TESYSH Safety Direct-on line Starter 0.75KW, 0.18...2.4A Control 24VDC

TESYSH Safety Direct-on line Starter 0.75KW, 0.18...2.4A Control 24VDC

TESYSH Safety Direct-on line Starter 0.75KW, 0.18...2.4A Control 24VDC

Item Number: LZ7H2X4BD

Retail
$573.51
RRP (Inc. GST)

Product Dimensions

Width icon

Width22.5 mm

Height icon

Height99 mm

Depth icon

Depth114.5 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys

Product or component type

ultra-compact starter

Sustainable offer status

Green Premium product

Physical

[Ue] rated operational voltage

500 V AC

[Ie] rated operational current

  • 2.4 A at 500 V AC-51
  • 2.4 A at 500 V AC-53A
  • 2.4 A at 500 V AC-51 mounting side by side
  • 2.4 A at 500 V AC-53A mounting side by side
    • Electrical durability

      30 Mcycles

      Mounting mode

      by clips

      Mounting support

      DIN rail

      Connections - terminals

    • screw clamp terminals 1 cable(s) 0.2-2.5 mm² - rigid
    • screw clamp terminals 1 cable(s) 0.25-2.5 mm² - flexible - with cable end
    • screw clamp terminals 1 cable(s) 0.2-2.5 mm² - flexible - without cable end
      • Standards

      • IEC 60947-4-2
      • UL 60947-4-1
        • Width

          22.5 mm

          Height

          99 mm

          Depth

          114.5 mm

          Net weight

          212 g

          IP degree of protection

          IP20

          Ambient air temperature for operation

          -25-70 °C without derating

          Ambient air temperature for storage

          -40-80 °C

          REACh free of SVHC

          Yes

          EU RoHS Directive

          Compliant

          Toxic heavy metal free

          Yes

          Mercury free

          Yes

          RoHS exemption information

          Yes

          China RoHS Regulation

          X

          Environmental Disclosure

          ENVPEP1509013EN

          Circularity Profile

          ENVEOLI1509013EN

          Others

          Product name

          TeSys H

          Device short name

          LZ7H

          Motor starter type

          direct on line

          Poles description

          3P

          Thermal protection adjustment range

          0.18-2.4 A

          Motor power kW

        • 0.37 kW at 220 V AC 0.65
        • 0.37 kW at 230 V AC 0.65
        • 0.75 kW at 380 V AC 0.65
        • 0.75 kW at 400 V AC 0.65
        • 0.75 kW at 415 V AC 0.65
        • 0.75 kW at 440 V AC 0.65
        • 1.1 kW at 500 V AC 0.65
          • Motor power hp

          • 0.5 hp at 200 V AC
          • 0.5 hp at 230 V AC
          • 1 hp at 460 V AC
            • [Uc] control circuit voltage

              24 V DC

              Safety level

            • SIL 3 conforming to IEC 61508-1 stop function
            • PL = e conforming to ISO 13849-1 stop function
            • SIL 2 conforming to IEC 61508-1 motor protection
              • Safety reliability data

              • MTTFd = 517 years stop function
              • SFF = 99 % stop function
              • SFF = 99 % motor protection
              • MTTFd = 447 years motor protection
              • PFHd = 2.40E-9 1/h stop function
                • Thermal overload class

                  class 10A conforming to IEC 60947-4-2

                  Auxiliary contact composition

                  1 C/O fault signalling

                  Control circuit voltage limits

                  19.2...30 V DC

                  Current consumption

                  <= 40 mA at 24 V DC

                  Reset

                • manual
                • electrical reset
                  • Maximum operating rate

                  • 120 cyc/mn AC-51 50 % ON
                  • 6 cyc/mn AC-53A 50 % ON
                    • Tightening torque

                      0.5-0.6 N.m flat Ø 2.5 mm screwdriver 3 mm

                      Certifications

                    • CE
                    • cULus
                    • ATEX as associated device for motor protection in zones 1 and 21
                      • [Ui] rated insulation voltage

                        500 V AC 50/60 Hz

                        [Uimp] rated impulse withstand voltage

                        Pollution degree

                        2

                        Protective treatment

                        TC

                        Unit Type of Package 1

                        PCE

                        Number of Units in Package 1

                        1

                        Package 1 Weight

                        254 g

                        Package 1 Height

                        3.6 cm

                        Package 1 width

                        11.7 cm

                        Package 1 Length

                        12 cm

                        Unit Type of Package 2

                        S01

                        Number of Units in Package 2

                        10

                        Package 2 Weight

                        2.711 kg

                        Package 2 Height

                        15 cm

                        Package 2 width

                        15 cm

                        Package 2 Length

                        40 cm

                        WEEE

                        The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                        Show all specifications