Spare Coils

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D

Range

TeSys

Product or component type

contactor coil

Product compatibility

  • LC1D150
  • LC1D115
    • Warranty

      18 months

      Physical

      Mechanical durability

      8 Mcycles

      Ambient air temperature for operation

      -5-60 °C

      Net weight

      0.3 kg

      Others

      Device short name

      LX4D8

      Control circuit type

      DC standard

      [Uc] control circuit voltage

      48 V DC

      Average resistance

      1061 Ohm at 20 °C

      Inductance of closed circuit

      24.19 H

      Maximum operating rate

      1200 cyc/h 60 °C

      Coil technology

      without built-in suppressor module

      Control circuit voltage limits

    • operational: 0.75...1.2 Uc (at <55 °C)
    • drop-out: 0.15...0.4 Uc (at <55 °C)
      • Time constant

        25 ms

        Inrush power in W

        270-365 W (at 20 °C)

        Hold-in power consumption in W

        2.4-5.1 W at 20 °C

        Unit Type of Package 1

        PCE

        Number of Units in Package 1

        1

        Package 1 Weight

        300 g

        Package 1 Height

        6.2 cm

        Package 1 width

        11.5 cm

        Package 1 Length

        17 cm
        Show all specifications

        Documents & downloads

        hide show
        Filter items
        • All

        • Product Brochures

        • Technical Data Catalogues

        • Product Environmental

        Frequently Asked Questions

        hide show

        What is the replacement AC coil for LC1D/LC2D40, D50, D65, D80, and D95?

        Issue:
        AC Coil information for LC1D/LC2D40, D50, D65, D80, and D95

        Product Line:
        Tesys D Replacement Parts

        Environment:
        TeSys™ D AC Coils

        Resolution:

        Is 240 volt replacement control coil available for LC1D11500?

        Issue:
        Identifying replacement coil part number

        Product Line:
        IEC contactors and starters

        Environment:
        Products sold and used in the United States

        Cause:
        Replacement control coil needed for older style Tesys Contactor

        Resolution:
        Yes, order LX1D8U5 for 50 hertz, LX1D8U6 for 60 hertz or LX1D8U7 for 50/60 hertz. Average coil consumption is 300 VA inrush 22 VA sealed for 50 hertz, 300 VA inrush 22 VA sealed for 60 hertz and 280 to 350 VA inrush 2 to 18 VA sealed for 50/60 hertz.


        CTA-ID : 11321

        What do the LA4D timing modules require for mounting on LC1D40A through LC1D65A contactors?

        Product Line:
         
        Tesys D line Contactors and Accessories

        Resolution:
         
        Mounting this module to TeSys LC1D40A through LC1D65A contactor requires the use of the LAD4BB3 wiring adaptor. This adaptor can be fitted only to contactors with no coil suppressor.
         

        What is the 240v coil to fit an LC1D1506

         The 240v coil is an LX1D8U7

        What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

        Issue:
        Identifying maximum voltage of an LC1D contactor

        Product Line:
        TeSys D Contactors

        Environment:
        IEC contactors and starters used in North America

        Cause:
        n/a

        Resolution:
        IThe maximum voltage per UL and CSA is 600VAC. 
         

        What is the altitude derating for a TeSys D-Line contactor?

        Issue:​
        What is the altitude derating for a TeSys D-Line contactor?

        Product Line:
        Digest 177 Section 18 : Contactors and Starters, IEC

        Environment:
        North American Products

        Resolution:
        The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

        Voltage
        3500m x 0.90
        4000m x 0.80
        4500m x 0.70
        5000m x 0.60

        Current
        3500m x 0.92
        4000m x 0.90
        4500m x 0.88
        5000m x 0.86

        For example, an LC1D80 at 5000 meters:
        - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
        - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



         

        Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

        Issue:
        Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

        Product Line: 
        Tesys D Contactors

        Environment:
        IEC contactors

        Resolution:
        The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
         

        Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

        Issue:
        Mounting adaptor for GV2 and LC1D contactor

        Product Line:
        Motor Starters and Protectors

        Environment:
        TeSys GV Manual Starter and Protectors
        Tesys D Contactors
         
        Resolution:
        The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.