Quantcast

ClimaSys, ClimaSys forced vent. IP54, 850m3/h, 230V, with outlet grille and filter G2

ClimaSys, ClimaSys forced vent. IP54, 850m3/h, 230V, with outlet grille and filter G2

ClimaSys, ClimaSys forced vent. IP54, 850m3/h, 230V, with outlet grille and filter G2

Item Number: NSYCVF850M230PF

Datasheet

Product Dimensions

Width icon

Width316 mm external:

Height icon

Height336 mm external:

Depth icon

Depth162 mm external:

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

ClimaSys

Product or component type

fan

Colour

outlet grille: grey (RAL 7035)

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[In] rated current

  • 0.65...0.65 A 50 Hz
  • 0.85...0.85 A 60 Hz

Height

336 mm external:

Width

316 mm external:

Depth

162 mm external:

Net weight

4.1 kg

Ambient air temperature for operation

-15...60 °C

Ambient air temperature for storage

-40...70 °C

Connections - terminals

terminal block

IP degree of protection

IP54

REACh Regulation

Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive

Compliant

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure

ENVPEP110717EN

Circularity Profile

ENVEOLI1107017EN

Material

Material

outlet grille: injected thermoplastic (ASA PC)

Device composition

  • 1 axial motor
  • 2 protective grille: on the front and rear surfaces
  • 1 filter: front of axial motor
  • 1 outlet grille: front
  • 1 cut-out template

Others

Package 1 Bare Product Quantity

1

Lead time

Usually Ships within 4 Weeks

Product name

ClimaSys CV

Type of ventilation filter

standard

Air flow

  • free flow rate with standard filter: 838 m3/h at 50 Hz
  • free flow rate with standard filter: 803 m3/h at 60 Hz

[Us] rated supply voltage

207...244 V

Input voltage

230 V 50/60 Hz

Power range

  • 150 W 50 Hz
  • 195 W 60 Hz

Noise level

75...76 dB

Bearing type

ball

Cut-out dimensions

291 x 291 mm

Maximum pressure

170 Pa flow rate 0 m³/h

Condition of use

  • outside temperature must be 5 °C lower than inside temperature
  • flow rates depends on the work point, see ProClima software
  • overfrequent filter replacement should be avoided
  • filter must be cleaned and replaced regularly
  • surrounding environment must be relatively clean

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

23.0 cm

Package 1 Width

32.0 cm

Package 1 Length

34.0 cm

Package 1 Weight

4.386 kg

Unit Type of Package 2

P12

Number of Units in Package 2

24

Package 2 Height

110.0 cm

Package 2 Width

80.0 cm

Package 2 Length

120.0 cm

Package 2 Weight

134.0 kg
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Product Brochures

  • Technical Data Catalogues

  • Installation Instruction

  • End of Life Manual

  • Environmental Disclosure

  • Operating Manuals

  • Declaration of Conformity

  • Certificates (MSDS)