC

Harmony Control Relays, Modular multifunction 3 phase supply control relay, 5A, 1CO, 183…528V AC

Item Number: RM17TE00

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Harmony Control Relays

Product or component type

3-phase control relay

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Connections - terminals

screw connectors

[In] rated current

5 A

Marking

CE

Insulation resistance

  • > 500 MOhm at 500 V DC conforming to IEC 60255-5
  • > 500 MOhm at 500 V DC conforming to IEC 60664-1

Connections - terminals

  • screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
  • screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
  • screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end
  • screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end

Local signalling

  • LED (green) for power ON
  • LED (yellow) for relay ON

Mounting support

35 mm symmetrical DIN rail conforming to EN/IEC 60715

Electrical durability

100000 cycles

Mechanical durability

30000000 cycles

Width

17.5 mm

Net weight

0.13 kg

Standards

EN/IEC 60255-1

Product certifications

  • GOST
  • C-Tick
  • CSA
  • UL
  • GL

Ambient air temperature for storage

-40...70 °C

Ambient air temperature for operation

-20...50 °C

Relative humidity

95 % at 55 °C conforming to IEC 60068...2-30

IP degree of protection

  • IP20 (terminals) conforming to IEC 60529
  • IP30 (casing) conforming to IEC 60529

REACh Regulation

Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive

Pro-active compliance (Product out of EU RoHS legal scope)

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

X

Environmental Disclosure

ENVPEP1504008EN

Circularity Profile

ENVEOLI1504008EN

California proposition 65

WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Others

Package 1 Bare Product Quantity

1

Relay type

multifunction control relay

Product specific application

for 3-phase supply

Relay name

RM17TE

Relay monitored parameters

  • undervoltage and overvoltage in window mode
  • asymmetry
  • phase sequence
  • phase failure detection

Time delay type

adjustable 0.1...10 s, +/- 10 % of the full scale value

Switching capacity in VA

1250 VA

Measurement range

208...480 V voltage AC

Contacts type and composition

1 C/O

[Uc] control circuit voltage

208...480 V

Reset time

1500 ms time delay

Maximum switching voltage

  • 250 V AC
  • 250 V DC

Minimum switching current

10 mA at 5 V DC

Maximum switching current

  • 5 A AC
  • 5 A DC

Supply voltage limits

183...528 V AC

Control circuit voltage limits

- 12 % + 10 % Un

Power consumption in VA

0...22 VA at 400 V AC 50 Hz

Control circuit frequency

50...60 Hz +/- 10 %

Output contacts

1 C/O

Nominal output current

5 A

Measurement voltage limits

183...528 V AC

Hysteresis

2 %

Run-up delay at power-up

650 ms

Maximum measuring cycle

150 ms measurement cycle as true rms value

Threshold adjustment voltage

  • -2...-17 % in the range 220 V AC
  • +2...+17 % in the range 480 V AC
  • -2...-12 % in the range 208 V AC
  • 2...20 % of Un selected

Voltage range

208...480 V phase to phase

Adjustment of asymmetry threshold

5...15 % of Un selected

Repeat accuracy

  • 0.5 % for input and measurement circuit
  • 3 % for time delay

Measurement error

  • < 0.05="" %/°c="" with="" temperature="">
  • < 1="" %="" over="" the="" whole="" range="" with="" voltage="">

Phase failure sensitivity

0.7 Un

Response time

< 200="" ms="" (in="" the="" event="" of="" a="">

Overvoltage category

III conforming to IEC 60664-1

[Ui] rated insulation voltage

400 V conforming to IEC 60664-1

Supply frequency

50/60 Hz +/- 10 %

Operating position

any position without derating

Tightening torque

0.6...1 N.m conforming to IEC 60947...1

Housing material

self-extinguishing plastic

Operating rate

<= 360="" operations/hour="" full="">

Utilisation category

  • AC-12 conforming to IEC 60947-5-1
  • AC-13 conforming to IEC 60947-5-1
  • AC-14 conforming to IEC 60947-5-1
  • AC-15 conforming to IEC 60947-5-1
  • DC-12 conforming to IEC 60947-5-1
  • DC-13 conforming to IEC 60947-5-1

Safety reliability data

  • MTTFd = 502.2 years
  • B10d = 470000

Functionality

undervoltage and overvoltage in window mode

Compatibility code

RM17

Electromagnetic compatibility

  • emission standard for industrial environments conforming to EN/IEC 61000-6-4
  • emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
  • immunity for industrial environments conforming to EN/IEC 61000-6-2

Directives

  • 89/336/EEC - electromagnetic compatibility
  • 73/23/EEC - low voltage directive

Vibration resistance

  • 0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6
  • 1 gn (f= 57.6-150 Hz) conforming to IEC 60255-21-1

Shock resistance

15 gn for 11 ms conforming to IEC 60255-21-1

Pollution degree

3 conforming to IEC 60664-1

Dielectric test voltage

  • 2 kV, 1 min AC 50 Hz conforming to IEC 60255-5
  • 2 kV, 1 min AC 50 Hz conforming to IEC 60664-1

Non-dissipating shock wave

  • 4 kV conforming to IEC 60255-5
  • 4 kV conforming to IEC 60664-1
  • 4 kV conforming to IEC 61000-4-5

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

2.7 cm

Package 1 Width

7.7 cm

Package 1 Length

9.6 cm

Package 1 Weight

92.0 g

Unit Type of Package 2

S02

Number of Units in Package 2

48

Package 2 Height

15.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

4.936 kg
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • Environmental Disclosure

  • End of Life Manual

  • Application Notes

  • Declaration of Conformity

  • Certificates (MSDS)

  • eTechPub

Frequently Asked Questions

hide show

Using the RM17TE00 on a High-leg Delta System

Issue:
Will the RM17TE00 phase loss relay work on a high-leg delta system?

Product Line:
Phase loss relays - GIC Product

Environment:
US Product

Cause:
Product Application

Resolution:
Yes, this relay can be used on this system.  The recommended configuration is to put the high-leg on L3 as shown in the attached document.

What type of DIN rail is the RM17TE00 mounted on?

Issue:
What type of DIN rail is the RM17TE00 mounted on?

Product Line:
Zelio Control Measurement Relays

Environment:
Control Measurement Relays

Resolution:
It mounts to 35mm DIN rail.

What type of fuse does RM17TE00 accept?

Issue:
Is the 100mA fast acting fuse the correct to be used with RM17TE00?

Product Line:
Relays and Timers

Environment:
Zelio Control

Cause:
Product Features

Resolution:
Correct fuse is a 1 A fast acting CC or gG fuse on the input.  There was an error in the instructions.

What is the overvoltage percentage for the zelio phase measurement relays part numbers RM17TU00 and RM17TE00

Issue: 
RM17TU00 and RM17TE00 Instruction sheet

Product Line:
Relays and Timers

Environment:
Zelio phase measurement relays

Resolution:
The overvoltage percentage is selectable from 2-20% of the supply voltage Un.
Refer to the attachment