Specifications

hide show
Range of product
TeSys D
Range
TeSys
Product or component type
contactor coil
Device short name
LXD3
Control circuit type
AC at 50/60 Hz
[Uc] control circuit voltage
42 V AC 50/60 Hz
Average resistance
6.18 Ohm at 20 °C
Inductance of closed circuit
0.37 H
Product compatibility
  • LC1DT60A
  • LC1DT80A
  • LC1D40A...D65A
    • Mechanical durability
      6 Mcycles
      Maximum operating rate
      3600 cyc/h 60 °C
      Coil technology
      without built-in suppressor module
      Control circuit voltage limits
    • drop-out: 0.3...0.6 Uc at 50/60 Hz (at <60 °C)
    • operational: 0.8...1.1 Uc at 50 Hz (at <60 °C)
    • operational: 0.85...1.1 Uc at 60 Hz (at <60 °C)
      • Inrush power in VA
      • 160-160 VA 60 Hz cos phi 0.75 (at 20 °C)
      • 160-160 VA 50 Hz cos phi 0.75 (at 20 °C)
        • Hold-in power consumption in VA
        • 15-15 VA 60 Hz cos phi 0.3 (at 20 °C)
        • 15-15 VA 50 Hz cos phi 0.3 (at 20 °C)
          • Heat dissipation
            4-5 W at 50/60 Hz
            Ambient air temperature for operation
            -5-60 °C
            Net weight
            0.07 kg
            Sustainable offer status
            Green Premium product
            REACh Regulation
            Free of Substances of Very High Concern above the threshold
            REACh free of SVHC
            Yes
            EU RoHS Directive
            Pro-active compliance (Product out of EU RoHS legal scope)
            Toxic heavy metal free
            Yes
            Mercury free
            Yes
            RoHS exemption information
            Yes
            China RoHS Regulation
            X
            Environmental Disclosure
            ENVPEP1503009EN
            Circularity Profile
            ENVEOLI1503009EN
            Warranty
            18 months

            Documents & downloads

            hide show
            Filter items
            • All

            • Product Brochures

            • Technical Data Catalogues

            • Installation Instruction

            Frequently Asked Questions

            hide show

            What the DC current contact ratings for the CAD50, CAD32, CAD503, CAD323, CAD506, and CAD326 relay?

            Issue:
            Checking on the DC current contact ratings for the CAD50, CAD32, CAD503,  CAD323,  CAD506, and  CAD326 relay.

            Product Line:
            CAD Industrial Relays

            Environment:
            Relays and Timers

            Resolution:
            Inductive:
            125V DC - 0.55 Amps make and break, 2.5 Amps cont.
            250V DC - 0.27 Amps make and break, 2.5 amps cont.
            600V DC - 0.10 Amps make and break, 2.5 Amps cont.

             

            What is the replacement AC coil for CAD32 and CAD50 relay?

            Issue:
            AC coil replacement for CAD32 and CAD50

            Product Line:
            Relays

            Environment:
            Tesys CAD Control Relays

            Cause:
            Product selection

            Resolution:
            Volt = coil part number
            12 = LXD1J7
            21 = LXD1Z7
            24 = LXD1B7
            32 = LXD1C7
            36 = LXD1CC7
            42 = LXD1D7
            48 = LXD1E7
            60 = LXD1EE7
            100 = LXD1K7
            110 = LXD1F7
            115 = LXD1FE7
            120 = LXD1G7
            127 = LXD1FC7
            200 = LXD1L7
            208 = LXD1LL7
            220/230 = LXD1M7
            230 595 21 LXD1P7
            230/240 = LXD1U7
            277 781 30 LXD1W7
            380/400 = LXD1Q7
            400 = LXD1V7
            415 = LXD1N7
            440 = LXD1R7
            480 = LXD1T7
            600 = LXD1X7
            690 = LXD1Y7

             

            What is the spare 48VAC coil for an LC1D40A contactor?

            LXD3E7

            What is the code for a 415VAC coil for a LC1D40A Contactor?

            The 415V coil is LXD3N7

            What is the spare coil for LC1D09U7 contactor

             The spare coil is LXD1U7

            What is the coil for an LC1D18 contactor

             The coil is an LXD1U7

            What is the code for a spare coil for LC1D32B7

            LXD1B7

            What is the spare coil for LC1D32 240V?

              LXD1U7

            240VAC spare coil for LC1D18U7 Contactor?


            Code = Lxd1u7

            What is the code for a 415V coil only for LC1D18 contactor?

            LXD1N7 is the code.

            What is the code for a 48VAC Coil for Conatactors sized LC1D09- LC1D38 ?

            Code = LXD1E7

            What is the code for a 24 v ac coil to suit a LC1D32 contactor?

            LXD1B7 is the code for the 24VAC coil for contactors LC1D09...38.

            The code for complete contactor + 24VAC coil is LC1D32B7
            Show More