Maximum switching voltage
250 V AC/DC
[Us] rated supply voltage
24...240 V AC/DC 50/60 Hz +/- 10 %
Supply voltage limits
20.4...264 V AC/DC
Control circuit voltage limits
- 15 % + 10 % Un
Maximum power consumption in W
1 W
Control circuit frequency
40...70 Hz sinusoidal
Nominal output current
5 A
Maximum measuring cycle
30 ms measurement cycle as true rms value
Hysteresis
15 % fixed of threshold setting
Run-up delay at power-up
0.5 s
Measurement accuracy
+/- 10 % of the full scale value
Repeat accuracy
+/- 0.5 % for input and measurement circuit
Measurement error
- +/- 0.05 %/°C with temperature variation
- < 1="" %="" over="" the="" whole="" range="" with="" voltage="">
Response time
< 200="" ms="" (in="" the="" event="" of="" a="">
Threshold setting
10...100 %
Input current
- 100000 mA permanent at 25 °C
- 300000 mA non repetitive < 3="" s="" at="" 25="">
Overvoltage category
III conforming to IEC 60664-1
[Ui] rated insulation voltage
400 V conforming to IEC 60664-1
Insulation
between supply and measurement
Operating position
any position without derating
Tightening torque
0.6...1 N.m conforming to IEC 60947...1
Housing material
self-extinguishing plastic
Operating rate
<= 360="" operations/hour="" full="">=>
Functionality
overcurrent detection
Immunity to microbreaks
10 ms
Electromagnetic compatibility
- emission standard for industrial environments conforming to EN/IEC 61000-6-4
- emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
- immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Vibration resistance
- 0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6
- 1 gn (f= 57.6-150 Hz) conforming to IEC 60255-21-1
Shock resistance
15 gn for 11 ms conforming to IEC 60255-21-1
Pollution degree
3 conforming to IEC 60664-1
Dielectric test voltage
2 kV AC 50 Hz
Non-dissipating shock wave
4 kV
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Unit Type of Package 2
S02
Number of Units in Package 2
32
Package 2 Weight
4.295 kg
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Relay type
current control relay
Relay monitored parameters
overcurrent detection
Switching capacity in VA
1250 VA
Minimum switching current
10 mA at 5 V DC
Maximum power consumption in VA
3 VA
Measurement range
2...20 A current
Utilisation category
- AC-12 conforming to IEC 60947-5-1
- AC-13 conforming to IEC 60947-5-1
- AC-14 conforming to IEC 60947-5-1
- AC-15 conforming to IEC 60947-5-1
- DC-12 conforming to IEC 60947-5-1
- DC-13 conforming to IEC 60947-5-1
- DC-14 conforming to IEC 60947-5-1
Contacts type and composition
1 C/O
[Uc] control circuit voltage
24...240 V