Quantcast

PM5350 Power Meter Withthd. Alarming

PM5350 Power Meter Withthd. Alarming

PM5350 Power Meter Withthd. Alarming

Item Number: METSEPM5350

Datasheet

Product Dimensions

Width icon

Width96 mm

Height icon

Height96 mm

Depth icon

Depth44 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

PowerLogic

Product or component type

power meter

Market segment

  • buildings small building cost management: billing: main incomer
  • buildings small building cost management: billing: sub feeder
  • buildings medium building cost management: billing: main incomer
  • buildings medium building cost management: billing: sub feeder
  • buildings large building cost management: billing: main incomer
  • buildings large building cost management: billing: sub feeder
  • buildings multi-site cost management: billing: main incomer
  • buildings multi-site cost management: billing: sub feeder
  • data center cost management: billing: main incomer
  • data center cost management: billing: sub feeder
  • healthcare cost management: billing: main incomer
  • healthcare cost management: billing: sub feeder
  • industry cost management: billing: main incomer
  • industry cost management: billing: sub feeder
  • buildings small building cost management: cost allocation: main incomer
  • buildings small building cost management: cost allocation: sub feeder
  • buildings medium building cost management: cost allocation: main incomer
  • buildings medium building cost management: cost allocation: sub feeder
  • buildings large building cost management: cost allocation: main incomer
  • buildings large building cost management: cost allocation: sub feeder
  • buildings multi-site cost management: cost allocation: main incomer
  • buildings multi-site cost management: cost allocation: sub feeder
  • data center cost management: cost allocation: main incomer
  • data center cost management: cost allocation: sub feeder
  • healthcare cost management: cost allocation: main incomer
  • healthcare cost management: cost allocation: sub feeder
  • industry cost management: cost allocation: main incomer
  • industry cost management: cost allocation: sub feeder
  • buildings small building network management: main incomer
  • buildings small building network management: sub feeder
  • buildings medium building network management: main incomer
  • buildings medium building network management: sub feeder
  • buildings large building network management: sub feeder
  • buildings multi-site network management: sub feeder
  • data center network management: sub feeder
  • healthcare network management: sub feeder
  • industry network management: sub feeder

Device application

power monitoring

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[In] rated current

  • 5 A
  • 1 A

Communication port protocol

  • JBUS
  • Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds

Connections - terminals

  • voltage circuit: screw terminal block4
  • control circuit: screw terminal block2
  • current transformer: screw terminal block6
  • input/output circuit: screw terminal block6
  • relay output: screw terminal block4
  • Ethernet network: RJ45 connector

Mounting mode

flush-mounted

Type of installation

indoor installation

Standards

IEC 61010-1

Product certifications

  • CE
  • cULus

Width

96 mm

Depth

44 mm

Height

96 mm

Net weight

0.25 kg

IP degree of protection

  • IP30 back: conforming to IEC 60529
  • IP51 front face: conforming to IEC 60529

Relative humidity

0...95 % at 50 °C

Ambient air temperature for operation

-25...70 °C

Ambient air temperature for storage

-40...85 °C

REACh Regulation

Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive

Compliant

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

X

Environmental Disclosure

ENVPEP110336EN

Circularity Profile

ENVEOLI110314EN

California proposition 65

WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov

Others

Package 1 Bare Product Quantity

1

Product name

PowerLogic PM5350

Device short name

PM5350

Power quality analysis

  • total demand distortion
  • total harmonic distortion

Type of measurement

  • current
  • voltage
  • frequency
  • power factor
  • energy
  • phase angle
  • apparent power
  • active power
  • reactive power

