Contacts type and composition
1 C/O
[Us] rated supply voltage
- 24...240 V AC 50/60 Hz
- 24 V DC
Voltage range
0.85...1.1 Us
Supply frequency
50...60 Hz +/- 5 %
Tightening torque
0.6...1 N.m conforming to IEC 60947...1
Housing material
self-extinguishing
Repeat accuracy
+/- 0.5 % conforming to IEC 61812-1
Temperature drift
+/- 0.05 %/°C
Voltage drift
+/- 0.2 %/V
Setting accuracy of time delay
+/- 10 % of full scale at 25 °C conforming to IEC 61812-1
Impulse duration
- 100 ms with load in parallel typical
- 30 ms typical
Reset time
120 ms on de-energisation typical
Power consumption in VA
0...32 VA at 240 V AC
Maximum power consumption in W
0.6 W at 24 V DC
Minimum switching current
10 mA at 5 V DC
Maximum switching current
8 A AC/DC
Maximum switching voltage
250 V AC
Breaking capacity
2000 VA
Operating rate in Hz
10 Hz
Dielectric strength
2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1
[Uimp] rated impulse withstand voltage
5 kV during 1.2/50 µs
Maximum delay response
100 ms
Creepage distance
4 kV/3 conforming to IEC 60664-1
Safety reliability data
- B10d = 270000
- MTTFd = 296.8 years
Functionality
on-delay timing
Immunity to microbreaks
20 ms
Vibration resistance
20 m/s² (f= 10-150 Hz) conforming to IEC 60068-2-6
Shock resistance
15 gn for 11 ms conforming to IEC 60068-2-27
Electromagnetic compatibility
- electrostatic discharge immunity test: (in contact), level 3, 6 kV, conforming to IEC 61000-4-2
- electrostatic discharge immunity test: (in air), level 3, 8 kV, conforming to IEC 61000-4-2
- susceptibility to electromagnetic fields: (80 MHz to 1 GHz), level 3, 10 V/m, conforming to IEC 61000-4-3
- electrical fast transient/burst immunity test: (capacitive connecting clip), level 3, 1 kV, conforming to IEC 61000-4-4
- electrical fast transient/burst immunity test: (direct), level 3, 2 kV, conforming to IEC 61000-4-4
- 1.2/50 µs shock waves immunity test: (differential mode), level 3, 1 kV, conforming to IEC 61000-4-5
- 1.2/50 µs shock waves immunity test: (common mode), level 3, 2 kV, conforming to IEC 61000-4-5
- conducted RF disturbances: (0.15...80 MHz), level 3, 10 V, conforming to IEC 61000-4-6
- voltage dips and interruptions immunity test: (1 cycle), 0 %, conforming to IEC 61000-4-11
- voltage dips and interruptions immunity test: (25/30 cycles), 70 %, conforming to IEC 61000-4-11
- conducted and radiated emissions: , class B, conforming to EN 55022
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Unit Type of Package 2
S02
Number of Units in Package 2
40
Package 2 Weight
3.665 kg
Unit Type of Package 3
P06
Number of Units in Package 3
640
Package 3 Weight
65.06 kg
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Discrete output type
relay
Time delay type
power on-delay
Time delay range
- 1...10 min
- 10...100 h
- 0.1...1 s
- 6...60 s
- 6...60 min
- 1...10 s
- 1...10 h
Nominal output current
8 A
[Uc] control circuit voltage