LZ8H2X4BD

TESYSH Safety Reversing Starter 0.75KW, 0.18...2.4A Control 110-230 VAC

Catalogue Number: LZ8H2X4FU
LZ8H2X4BD
Colour:
Colour: Per UOM Std.
  • 1 PCE
Added to cart
Successfully added, you can view your cart here

Key Features & Specifications

hide show
  • Ultra-compact 22.5mm width, ideal starter solution for control panels where space saving is a priority
  • High electrical life
  • Multifunctional ( forward, reverse, integrated overload protection & safe shutdown)
  • Safety version with Safe Torque Off embedded function ( SIL3 as per IEC61508-1)
Range
TeSys
Product name
TeSys H
Device short name
LZ8H
Product or component type
reversing ultra-compact starter
Motor starter type
direct on line
Poles description
3P
[Ue] rated operational voltage
500 V AC
[Ie] rated operational current
  • 2.4 A at 500 V AC-51
  • 2.4 A at 500 V AC-53A
  • 2.4 A at 500 V AC-51 mounting side by side
  • 2.4 A at 500 V AC-53A mounting side by side
    • Thermal protection adjustment range
      0.18-2.4 A
      Motor power kW
    • 0.37 kW at 220 V AC 0.65
    • 0.37 kW at 230 V AC 0.65
    • 0.75 kW at 380 V AC 0.65
    • 0.75 kW at 400 V AC 0.65
    • 0.75 kW at 415 V AC 0.65
    • 0.75 kW at 440 V AC 0.65
    • 1.1 kW at 500 V AC 0.65
      • Motor power hp
      • 0.5 hp at 200 V AC
      • 0.5 hp at 230 V AC
      • 1 hp at 460 V AC
        • [Uc] control circuit voltage
          110...230 V AC 50/60 Hz
          Safety level
        • SIL 3 conforming to IEC 61508-1 stop function
        • PL = e conforming to ISO 13849-1 stop function
        • SIL 2 conforming to IEC 61508-1 motor protection
          • Safety reliability data
          • SFF = 99 % stop function
          • SFF = 99 % motor protection
          • MTTFd = 289 years stop function
          • MTTFd = 273 years motor protection
          • PFHd = 6.82E-9 1/h stop function
            • Thermal overload class
              class 10A conforming to IEC 60947-4-2
              Auxiliary contact composition
              1 C/O fault signalling
              Control circuit voltage limits
              85...253 V AC
              Current consumption
              <= 4 mA at 110...230 V AC
              Reset
            • manual
            • electrical reset
              • Electrical durability
                30 Mcycles
                Maximum operating rate
              • 120 cyc/mn AC-51 50 % ON
              • 6 cyc/mn AC-53A 50 % ON
                • Mounting mode
                  by clips
                  Mounting support
                  DIN rail
                  Connections - terminals
                • screw clamp terminals 1 cable(s) 0.2-2.5 mm² - rigid
                • screw clamp terminals 1 cable(s) 0.25-2.5 mm² - flexible - with cable end
                • screw clamp terminals 1 cable(s) 0.2-2.5 mm² - flexible - without cable end
                  • Tightening torque
                    0.5-0.6 N.m flat Ø 2.5 mm screwdriver 3 mm
                    Certifications
                  • ATEX as associated device for motor protection in zones 1 and 21
                  • CE
                  • cULus
                    • Standards
                    • UL 60947-4-1
                    • IEC 60947-4-2
                      • [Ui] rated insulation voltage
                        500 V AC 50/60 Hz
                        [Uimp] rated impulse withstand voltage
                        Pollution degree
                        2
                        Width
                        22.5 mm
                        Height
                        99 mm
                        Depth
                        114.5 mm
                        Net weight
                        212 g
                        IP degree of protection
                        IP20
                        Protective treatment
                        TC
                        Ambient air temperature for operation
                      • -25-65 °C without derating
                      • 65-70 °C with derating
                        • Ambient air temperature for storage
                          -40-80 °C
                          Sustainable offer status
                          Green Premium product
                          REACh Regulation
                          Reference contains Substances of Very High Concern above the threshold
                          REACh free of SVHC
                          Yes
                          EU RoHS Directive
                          Compliant
                          Mercury free
                          Yes
                          RoHS exemption information
                          Yes
                          China RoHS Regulation
                          Product out of China RoHS scope. Substance declaration for your information
                          Environmental Disclosure
                          ENVPEP1509013EN
                          Circularity Profile
                          ENVEOLI1509013EN
                          WEEE
                          The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins