Frequently Asked Questions

hide show

What are the string size limitations of the Conext CL-NA inverters?

Issue
Engineering/designers doing string design for Conext CL units, and needs to account for any design limitations

Product Line
Conext CL

Environment
Design assistance for the Conext CL

Cause
The Conext CL does have some power limitations per MPPT that can result in damage to the inverter if exceeded.

Resolution
There are three major limits to consider
1. Power - The maximum power of an array for a single MPPT must not exceed 11400W (for the CL 18000NA) or 15900W (for Conext CL 25000NA)
2. Voltage - The PV array open circuit voltage must never exceed 1000Vdc.  This includes temperature compensation.
3. Current - The maximum array short circuit current must never exceed 36.0Adc.  This also includes temperature compensation.

What is the part number for Modena, M8000,1 gang phone outlet( 6 way 4 contact)?

Below mentioned part numbers are needed to put together a Modena, 1 gang phone outlet.
M8031VH  - Assembled Grid and Cover Assemblies with adaptor to suit Clipsal 30 Series Mechanism, 1 Gang.
+
30RJ64SMT - 30 series, Cat 3, 6 way 4 contact socket mechanism "Telephone" (RJ12).
For further information, please visit:
https://www.clipsal.com/Trade/Products/ProductDetail?CatNo=M8031VH
https://www.clipsal.com/Trade/Products/ProductDetail?catno=30RJ64SMT

 

Why is my Conext CL showing an alarm code: 31 (AC Curr Snsr Flt Service Alarm)

Issue: 
Customer is calling to confirm alarm code: 31 (AC Curr Snsr Flt Service Alarm)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

Environment:  
On site troubleshooting

Cause:
AC current sensor doesn’t measure the grid current accurately
Grid connection
Detection circuit malfunction

Resolution: 
Check AC connection on inverter

Why is my Conext CL showing an alarm code:2418 & 2419 (AC UV Slow Err & AC OV Slow Err Service Alarm)

Issue: 
Customer is calling to confirm alarm code:2418 & 2419 (AC UV slow err & AC OV slow err Service)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

Environment:  
On site troubleshooting

Cause:
AC voltage is below (Under Voltage) or above (Over Voltage) the set limits
AC Voltages are not according to the set country or custom setting

Resolution: 
Measure the voltage at the inverter AC connections and check if it is within the country or custom setting limits, adjust if necessary in accordance with utility.

Why is my Conext CL showing an alarm code:8000 (AC Internal Error Service Alarm)

Issue: 
Customer is calling to confirm alarm code:8000 (AC Internal Error Service Alarm)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

Environment:  
On site troubleshooting

Cause:
Grid current measured exceeds unit rating
DC bus voltage outside operational parameters
Internal AC bus voltage too high
Phase lock loop failure during inverting

Resolution: 
Reset unit by turn off both AC and DC
If problem persist replace the unit
 
 

Why is my Conext CL showing an alarm code: 9000 (DC Internal Error Service Alarm)

Issue: 
Customer is calling to confirm alarm code: 9000 (DC Internal Error Service Alarm)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

Environment:  
On site troubleshooting

Cause:
PV current measured exceeds unit rating
Internal DC bus voltage too high
Difference between top or bottom DC bus voltage too high
Dc bus voltage too low
DC voltage sensor measurement failure

Resolution: 
Reset unit by turn off both AC and DC
If problem, persist replace the unit

Why is my Conext CL showing an alarm code: 32 & 33 - AC temp snsr flt & DC temp snsr flt ( AC and DC Temp Sensor Fault Service Alarm)

Issue: 
Customer is calling to confirm alarm code: 32 & 33 ( AC temp snsr flt Service)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

Environment:  
On site troubleshooting
 
Cause:
Abnormal ambient temp
Cooling problem
Detection circuit malfunction

Resolution: 
Check fans, installation conditions, air inlet and outlet
Check Internal temperature displays in STATUS screen
Turn off and on AC breaker
If failure persists, replace the unit

Why is my Conext CL showing an alarm code: 10 - AC relay flt (AC Relay Fault: Service Alarm)

Issue: 
Customer is calling to confirm alarm code: 10 (AC relay flt: Service Alarm)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext cL 25000E

Environment:  
On site troubleshooting

Cause:
AC output relay is either welded or opened  
Abnormal frequent disconnections from the grid that caused premature ageing of the relay

Resolution:  
If the failure persists, replace the inverter

Why is my Conext CL showing an alarm code: 712 & 713 (AC & DC Int Config Fit Service Alarm)

Issue: 
Customer is calling to confirm alarm codes: 712 & 713 (AC&DC Int Config Fit Service Alarm)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext 20000E Conext CL 25000E

Environment:  
On site troubleshooting

Cause:
Internal configuration on control processor is incorrect (firmware issue)

Resolution: 
Reset by turning off DC and AC 
Upgrade the firmware (2.6.4 or newer)
Ensure Bootloader (Control Boot) firmware is 2.02.03 or newer

Why is my Conext CL showing an alarm code: 4661 & 4662 ( PV1&PV2 SPD Service Alarm)

Issue: 
Customer is calling to confirm alarm codes: 4661 & 4662 ( PV1&PV2 SPD Service Alarm) 

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

Environment:  
On site troubleshooting

Cause:
PV1 or PV2 input SPD reached End of Life
SPD remote control wiring issue

Resolution: 
Check the SPD and replace EOL cartridges if required
Check SPD remote wiring 

Why is my Conext CL showing an alarm code: 2102 & 2018 & 2101(DC AC Comm Err / AC Inter-Comm Err / DC Inter-Comm Err Service Alarm)

Issue:  
Customer is calling to confirm alarm codes: 2102 & 2018 & 2101 (DC AC Comm Err / AC Inter-Comm Err / DC Inter-Comm Err Service Alarm)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

Environment:  
On site troubleshooting

Cause:
Communication error between processors
Firmware issue
Internal circuit issue

Resolution: 
Reset by turning off both DC & AC connections
Upgrade firmware to lastest version
If problem persist, replace inverter

Why is my Conext CL showing an alarm code: 2415 (AC OV Avg Err Service Alarm)

Issue
Customer is calling confirming an alarm code: 2415 (AC OV avg err Service)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

Environment:  
On site troubleshooting

Cause:
AC voltage is above (Over Voltage) the set limits during a set period of time 
AC Voltages are not set correctly (country or custom setting) 

Resolution: 
Measure the voltage at the inverter AC connections and check if it is within the country or custom setting limits, adjust if necessary in accordance with utility.
Show More