[Us] rated supply voltage

  • 85...265 V AC 45...65 Hz
  • 100...300 V DC

Network frequency

  • 50 Hz
  • 60 Hz

Poles description

  • 1P + N
  • 3P + N
  • 3P

Maximum power consumption in VA

9.6 VA

Ride-through time

  • 80 ms 120 V AC typical
  • 100 ms 230 V AC typical
  • 100 ms 415 V AC typical

Display type

backlit LCD

Display resolution

6 lines

Sampling rate

32 samples/cycle

Measurement current

  • 0...1 A
  • 0...5 A

Analogue input type

current 0.05...9 A (impedance <= 0.3="">

Measurement voltage

  • 20...690 V AC phase to phase
  • 20...400 V AC phase to neutral

Frequency measurement range

45...70 Hz

Number of inputs

4 digital

Measurement accuracy

  • current 0.3 %
  • voltage 0.3 %
  • frequency 0.05 %
  • power factor +/- 0.005

Accuracy class

  • class 0.5S active energy conforming to IEC 62053-22
  • class 0.5 active energy conforming to IEC 61557-12
  • class 3 reactive energy conforming to IEC 62053-23
  • class 2 reactive energy conforming to IEC 61557-12
  • class 0.5 power conforming to IEC 61557-12

Number of outputs

2 relay

Information displayed

tariff (4)

Communication port support

terminal block: RS485

Data recording

  • min/max of instantaneous values
  • alarms

Electromagnetic compatibility

  • limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3
  • electrostatic discharge conforming to IEC 61000-4-2
  • susceptibility to electromagnetic fields conforming to IEC 61000-4-3
  • electrical fast transient/burst immunity test conforming to IEC 61000-4-4
  • 1.2/50 µs shock waves immunity test conforming to IEC 61000-4-5
  • conducted RF disturbances conforming to IEC 61000-4-6
  • immunity to impulse waves conforming to IEC 61000-4-12
  • conducted and radiated emissions class A conforming to EN 55011
  • limits for harmonic current emissions conforming to IEC 61000-3-2

Overvoltage category

III

Pollution degree

2

Operating altitude

0...3000 m

Compatibility code

PM5350

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

11.2 cm

Package 1 Width

12.5 cm

Package 1 Length

12.7 cm

Package 1 Weight

358.0 g

Unit Type of Package 2

S03

Number of Units in Package 2

12

Package 2 Height

30.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

4.962 kg

Unit Type of Package 3

P12

Number of Units in Package 3

288

Package 3 Height

105.0 cm

Package 3 Width

80.0 cm

Package 3 Length

120.0 cm

Package 3 Weight

216.0 kg

WEEE

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Technical Leaflet

  • Installation Instruction

  • Environmental Disclosure

  • Operating Manuals

  • Declaration of Conformity

  • Certificates (MSDS)

  • Firmware

Frequently Asked Questions

hide show

Does PM5000 Series Meter have internal battery?

PM5000 Series Meter have internal RTC (Real Time Clock).
The internal battery in the meter keeps its clock running and helps maintain the time even when the meter is powered down.
Battery back-up time - 3 years without control power
The life expectancy of the meter’s internal battery is estimated to be over 10 years at 25 °C under typical operating conditions.

Refer to user manual (Meter Battery) page 188 and 208.
https://www.se.com/au/en/download/document/HRB1684301/

PM5000

Can PM5350 log data and send them ?

PM5350 does not have on-board data logging feature. 

The meter has Modbus serial port and can send data when requested via Modbus. 
However, PM5350 does not log data inside the meter.
Modbus Register Map PM5350 : 
https://www.se.com/au/en/download/document/Public+PM5350+v1.11.0+Register+List/

A data logger such as Com'X is required for data logging.
Refer to the catalogue in the link- https://download.schneider-electric.com/files?p_enDocType=Catalog&p_File_Name=LVCATENLX_EN+%28web%29.pdf&p_Doc_Ref=LVCATENLX_EN

PM5350.png
 

What do asterisks represent in the Power Factor (PF) measurements of the PM5000 power meters?

The Power meter PF measurement display may indicate undefined values as ******. This is due to the calculation of having 0mA when the load is not drawing any current. The Power Factor when calculated is an undefined value (divide by 0) and, therefore, displays as ******.