Quantcast

Clipsal MAX9 Arc Fault Detection (AFDD+RCBO) 1P+N, 16A, 30mA, C Curve, 6000A, A Type, All-in-one

Clipsal MAX9 Arc Fault Detection (AFDD+RCBO) 1P+N, 16A, 30mA, C Curve, 6000A, A Type, All-in-one

Clipsal MAX9 Arc Fault Detection (AFDD+RCBO) 1P+N, 16A, 30mA, C Curve, 6000A, A Type, All-in-one

Item Number: MX9A3216
Retail
$416
RRP (Inc. GST)

Product Dimensions

Width icon

Width36 mm

Height icon

Height91 mm

Depth icon

Depth75 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-
max9 AFDD
max9 AFDD
max9 AFDD

Specifications

Design

Sustainable offer status

Green Premium product

Range

MAX9

Product or component type

arc fault detection RCBO

Physical

[Ue] rated operational voltage

240 V AC 50 Hz conforming to AS/NZS 61009.1

Control type

toggle

Local signalling

ON, OFF, fault trip

Mounting mode

clip-on

Mounting support

DIN rail

Mechanical durability

20000 cycles

Electrical durability

10000 cycles AC 50 Hz conforming to IEC 61009

Connections - terminals

  • tunnel type terminal top or bottom 1-10 mm² flexible
  • tunnel type terminal top or bottom 1-16 mm² rigid
    • Wire stripping length

      14 mm for top or bottom connection

      Height

      91 mm

      Width

      36 mm

      Depth

      75 mm

      Net weight

      237 g

      IP degree of protection

      IP20

      Relative humidity

      95-95 % at 55-55 °C

      Ambient air temperature for operation

      -25-70 °C

      Ambient air temperature for storage

      -40-85 °C

      REACh Regulation

      Free of Substances of Very High Concern above the threshold

      EU RoHS Directive

      Compliant

      Mercury free

      Yes

      RoHS exemption information

      Yes

      China RoHS Regulation

      Product out of China RoHS scope. Substance declaration for your information

      Environmental Disclosure

      ENVPEP1906001EN

      Circularity Profile

      ENVEOLI1906001EN

      Standards

    • EN/IEC 62606
    • AS/NZS 61009.1
      • [In] rated current

        16 A at 30 °C

        Others

        Network frequency

        50 Hz

        Device location in system

        outgoer

        Magnetic tripping limit

        5...10 x In

        [Ics] rated service breaking capacity

        6000 A at 240 V AC 50 Hz conforming to AS/NZS 61009.1

        Rated breaking and making capacity

        500 A

        Limitation class

        3

        [Ui] rated insulation voltage

        440 V AC 50 Hz

        Threshold tripping voltage

        275 V

        [Uimp] rated impulse withstand voltage

        4 kV conforming to AS/NZS 61009.1

        Contact position indicator

        yes

        Overvoltage category

        III

        Locking options description

        by padlocks

        Tightening torque

        2-2 N.m top or bottom

        Comb busbar and distribution block compatibility

        top comb busbar: YES

        Connection pitch

        9 mm pitches

        4

        Targeted country

        Australia

        Temperature derating table

      • -25 °C ( 19.6 A )
      • -20 °C ( 19.3 A )
      • -15 °C ( 19 A )
      • -10 °C ( 18.7 A )
      • -5 °C ( 18.4 A )
      • 0 °C ( 18.1 A )
      • 5 °C ( 17.7 A )
      • 10 °C ( 17.4 A )
      • 15 °C ( 17.1 A )
      • 20 °C ( 16.7 A )
      • 25 °C ( 16.4 A )
      • 30 °C ( 16 A )
      • 35 °C ( 15.6 A )
      • 40 °C ( 15.3 A )
      • 45 °C ( 14.9 A )
      • 50 °C ( 14.5 A )
      • 55 °C ( 14.1 A )
      • 60 °C ( 13.6 A )
      • 65 °C ( 13.2 A )
      • 70 °C ( 12.7 A )
        • Grid distance

          35 mm

          Heat dissipation

          3.5-3.5 W at 240 V - 16 A

          Pollution degree

          2

          Tropicalisation

          severity B conforming to IEC 60068-2-30 for 28 d

          Operating altitude

          0...2000 m

          Quality labels

          RCM

          Unit Type of Package 1

          PCE

          Number of Units in Package 1

          1

          Package 1 Weight

          234 g

          Package 1 Height

          8.4 cm

          Package 1 width

          4.4 cm

          Package 1 Length

          10.4 cm

          Unit Type of Package 2

          CAR

          Number of Units in Package 2

          40

          Package 2 Weight

          9.86 kg

          Package 2 Height

          20 cm

          Package 2 width

          30 cm

          Package 2 Length

          40 cm

          Circuit breaker application

          distribution

          Product specific application

          fire prevention by arc detection

          Poles description

          1P + N

          Number of protected poles

          1

          Curve code

          C

          Breaking capacity

          6000 A Icn at 240 V AC 50 Hz conforming to AS/NZS 61009.1

          Earthing system

        • TN-S
        • TT
        • IT
          • Earth-leakage sensitivity

            30 mA

            Network type

            AC

            Earth-leakage protection time delay

            instantaneous

            Earth-leakage protection class

            type A

            Neutral position

            left

            Suitability for isolation

            yes

            Trip unit technology

            thermal-magnetic

            Earth-leakage protection

            integrated
            Show all specifications
            max9 busbar
            max9 AFDD
            max9 distribution board
            max9 icons