Specifications

hide show
Range
Resi MAX
Product or component type
residual current breaker with overcurrent protection (RCBO)
Product brand
Clipsal
Device application
distribution
Poles description
1P + N
Neutral position
left
Number of modules
2
Number of protected poles
1
[In] rated current
10 A
Network type
AC
Trip unit technology
thermal-magnetic
Curve code
C
Earth-leakage sensitivity
30 mA
Earth-leakage protection class
type AC
Breaking capacity
6000 A
[Ue] rated operational voltage
250 V AC
[Uimp] rated impulse withstand voltage
4 kV
Local signalling
ON/OFF indication
Mounting mode
clip-on
Mounting support
DIN rail
Size
81 x 36 x 77.5 mm conforming to DIN 43880
Standards
AS/NZS 61009
IP degree of protection
  • IP20 conforming to IEC 60529
  • IP40 (modular enclosure) conforming to IEC 60529
    • Ambient air temperature for operation
      -5-40 °C
      Package 1 Weight
      219 g
      Package 1 Height
      40 mm
      Package 1 width
      80 mm
      Package 1 Length
      100 mm
      Sustainable offer status
      Green Premium product
      EU RoHS Directive
      Compliant
      Mercury free
      Yes
      RoHS exemption information
      Yes
      China RoHS Regulation
      Product out of China RoHS scope. Substance declaration for your information
      Environmental Disclosure
      ENVPEP120401EN

      Documents & downloads

      hide show
      Filter items
      • All

      • Product Brochures

      • Installation Instruction

      • Product Environmental

      • Certificates (MSDS)

      • Corporate Marketing

      Frequently Asked Questions

      hide show

      What is part number for Resimax Busbar to suit RCBM216/30?

      RCBM216/30 can be used with RMXPH105,RMXPH112 or RMXPH124.

      Is the RCBM210/30 an RCD only ,or is it a combination RCD/MCB?

      The RCBM210/30 is a combination RCD/MCB.

      For further information , visit link below:-
      https://www.clipsal.com/Trade/search-results?q=RCBM210/30
      User-added image

      Do you have a 10A RCBO double pole and 1 module wide?

      Yes, we do have a 10A RCBO double pole that is 1 module wide. The part number is RCBE210/30S.

      Are the RCBM series of RCBOs double pole isolating?

      Yes they are.

      Does 4RCBM220/30 switch both active and neutral?

       4RCBM220/30 will switch both active and neutral.
      For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?CatNo=4RCBM220/30

      Replacement for the 4RCBE110/10

      This part has been replaced with 4RCBE210/30S

      Is the RCBM216/30 fed from the top or the bottom?

      The RCBM216/30 line and load terminals may be connected to either the top or bottom for ease of installation.

      Some of the key features are:
      • Separate RCD trip flag for easy fault finding
      • New insulated openings for easy busbar installation
      • No need to cut the busbar providing safe and quick fit off
      • Top and bottom line load compatible for easy installation

      For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=RCBM216/30

      What does the yellow warning label adjacent the bottom neutral terminal indicate on a RCBE220/30S?

      Please refer to the attached literature for details.

      What is the alternative to the 4RCBE210/30?

      Within the Schneider Electric range, the alternative for the 4RCBE210/30 is A9D11210

      What is the replacement for a 4RCBE110/30?

      The replacement for a 4RCBE110/30 is a A9D61810.
      Some of the key features are:
      • 2 Pole wide
      • 30mA
      • 10A
      • RCBO
      For further informatio please visit www.clipsal.com/Trade/Products/ProductDetail?catno=A9D61810

      What are the conections of the RCD240/30?

      The connection of the RCD240/30 is line at the top and load at the bottom.

      For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=RCD240/30

       

      What are the dimensions of the RCBM216/30?

      The dimensions of the RCBM216/30 are 44mm(D) X 81mm(H) X 36mm(W).
      Some of the key feaures are:
      • Seperate RCD trip flag for easy fault finding
      • New insulated openings for easy busbar installation
      • No need to cut the busbar providing safe and quick fit off
      • Top and bottom line load compatible for easy installation
      • Operating temperature: -5 to 40 deg C/li>
      • Mechanical combination Standard-type
      • 4 kV Rated impulse withstand voltage
      For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=RCBM216/30
       
      Show More